background image

Manual 2100-594 

Page  14 of 19

START UP

THESE UNITS REQUIRE R-410A 
REFRIGERANT AND POLYOL 
ESTER OIL.

GENERAL:

1.  Use separate service equipment to avoid cross    
 

contamination of oil and refrigerants.

2.  Use recovery equipment rated for R-410A  

 

 refrigerant.

3.  Use manifold gauges rated for R-410A (800 psi/250  
 

psi low).

4.  R-410A is a binary blend of HFC-32 and HFC-125.

5.  R-410A is nearly azeotropic - similar to R-22 and  
 

R-12.  Although nearly azeotropic, charge with   

 

liquid refrigerant.

6.  R-410A operates at 40-70% higher pressure than   
 

R-22, and systems designed for R-22 cannot  

 

 

withstand this higher pressure.

7.  R-410A has an ozone depletion potential of zero,  
 

but must be reclaimed due to its global warming  

 potential.

8.  R-410A compressors use Polyol Ester oil.

9.  Polyol Ester oil is hygroscopic; it will rapidly    
 

absorb moisture and strongly hold this moisture in  

 

the oil.

10. A liquid line dryer must be used - even a deep    
 

vacuum will not separate moisture from the oil.

11. Limit atmospheric exposure to 15 minutes.

12. If compressor removal is necessary, always plug  
 

compressor immediately after removal.  Purge with  

 

small amount of nitrogen when inserting plugs.

TOPPING OFF SYSTEM CHARGE

If a leak has occurred in the system, Bard 
Manufacturing recommends reclaiming, evacuating 
(see criteria above), and charging to the nameplate 
charge.  If done correctly, topping off the system charge 
can be done without problems.

With R-410A, there are no significant changes in the 

refrigerant composition during multiple leaks and 
recharges.  R-410A refrigerant is close to being an 
azeotropic blend (it behaves like a pure compound 
or single component refrigerant).  The remaining 
refrigerant charge, in the system, may be used after 
leaks have occurred and then “top-off” the charge by 
utilizing the pressure charts on the inner control panel 
cover as a guideline.

REMEMBER:  

When adding R-410A refrigerant, it 

must come out of the charging cylinder/tank as a liquid 
to avoid any fractionation, and to insure optimal system 
performance.  Refer to instructions for the cylinder that 
is being utilized for proper method of liquid extraction.

SAFETY PRACTICES:

1.  Never mix R-410A with other refrigerants.

2.  Use gloves and safety glasses, Polyol Ester oils can  
 

be irritating to the skin, and liquid refrigerant will  

 

freeze the skin.

3.  Never use air and R-410A to leak check; the  

 

 

mixture may become flammable.

4.  Do not inhale R-410A – the vapor attacks the    
 

nervous system, creating dizziness, loss of  

 

 

coordination and slurred speech.  Cardiac  

 

 

irregularities, unconsciousness and ultimate death  

 

can result from breathing this concentration.

5.  Do not burn R-410A.  This decomposition  

 

 

produces hazardous vapors.  Evacuate the area if  

 exposed.

6.  Use only cylinders rated DOT4BA/4BW 400.

7.  Never fill cylinders over 80% of total capacity.

8.  Store cylinders in a cool area, out of direct  

 

 sunlight.

9.  Never heat cylinders above 125°F.

10. Never trap liquid R-410A in manifold sets, gauge  

 

lines or cylinders.  R-410A expands significantly  

 

at warmer temperatures.  Once a cylinder or line is  

 

full of liquid, any further rise in temperature will  

 

cause it to burst.

        WARNING

Failure to conform to these practices 

could lead to damage, injury or death.

Содержание W48A23

Страница 1: ...INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS W48A23 W48L23 W60A23 W60L23 Manual 2100 594 Supersedes NEW File Volume III Tab 16 Date 04 23 13 Bard Manufacturing Company Inc Bryan Ohio 4350...

Страница 2: ...e 8 Electric Heat 19 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Condensate Drain 5 Filters 5 In...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...ting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any wa...

Страница 5: ...ls Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return...

Страница 6: ...lly recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 3 Locate and mark l...

Страница 7: ...iew Ventilation Air Supply Air Opening Bracket Installation Return Air Opening Electric Heat Electrical Drain Built In Slope Top 2 Pitch Panel Built In Heater Access Circuit Breaker Disconnect Access...

Страница 8: ...Opening Supply Left Side View Installation Air Opening Return Heat Electric Top 2 Pitch Built In Slope Bracket Panel Access Heater Circuit Breaker Panel Lockable Disconnect Access Entrances Entrances...

Страница 9: ...HING FOUR SIDES OF SUPPLY REQUIRED DIMENSIONS TO MAINTAIN IT IS RECOMMENDED THAT A BEAD OF TOP FLASHING AT TIME OF INSTALLATION COMBUSTIBLE MATERIALS THE SIDE MOUNTING FLANGES AND UNDER RETURN AIR OPE...

Страница 10: ...ible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating t...

Страница 11: ...R FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 13: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high...

Страница 14: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 15: ...rrect phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation...

Страница 16: ...manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardle...

Страница 17: ...is unit was charged at the factory with the quantity of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity The...

Страница 18: ...s are in a raceway Top outlet supply option is available only factory installed and only on the selected models IMPORTANT While this electrical data is presented as a guide it is important to electric...

Страница 19: ...W48A23 W48L23 ARE NOT APPROVED FOR USE WITH ELECTRIC HEAT W60A23 W48A23 Part Number Description CMC 15 Start Kit X X WMCB 09A WMCB 08A Circuit Breaker Kit Circuit Breaker Kit X X Model W60A23 240V 1 2...

Отзывы: