START UP

IMPORTANT INSTALLER NOTE

For improved start up performance, wash the indoor coil
with a dishwasher detergent.

SERVICE HINTS

1. Caution owner to maintain clean air filters at all

times.  Also not to needlessly close off supply and
return air registers.  This reduces airflow through the
system which shortens equipment service life as well
as increasing operation costs.

2. The unit is equipped with a high pressure cut out

switch.

3. Check all power fuses or circuit breakers to be sue

they are the correct rating.

4. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

HIGH PRESSURE SWITCH

The WA121 models are supplied with a remote reset
high pressure switch.  If tripped, this pressure switch may
be reset by turning the thermostat off then back on again.

SEQUENCE OF OPERATION

COOLING

 – Circuit R-Y makes at thermostat pulling in

compressor contactor, starting the compressor and
outdoor motor.  The G (indoor motor) circuit is
automatically completed on any call for cooling
operation or can be energized by manual fan switch on
subbase for constant air circulation.  On a call for
heating, circuit R-W1 make at the thermostat pulling in
heat contact for the strip heat and blower operation.

COMPRESSOR CONTROL MODULE

The compressor control module is optional on the models
covered by this manual.  The compressor control is an
anti-short cycle/lockout timer with high and low pressure
switch monitoring and alarm relay output.

Adjustable Delay on Make and Break Timer

On initial power up or any time power is interrupted to
the unit the 

delay on make

 period begins, which will be 2

minutes plus 10% of the 

delay on break

 setting.  When

the delay on make is complete and the high pressure
switch (and low pressure switch if employed) is closed,
the compressor contactor is energized.  Upon shutdown
the delay on break time starts and prevents restart until
the delay on break and delay on make periods have
expired.

During routine operation of the unit with no power
interruptions the compressor will operate on demand with
no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a 

soft lockout

 and stay in soft lockout

until the high pressure switch closes 

and

 the delay on

break time has expired.  If the high pressure switch opens
again in this same operating cycle the unit will go into
manual lockout condition and the alarm relay circuit will
energize.  Recycling the wall thermostat resets the manual
lockout.

Low Pressure Switch, Bypass  and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.  Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
that 120 seconds, the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is powered
whenever compressor is locked out due to HPC or LPC
sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The lockout
features, both soft and manual, are a function of
the Compressor Control Module.

Содержание WA121

Страница 1: ...PACKAGE AIR CONDITIONERS Model WA121 INSTALLATION INSTRUCTIONS Manual 2100 234I Supersedes 2100 234H File Volume III Tab 16 Date 08 01 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Mo...

Страница 2: ...nsion 16 Refrigerant Charge 16 Pressure Tables 17 Option Field Installed Accessories 17 Figures Figure 1 Unit Dimensions 5 Figure 2 Blower Damper Assembly 7 Figure 3 Mounting Instructions 9 Figure 4 W...

Страница 3: ...esign for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hamps...

Страница 4: ...0 8 0 1 5 0 8 0 2 0 4 5 7 1 1 8 1 5 7 2 3 1 1 d e d u l c n i s t t a w r e w o l b h t i W WA 12 1 A 00 X X X X X J MODEL NUMBER REVISIONS CONTROL MODULES E Low Ambient Control J Telecommunication VO...

Страница 5: ...Manual 2100 234I Page 5 of 17 FIGURE 1 UNIT DIMENSIONS FACTORY BUILT AT 5 INCHES...

Страница 6: ...Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Vent...

Страница 7: ...service door A 2 inch pleated filter is also available as an optional accessory The internal filter brackets are adjustable to accommodate the 2 inch filter by bending the metal tabs holding the 1 in...

Страница 8: ...unit a different size wall opening is required 2 Locate and mark lag bolt locations if desired See Figure 3 3 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the...

Страница 9: ...Manual 2100 234I Page 9 of 17 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 10: ...Manual 2100 234I Page 10 of 17 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 11: ...Manual 2100 234I Page 11 of 17 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 12: ...T E G N A R 0 4 2 3 5 2 6 1 2 8 0 2 0 2 2 7 8 1 NOTE The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load maximum amperage operat...

Страница 13: ...Manual 2100 234I Page 13 of 17 FIGURE 7 LOW VOLTAGE WIRING...

Страница 14: ...ke is complete and the high pressure switch and low pressure switch if employed is closed the compressor contactor is energized Upon shutdown the delay on break time starts and prevents restart until...

Страница 15: ...38 second DOM 4 0 minute 240 seconds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand...

Страница 16: ...9 o D O e r u t a r e p m e T 2 8 o D O e r u t a r e p m e T 1 2 1 A W 0 0 4 6 5 4 5 7 6 5 6 TABLE 6 SUCTION LINE TEMPERATURE The suction line temperatures in Table 6 are based upon 80 F dry bulb 67...

Страница 17: ...7 2 9 1 9 7 7 0 2 2 8 2 2 2 4 8 8 3 2 7 8 5 5 2 0 9 2 7 2 2 9 0 9 2 5 9 9 0 3 7 9 8 2 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 8 8 9 1 5 8 4 1 2 8 8 0 3 2 1 9 7 4 2 4 9 4 6 2 7 9...

Отзывы: