background image

Manual 2100-692E 

Page 

9 of 42

Ducted Applications

Field fabricated supply and return duct work may be 
installed inside the structure being conditioned. A short 
supply and/or return stub duct may be connected to the 
unit supply and return flanges before unit installation to 
help with duct connections inside the structure. Supply 
and return ducts must be properly sized for the design 
airflow requirement of the equipment. Air Conditioning 
Contractors of America (ACCA) is an excellent guide 
to proper sizing. All duct work or portions thereof not 
in the conditioned space should be properly insulated 
in order to conserve energy, reduce heat conductivity, 
and prevent condensation or moisture damage. Refer to 
Maximum External Static Pressure (ESP) of Operation 
Table 16 on page 38. Design the duct work according 
to methods given by the Air Conditioning Contractors 
of America (ACCA). When duct work is installed 
in unheated spaces, it should be insulated with a 
minimum of 1" of insulation. Use insulation with a 
vapor barrier on the outside of the insulation. Flexible 
joints should be used to connect the duct work to the 
equipment in order to keep the noise transmission to a 
minimum. Ducts through the walls must be insulated 
and all joints taped or sealed to prevent air or moisture 
from entering the wall cavity.
All model series require a 1/4" clearance to 
combustible material for the first 3' of duct attached 
to the outlet air frame is required. See instructions 
on page 10 and Figures 14 − 18 (pages 13 – 16) for 
further details.

A non-restrictive metallic supply air grille with 
deflectors is required for free blow applications. Contact 
the local Bard distributor or visit www.bardhvac.com for 
ordering information.
A metallic return air grille is required for non-ducted 
applications. The spacing between louvers on the grille 
shall not be larger than 5/8". It is recommended that a 
Bard Return Air Grille Kit is installed that is designed 
specifically for the wall mount product. Contact the 
local Bard distributor or visit www.bardhvac.com for 
ordering information. A field-supplied return grille 
that meets the 5/8" louver criteria and does not cause 
the unit to exceed the maximum specified external 
static pressure (ESP) may be used. If using a return 
air filter grille, filters must be of sufficient size to 
allow a maximum velocity of 400 fpm. Filter return 
air grilles do not filter air being brought into the 
structure through ventilation options including fresh air 
dampers, ventilators, economizers and energy recovery 
ventilators. Be sure to install the return grille with the 
louvers pointed downward towards the floor. This will 
help ensure return air is drawn upward from the floor 
and improve air circulation in the room.

NOTE:

  If no return air duct is used, applicable 

installation codes may limit this cabinet to 

installation only in a single story structure.

Thermostat or Indoor Temperature Sensor Placement

The location and installation of the thermostat or 
temperature sensor that monitors indoor temperature is 
very important regarding unit operation. Avoid placing 
the thermostat in an area exposed to direct sunlight 
or air from doorways leading outdoors. Use a piece 
of insulating material to close off conduit openings 
or holes in the wall surface for wire entry into the 
thermostat or temperature sensor. This will help avoid 
non-conditioned air from entering the thermostat 
and effecting temperature and/or humidity readings. 
As common practice, the thermostat or temperature 
sensor should measure the temperature of the air 
being returned to the unit, and not the conditioned 
air being supplied by the unit. Placing the thermostat 
or temperature sensor near a return air opening will 
normally result in optimal unit performance.

Unit Installation

Make sure to have the proper tools at the work site that 
are needed for unit installation. The following steps 
are provided to ensure the unit is installed properly to 
the wall surface, and that the unit will provide years of 
service with minimal service requirements.

Materials/Tools List

Additional hardware and miscellaneous supplies are 
needed for installation. These items are field supplied 
and must be sourced before installation. This list also 
includes tools needed for installation.

Fire hazard.

Maintain minimum 1/4" clearance between the 
supply air duct and combustible materials in 

the first 3' of ducting.
Failure to do so could result in fire causing 

damage, injury or death.

!

WARNING

Free Blow Applications

Some installations may not require extensive supply 
duct work throughout the structure and are referred 
to as free blow applications. A short field-fabricated 
supply duct must be used in the wall cavity to 
transition between the supply collar on the unit and 
the supply louver grille in the room. The duct must 
be properly insulated in order to conserve energy, 
reduce heat conductivity and prevent condensation or 
moisture damage. All joints must be taped or sealed to 
prevent air or moisture entering the wall cavity. Follow 
all clearances including distances to combustible 
materials and all instructions provided in this manual. 

Содержание W42AC-B

Страница 1: ...42AC B W42AC C W48AC A W48AC B W48AC C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 692E Supersedes 2100 692D Date 3 1 21 W60AC A W60AC B W60AC C W72AC A W72AC B W72AC...

Страница 2: ...4 Sequence of Operation 24 Balanced ClimateTM Mode 24 Vent Connection Plug 25 Compressor Control Module 25 Features 25 Delay on Make Timer 25 Short Cycle Delay on Break 25 Low Pressure Detection 25 Hi...

Страница 3: ...617 984 7057 Figure 21 Non Programmable Thermostat Connections 22 Figure 22 8201 169 Compressor Control Module 26 Figure 23 Motor Connections 27 Figure 24 Motor Connections 28 Figure 25 Fan Blade Set...

Страница 4: ...beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not s...

Страница 5: ...ge 10 and Figures 14 18 pages 13 16 for further details Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations...

Страница 6: ...tray see Figure 7 FIGURE 6 Remove Four Screws 5 Re install the four 4 screws into the upper screw holes on the filter support brackets Then bend the tab up out of the way see Figure 8 FIGURE 7 Re Inst...

Страница 7: ...ade FIGURE 9 Install Right 2 Filter FIGURE 10 Install Left 2 Filter There is an adjustable slide on the side of the fresh air intake that can be adjusted to limit how far the damper opens so that the...

Страница 8: ...hinder unit installation and servicing including outdoor electrical conduits junction boxes wall drains vent hoods windows doors overhangs and posts Condensate Water Drainage Review all codes and requ...

Страница 9: ...ing fresh air dampers ventilators economizers and energy recovery ventilators Be sure to install the return grille with the louvers pointed downward towards the floor This will help ensure return air...

Страница 10: ...he side of the unit 2 Locate and mark bolt hole locations and bottom mounting bracket location Install bottom mounting bracket with field supplied fasteners to wall if it is to be used optional Bracke...

Страница 11: ...48AC W60AC W72AC 20 20 10 TABLE 2 Minimum Clearances Required to Combustible Materials Model Supply Air Duct 1st 3 Cabinet W42AC W48AC W60AC W72AC 1 4 0 FIGURE 12 Vent Installation Removal Clearance R...

Страница 12: ...g MIS 3978 A Condenser Air Outlet Ventilation Air Inlet Cond Air Exhaust Air Brackets Built In Mounting Side Wall Location Shipping Flashing Top Rain DO NOT PLACE ELECTRICAL ENTRANCES IN SHADED AREAS...

Страница 13: ...ng and Hole Location View Supply Opening Return Opening UNITS REQUIRED DIMESIONS A B C D E F G W42AC W48AC UNITS REQUIRED DIMESIONS TO MAINTAIN 1 4 MIN CLEARANCE FROM COMBUSTIBLE MATERIALS 30 1 2 10 1...

Страница 14: ...W OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 CLEARANCE TO COMBUSTIBLE SURFACES Fire hazard Maintain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3...

Страница 15: ...TTACH TO TOP PLATE OF WALL ALL AROUND DUCT MIS 3982 A THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS SUPPY DUCT OPENING RETURN DUC...

Страница 16: ...VE RAFTERS GRILLE FLASHING OR BELOW CEILING RAFTERS AS SHOWN OR BELOW CEILING RAFTERS AS SHOWN FLASHING OUTSIDE SURFACE RAIN FLASHING SLEEVE FINISHED SUPPLY DUCT MAYBE LOCATED IN AN ATTIC GRILLE OUTSI...

Страница 17: ...eld can be removed for wire installation If field power is supplied to the left side of the unit run the high voltage wires under the shield and to the right of the wire shield next to the MIS 4044 US...

Страница 18: ...ons on auxiliary terminal strip Unit Shutdown Feature Standard on All Models The RT terminal is the 24VAC transformer output and the R terminal is the 24VAC hot terminal for the operation of the equip...

Страница 19: ...Feature Controls Option The alarm relay provides a set of NO normally open and NC normally closed pilot duty contacts that operate when the compressor control module locks out compressor operation bec...

Страница 20: ...2 3 18 gauge 16 gauge 14 gauge 12 gauge 60 100 160 250 TABLE 5 Wall Thermostats Part Number Predominate Features 8403 060 1120 445 3 stage Cool 3 stage Heat Electronic Programmable Non Programmable H...

Страница 21: ...upied periods Must be configured for multi stage for Y1 output to be active 1st stage cooling For dehumidification must be configured for No Economizer for YO D to be active for humidity control 4 Fac...

Страница 22: ...See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while blower is energized For ECON CRV V an additional wire change is required See in...

Страница 23: ...A refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to ensure optimal system performance Refer to instructions for the cylinder that is being utiliz...

Страница 24: ...y wired on low speed Service Hints 1 Caution owner operator to maintain clean air filters at all times and also not to needlessly close off supply and return air registers This reduces airflow through...

Страница 25: ...the switch closes again it will then restart the compressor If the switch trips again during the same Y call the compressor will be de energized and the alarm terminal will be energized indicating an...

Страница 26: ...power this could lead to the compressor never starting The control will see the brownout immediately and not start A common scenario and one that has been seen in the field is when a unit or units sw...

Страница 27: ...3302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock back a...

Страница 28: ...utput 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground at the L L1 G N L2 connections then continue with the Model SelecTech Communi...

Страница 29: ...enser coil for cleaning or to service the outdoor fan first remove the side grilles 3 The fan shroud sides can then be removed for ease of access to the coil and the back side of the shroud by removin...

Страница 30: ...55 629 85 72 Low Side High Side 135 333 138 357 140 382 142 407 144 434 146 461 148 489 150 519 152 549 155 580 157 612 W48AC 75 62 Low Side High Side 128 331 131 352 133 374 135 398 137 422 138 448 1...

Страница 31: ...587 149 633 85 72 Low Side High Side 127 331 129 349 131 368 134 390 136 415 139 441 141 470 143 501 146 534 148 569 151 608 W48AC 75 62 Low Side High Side 122 320 123 341 125 365 127 388 129 412 132...

Страница 32: ...W72AC A00 A0Z A05 A10 A15 A20 230 208 1 1 1 1 or 2 1 or 2 1 or 2 56 56 60 86 112 60 60 70 90 125 6 6 6 3 2 10 10 8 8 6 56 60 60 26 26 52 60 60 60 30 30 60 6 6 6 10 10 6 10 10 10 10 10 10 W72AC B00 B0...

Страница 33: ...ire on the blower speed terminal block to either MED or HI Refer to Table 15 on page 37 for the corresponding airflow of each tap Set the unit duct static based on the highest airflow that the unit wi...

Страница 34: ...per between Y1 and Y2 installed and it must be removed to use Balanced Climate mode The unit is shipped with the orange black wire connected to terminal LO rated speed on the blower selection speed te...

Страница 35: ...to the unit Remove the upper front panel and the cover on the airflow switch so that adjustment can be made If the switch tripped before 75 restriction was reached turn the knob slightly clockwise If...

Страница 36: ...2100 692E Page 36 of 42 FIGURE 30 Adjusting Dirty Filter Switch TURN CLOCKWISE TO INCREASE RESTRICTION AMOUNT REQUIRED TO ACTIVATE THE SWITCH AND COUNTER CLOCKWISE TO DECREASE RESTRICTION AMOUNT MIS...

Страница 37: ...1655 1555 1785 1685 1870 1780 0 25 1615 1520 1750 1645 1835 1745 0 30 1575 1485 1715 1610 1800 1710 0 40 1485 1405 1635 1540 1730 1635 0 50 1390 1325 1550 1475 1655 1560 W60AC 0 00 1540 1480 1960 187...

Страница 38: ...5 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 15 62 5 51250 54 0 38400 36 2 51200 31 2 38400 18 0 51200 18 43 3 61430 37 4 46060 20 83 2 68...

Страница 39: ...A 43 ODT X X CMA 44 DDC X X BOP5 Blank Off Plate X X FAD NE5 Fresh Air Damper No Exhaust X X FAD BE5 Fresh Air Damper Barometric Exhaust X X CRV F5 Commercial Ventilator On Off Spring Return X X CRV V...

Страница 40: ...B18 X EHWA42CD B18 X EHWA42C C05 X X EHWA42C C09 X EHWA42CD C09 X EHWA42C C15 X X EHWA48C A05 X X EHWA48CD A05 X EHWA48CD A10 X X EHWA48CD B09 X EHWA48C B15 X EHWA48C B18 X X EHWA48CD B18 X EHWA48C C...

Страница 41: ...Manual 2100 692E Page 41 of 42 GRAPH 1 W42AC FAD NE5 W O Exhaust Ventilation Delivery GRAPH 2 W48AC FAD NE5 W O Exhaust Ventilation Delivery...

Страница 42: ...Manual 2100 692E Page 42 of 42 GRAPH 3 W60AC FAD NE5 W O Exhaust Ventilation Delivery GRAPH 4 W72AC FAD NE5 W O Exhaust Ventilation Delivery...

Отзывы: