background image

Manual 2100-594 

Page  6 of 19

Clearances Required for Service Access 

and Adequate Condenser Airflow

MODELS

LEFT SIDE

RIGHT SIDE

W48A, W60A

20"

20"

W48L, W60L

20"

20"

NOTE: For side by side installation of two (2) W**A models there 

must be 20" between units.  This can be reduced to 15" by using a 

W**L model (left side compressor and controls) for the left unit and 

WA (right side compressor and controls) for right unit.

See W**A / W**L Specification S3402.

INSTALLATION  INSTRUCTIONS

WALL MOUNTING INFORMATION

 1.  Two holes for the supply and return air openings must 
     be cut through the wall as shown in Figure 1 or 2.   
    Figure 1 is for models W48A23 and W60A23.

 2.  On wood frame walls, the wall construction must  
    be strong and rigid enough to carry the weight of  
    the unit without transmitting any unit vibration.

  3. Concrete block walls must be thoroughly inspected 

to insure that they are capable of carrying the 
weight of the installed unit.

MOUNTING THE UNIT

  1. These units are secured by wall mounting brackets 

which secure the unit to the outside wall surface at 
both sides.  A bottom mounting bracket is provided 
for ease of installation, but is not required.

 2. The unit itself is suitable for 0 inch clearance, but the 

supply air duct flange and the first 3 feet of supply air duct 

require a minimum of 1/4 inch clearance to combustible 
material.  If a combustible wall, use a minimum of 30½" 
x 10½" dimensions for sizing.  However, it is generally 
recommended that a 1 inch clearance is used for ease 
of installation and maintaining the required clearance to 
combustible material.  The supply air opening would then 
be 32" x 12".

  3. Locate and mark lag bolt locations and bottom 

mounting bracket location.

  4. Mount bottom mounting bracket.

 5. 

Hook top rain flashing under back bend of top.  Top rain 

flashing is shipped secured to the right side of the back.

 6. Position unit in opening and secure with 5/16 lag bolts; 

use 7/8 inch diameter flat washers on the lag bolts.

  7. Secure rain flashing to wall and caulk across entire 

length of top.

  8. For additional mounting rigidity, the return air 

and supply air frames or collars can be drilled 
and screwed or welded to the structural wall itself 
(depending upon wall construction).  Be sure to 
observe required clearance if combustible wall.

  9. On side by side installations, maintain a minimum 

of  20 inches clearance on right side to allow access 
to control panel and heat strips, and to allow proper 

airflow to the outdoor coil.  Additional clearance 

may be required to meet local or national codes.

       WARNING

Fire hazard can result if 1/4 inch clearance to 

combustible materials for supply air duct is not 

maintained.

        WARNING

Failure to provide the 1/4 inch clearance 

between the supply duct and a combustible 

surface for the first 3 feet of duct can result in 

fire causing damage, injury or death.

TABLE  1

MAXIMUM ESP OF OPERATION 

ELECTRIC HEAT ONLY 

VALUES SHOWN ARE FOR UNITS EQUIPPED WITH 

STANDARD 1" THROWAWAY FILTERS OR 1" WASHABLE 

FILTERS.  DERATE ESP BY .15 FOR 2" PLEATED FILTERS.

MODELS

ESP

W60A23 - ONLY

W60L23 - ONLY

A05

A10

.4

.3

Содержание W48A23

Страница 1: ...INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS W48A23 W48L23 W60A23 W60L23 Manual 2100 594 Supersedes NEW File Volume III Tab 16 Date 04 23 13 Bard Manufacturing Company Inc Bryan Ohio 4350...

Страница 2: ...e 8 Electric Heat 19 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Condensate Drain 5 Filters 5 In...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...ting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any wa...

Страница 5: ...ls Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return...

Страница 6: ...lly recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 3 Locate and mark l...

Страница 7: ...iew Ventilation Air Supply Air Opening Bracket Installation Return Air Opening Electric Heat Electrical Drain Built In Slope Top 2 Pitch Panel Built In Heater Access Circuit Breaker Disconnect Access...

Страница 8: ...Opening Supply Left Side View Installation Air Opening Return Heat Electric Top 2 Pitch Built In Slope Bracket Panel Access Heater Circuit Breaker Panel Lockable Disconnect Access Entrances Entrances...

Страница 9: ...HING FOUR SIDES OF SUPPLY REQUIRED DIMENSIONS TO MAINTAIN IT IS RECOMMENDED THAT A BEAD OF TOP FLASHING AT TIME OF INSTALLATION COMBUSTIBLE MATERIALS THE SIDE MOUNTING FLANGES AND UNDER RETURN AIR OPE...

Страница 10: ...ible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating t...

Страница 11: ...R FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 13: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high...

Страница 14: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 15: ...rrect phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation...

Страница 16: ...manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardle...

Страница 17: ...is unit was charged at the factory with the quantity of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity The...

Страница 18: ...s are in a raceway Top outlet supply option is available only factory installed and only on the selected models IMPORTANT While this electrical data is presented as a guide it is important to electric...

Страница 19: ...W48A23 W48L23 ARE NOT APPROVED FOR USE WITH ELECTRIC HEAT W60A23 W48A23 Part Number Description CMC 15 Start Kit X X WMCB 09A WMCB 08A Circuit Breaker Kit Circuit Breaker Kit X X Model W60A23 240V 1 2...

Отзывы: