TABLE 6 

Cooling Pressure

Air Temperature Entering Outdoor Coil °F

Low side pressure ± 4 PSIG                                                         
High side pressure ± 10 PSIG

Tables are based upon rated CFM (airflow) across the evaporator coil.  If there is any doubt as to correct operating 
charge being in the system, the charge should be removed and system evacuated and recharged to serial plate 
charge weight.

NOTE:

  Pressure table based on high speed condenser fan operation.  If condensing pressures appear elevated 

check condenser fan wiring.  See “Condenser Fan Operation”.

Model

Return Air Temp 

(DB/WB)

Pressure

75

80

85

90

95

100

105

110

115

120

125

W18A/L

75/62

Low Side

High Side

121
293

123
312

126
332

128
353

131
376

134
400

136
425

137
452

140
480

142
510

144
540

80/67

Low Side

High Side

129
300

132
320

135
340

137
362

140
386

143
410

145
436

147
464

150
492

152
523

154
554

85/72

Low Side

High Side

134
311

137
331

140
352

142
375

145
400

148
424

150
451

152
480

155
509

157
541

159
573

W24A/L

75/62

Low Side

High Side

123
314

124
334

126
355

128
377

129
401

131
425

133
451

135
479

137
507

139
536

141
567

80/67

Low Side

High Side

132
322

133
343

135
364

137
387

138
411

140
436

142
463

144
491

146
520

149
550

151
582

85/72

Low Side

High Side

137
333

138
355

140
377

142
401

143
425

145
451

147
479

149
508

151
538

154
569

156
602

W30A/L

75/62

Low Side

High Side

118
312

120
333

122
355

124
378

126
403

128
428

131
454

133
483

135
511

137
540

138
570

80/67

Low Side

High Side

126
320

128
342

131
364

133
388

135
413

137
439

140
466

142
495

144
524

146
554

148
585

85/72

Low Side

High Side

130
331

132
354

136
377

138
402

140
427

142
454

145
482

147
512

149
542

151
573

153
605

W36A/L

75/62

Low Side

High Side

117
323

120
346

122
370

124
394

127
419

129
446

131
473

134
500

136
528

137
558

138
587

80/67

Low Side

High Side

125
331

128
355

130
379

133
404

136
430

138
457

140
485

143
513

145
542

147
572

148
602

85/72

Low Side

High Side

129
343

132
367

135
392

138
418

141
445

143
473

145
502

148
531

150
561

152
592

153
623

W42A/L

75/62

Low Side

High Side

123
323

125
346

128
371

130
395

132
421

135
447

137
474

138
501

140
528

142
558

144
587

80/67

Low Side

High Side

132
331

134
355

137
380

139
405

141
432

144
458

146
486

148
514

150
542

152
572

154
602

85/72

Low Side

High Side

137
343

139
367

142
393

144
419

146
447

149
474

151
503

153
532

155
561

157
592

159
623

W48A/L

75/62

Low Side

High Side

120
330

122
353

125
377

127
402

130
428

132
454

134
482

136
510

137
540

139
570

141
601

80/67

Low Side

High Side

128
338

131
362

134
387

136
412

139
439

141
466

143
494

145
523

147
554

149
585

151
616

85/72

Low Side

High Side

132
350

136
375

139
401

141
426

144
454

146
482

148
511

150
541

152
573

154
605

156
638

W60A/L

75/62

Low Side

High Side

127
344

129
362

131
380

134
401

136
421

137
444

140
467

142
492

145
518

148
545

151
573

80/67

Low Side

High Side

136
353

138
371

140
390

143
411

145
432

147
455

150
479

152
505

155
531

158
559

161
588

85/72

Low Side

High Side

141
365

143
384

145
404

148
425

150
447

152
471

155
496

157
523

160
550

164
579

167
609

W72A/L

75/62

Low Side

High Side

117
332

119
353

121
376

122
402

124
427

126
454

128
483

130
512

132
542

134
574

136
607

80/67

Low Side

High Side

125
340

127
362

129
386

131
412

133
438

135
466

137
495

139
525

141
556

143
589

145
623

85/72

Low Side

High Side

129
352

131
375

134
400

136
426

138
453

140
482

142
512

144
543

146
575

148
610

150
645

Содержание W60LB-A

Страница 1: ...io 43506 www bardhvac com Manual 2100 640I Supersedes 2100 640H Date 10 3 18 W18LA A W24LA A W24LA B W24LA F W30LA A W30LA B W30LA C W30LA F W36LA A W36LA B W36LA C W36LA F W42LA A W42LA B W42LA C W42LA F W48LA A W48LA B W48LA C W48LA F W60LB A W60LB B W60LB C W60LB F W72LB A W72LB B W72LB C W72LB F W48AA C W48AA E W48AA F W60AB A W60AB B W60AB C W60AB E W60AB F W72AB A W72AB B W72AB C W72AB F W30...

Страница 2: ...Recommended Airflow 28 Table 10 Indoor Blower Performance 28 Table 11 Maximum ESP Electric Heat Only 28 Table 12 Electric Heat 29 Table 13 Vent and Control Options 30 Table 14A Optional Accessories Right Hand 31 Table 14B Optional Accessories Left Hand 32 Getting Other Information and Publications 3 Wall Mount General Information 4 Air Conditioner Wall Mount Model Nomenclature 4 Shipping Damage 4 ...

Страница 3: ...Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Telephone ...

Страница 4: ...recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be inst...

Страница 5: ...ir Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable installation codes may limit this cabinet to installation only in a single story structure FILTE...

Страница 6: ...unit MOUNTING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is provided for ease of installation but is not required 2 The supply air duct flange and the first 3 of supply air duct require a minimum of 1 4 clearance to combustible material for model series W30 W36 ...

Страница 7: ... Q R S S S 44 E T B N L Disconnect Rain Hood Built In Lockable Low Voltage Access Panel Entrance Heater Electrical Entrance Access Cond Inlet Panel Air Electrical High Voltage Drain Side View 4 Pitch C Breaker Hood for CRV and ECON models only 1 250 2 13 A I D J C H K 7 00 MIS 3736 Electric Heat Ventilation Air Front View Air Outlet Condenser Filter Access Panel Standard flush vent door for non ER...

Страница 8: ...CAULKING ALONG PANEL FOAM AIR SEAL DUCT RAIN FLASHING HEATER ACCESS MIS 3157 A Wall Opening and Hole Location View Right Side View RETURN AIR TOP FLASHING AT TIME OF INSTALLATION OPENING THE SIDE MOUNTING FLANGES AND UNDER SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHIND SUPPLY AIR SUPPLIED Return Opening Supply Opening J A UNIT SHOWN J L UNIT CONTROLS AND HEATER ...

Страница 9: ...PLY AIR DUCT IS REQUIRED FROM COMBUSTABLE MATERIALS RAIN FLASHING TOP SUPPLY AIR OPENING Right Side View HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD OF WALL Wall Opening and Hole Location View 17 5 8 4 5 8 16 7 8 8 3 8 A 9 7 8 29 7 8 Return Opening 4 7 16 3 11 16 1 4 MIN CLEARANCE FROM 28 3 8 E D 5 3 8 B COMBUSTIBLE MATERIALS C RECOMMENDED 1 CLEA...

Страница 10: ...29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION TOP PANEL HEATER ACCESS FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE WALL 1 4 CLEARANCE ON ALL MATERIALS Supply Opening FOA...

Страница 11: ...FROM COMBUSTIBLE MATERIALS REQUIRED DIMENSIONS TO MAINTAIN OPENING COMBUSTIBLE MATERIALS B D E PANEL AIR DUCT IS REQUIRED 32 10 1 2 Right Side View SUPPLY AIR RECOMMENDED 1 CLEARANCE FROM MIS 3789 RAIN FLASHING REQUIRED DIMENSIONS TO MAINTAIN 12 TOP MATERIALS 5 1 2 WALL STRUCTURE 2 6 1 4 29 29 3 4 IT IS RECOMMENDED THAT A BEAD OF THE SIDE MOUNTING FLANGES AND UNDER WALL C Wall Opening and Hole Loc...

Страница 12: ...pply air duct and combustible materials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death NOTE 1 SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 CLEARANCE TO COMBUSTIBLE SU...

Страница 13: ...TORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRUCTURAL STEEL ATTACH TO TOP 1 000 CLEARANCE 1 000 CLEARANCE PLATE OF WALL C SEE UNIT DIMENSIONS FIGURE 2 OPENING RETURN DUCT 2 x 6 ATTACH TO BOTTOM OVER FRAME PLATE ...

Страница 14: ...TIC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSASSHOWN FINISHEDCEILING WALL CLOSETWALL SURFACE OPENINGW GRILLE SLEEVE ORBELOWCEILINGRAFTERSASSHOWN SUPPLYAIRDUCT OUTSIDE WALLSLEEVE SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSASSHOWN FINISH...

Страница 15: ...G All 230 208V 1 phase and 3 phase equipment have dual primary voltage transformers All equipment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptable operating voltage range for the 240 and 208V taps are TAP RANGE 240 253 216 208 220 187 NOTE The voltage should be measured at the field power connection point in the unit and while the unit is opera...

Страница 16: ...3 stage Heat Electronic Programmable Non Programmable HP or Conventional Auto or Manual changeover Dehumidification Output CS9B THO 3 stage Cool 3 stage Heat Programmable Non Programmable HP or Conventional Auto or Manual Changeover Humidity Sensor w dehumidification Motion Sensor w Intelligent Learning Control BACnet compatible CS9B THOC 3 stage Cool 3 stage Heat Programmable Non Programmable HP ...

Страница 17: ...programmable and fan set to be programmed fan for the A output to function during scheduled occupied periods Must be configured for multi stage for Y1 output to be active 1st stage cooling For dehumidification must be configured for No Economizer for YO D to be active for humidity control 4 Factory installed jumper Remove jumper and connect to N C fire alarm circuit if emergency shutdown required ...

Страница 18: ...Only See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while blower is energized 4 Factory installed jumper Remove jumper and connect to N C fire alarm circuit if emergency shutdown required 3 Wire not needed below 15KW 2A Wire required for dehumidification models only 1 Thermostat will not work with units equipped with economizers 9 ...

Страница 19: ...to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrigerant it must come out of the charging cylinder tank as a liquid to avoid any f...

Страница 20: ...gnal is present at the phase monitor and phases are correct the green LED will light If phases are reversed the red fault LED will be lit and compressor operation is inhibited If a fault condition occurs reverse two of the supply leads to the unit Do not reverse any of the unit factory wires as damage may occur CONDENSER FAN OPERATION NOTE Certain models may be equipped with a low ambient control ...

Страница 21: ...rgize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize Recycling the wall thermostat resets the manual lockout Alarm Relay Output Alarm terminal is output connection for applications where alarm relay is employed This terminal is ...

Страница 22: ...13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock back and forth on start up Do not replace the motor if this is the only problem identified 2 If the system is excessively noisy does not appear to change speeds in response to a demand Heat Cool Other or is having...

Страница 23: ...or is failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground at the L L1 G N L2 connections then continue with the Model SelecTech Communication Diagnostics Model SelecTech Communication Diagnostics The SelecTech motor is communicated through 24 VAC low voltage...

Страница 24: ...charge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove nine screws holding fan shroud to condenser and bottom 4 Unwire condenser fan motor 5 Slide complete motor fan blade and shroud assembly out the left side of the unit 6 Service motor fan as needed 7 Reverse steps to reinstall A AIRFLOW MIS 17...

Страница 25: ...138 402 140 427 142 454 145 482 147 512 149 542 151 573 153 605 W36A L 75 62 Low Side High Side 117 323 120 346 122 370 124 394 127 419 129 446 131 473 134 500 136 528 137 558 138 587 80 67 Low Side High Side 125 331 128 355 130 379 133 404 136 430 138 457 140 485 143 513 145 542 147 572 148 602 85 72 Low Side High Side 129 343 132 367 135 392 138 418 141 445 143 473 145 502 148 531 150 561 152 59...

Страница 26: ...58 26 60 30 6 10 10 10 W30AA B00 B0Z B06 B09 B15 230 208 3 1 1 1 1 19 24 33 51 20 25 35 60 12 10 8 6 12 10 10 10 W30AA C00 C0Z C06 C09 C12 C15 460 3 1 1 1 1 1 9 12 17 21 26 15 15 20 25 30 14 14 12 10 10 14 14 12 10 10 W36AA A00 A0Z A05 A08 A10 A15 230 208 1 1 1 1 1 1 or 2 29 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 W36AA B00 B0Z B06 B09 B15 230 208 3 1 1 1 1 23 24 ...

Страница 27: ...C0Z C06 460 3 1 1 9 11 15 15 14 14 14 14 W30LA A00 A0Z A05 A08 A10 A15 230 208 1 1 1 1 1 1 or 2 26 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 W30LA B00 B0Z B09 B15 230 208 3 1 1 1 19 33 51 20 35 60 12 8 6 12 10 10 W30LA C00 C0Z C09 C15 460 3 1 1 1 9 17 26 15 20 30 14 12 10 14 12 10 W36LA A00 A0Z A05 A10 A15 230 208 1 1 1 1 1 or 2 29 32 58 84 35 35 60 90 8 8 6 4 10 10...

Страница 28: ... 1940 1750 1700 2105 2010 1540 1460 2255 2155 2075 2015 1995 1930 0 1 965 950 700 690 960 925 1385 1320 930 920 1340 1260 940 930 1905 1880 1700 1640 1910 1865 1675 1615 2045 1960 1480 1395 2185 2095 2010 1965 1950 1870 0 2 935 900 665 660 905 870 1305 1240 920 910 1265 1185 905 890 1820 1760 1615 1565 1820 1770 1600 1540 1970 1885 1400 1315 2115 2035 1960 1915 1885 1825 0 3 880 845 635 625 835 80...

Страница 29: ...H Amps BTUH Amps BTUH Amps BTUH 4 16 7 13650 14 4 10240 5 20 8 17065 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 8 33 3 27300 28 8 20475 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 12 14 4 40950 15 62 5 51250 54 0 38400 36 2 51200 31 2 38400 18 0 51200 18 43 3 61430 37 5 46100 20 83 2 68260 72 1 51200 ...

Страница 30: ...ntilator 460 Volt X BFAD 3 Barometric Fresh Air Damper Standard X BOP 3 Blank Off Plate X WMFADP3 Motorized Fresh Air Damper X WCRVPS3 Commercial Ventilator Spring Return X WECOPE3 WECOPT3 Economizer Bldg Equipment Enthalpy Economizer Bldg Equipment DB Temp X X WERVPA3 Energy Recovery Ventilator 230 Volt X WERVPC3 Energy Recovery Ventilator 460 Volt X BFAD 5 Barometric Fresh Air Damper Standard X ...

Страница 31: ...HW3TA B06 X EHW3TA B09 X X EHW3TA B15 X X EHW3TA C06 X X EHW3TA C09 X X EHW3TA C12 X X EHW3TA C15 X X EHW4TA A05 X X EHWA05 A10B X X X EHWA05 A15B X X X EHWA05 A20B X X X EHW4TA B06 X X X EHWA05 B09B X X EHW6TA B06 X EHWA05 B15B X X X X EHW5TA B18 X EHW4TA B18 X X EHW4TA C09 X X X X EHW4TA C15 X X X X EHW5TA A05 X X EHW60A B09B X EHW70A B09B X EHW6TA B18 X EHW72A A10B X EHW72A A15B X EHW72A A20B X...

Страница 32: ...A A10L X X EHW3TA A15L X X EHW3TA B09L X X EHW3TA B15L X X EHW3TA C09L X X EHW3TA C15L X X EHW4TA A05L X X X EHWA05 A10LB X X X EHWA05 A15LB X X X EHW4TA B06L X X X EHWA05 B09LB X X EHW6TA B06L X EHWA05 B15LB X X X X EHW4TA C09L X X X X EHW4TA C15L X X X X EHW6TA A05L X EHWA60 B09LB X EHW70A B09LB X EHW72A A10LB X EHW72A A15LB X WMCB 01B X WMCB 02A X WMCB 02B X WMCB 03A X WMCB 04B X WMCB 05A X X W...

Отзывы: