Manual 2100-692E 

Page 

31 of 42

TABLE 11 

Cooling Pressure 

 Balanced Climate Airflow

Air Temperature Entering Outdoor Coil °F

Low side pressure ± 4 PSIG                                                         
High side pressure ± 10 PSIG

Tables are based upon Balanced Climate CFM (airflow) across the evaporator coil. If there is any doubt as to correct 
operating charge being in the system, the charge should be removed and system evacuated and recharged to serial plate 
charge weight.

NOTE:

  Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check 

condenser fan wiring. See 

Condenser Fan Operation

 on page 24.

* Operating at these conditions would be outside the compressor operating envelope and is not recommended.

Model

Return Air Temp 

(DB/WB)

Pressure

75

80

85

90

95

100

105

110

115

120

125

131

W42AC

75/62

Low Side

High Side

115
312

117
329

119
347

121
368

122
391

125
415

127
443

129
472

132
503

134
536

137
572

139
617

80/67

Low Side

High Side

123
320

125
337

127
356

129
377

131
401

134
426

136
454

138
484

141
516

143
550

146
587

149
633

85/72

Low Side

High Side

127
331

129
349

131
368

134
390

136
415

139
441

141
470

143
501

146
534

148
569

151
608

--*

W48AC

75/62

Low Side

High Side

122
320

123
341

125
365

127
388

129
412

132
438

134
464

136
491

137
520

139
549

141
579

143
616

80/67

Low Side

High Side

130
328

132
350

134
374

136
398

138
423

141
449

143
476

145
504

147
533

149
563

151
594

153
632

85/72

Low Side

High Side

135
339

137
362

139
387

141
412

143
438

146
465

148
493

150
522

152
552

154
583

156
615

--*

W60AC

75/62

Low Side

High Side

120
323

122
345

123
370

126
394

128
419

130
445

132
471

134
498

136
526

137
554

138
583

141
619

80/67

Low Side

High Side

128
331

130
354

132
379

135
404

137
430

139
456

141
483

143
511

145
539

147
568

148
598

151
635

85/72

Low Side

High Side

132
343

135
366

137
392

140
418

142
445

144
472

146
500

148
529

150
558

152
588

153
619

--*

W72AC

75/62

Low Side

High Side

109
325

111
347

113
371

115
394

117
419

119
445

121
472

122
499

124
528

126
558

128
588

130
626

80/67

Low Side

High Side

117
333

119
356

121
380

123
404

125
430

127
456

129
484

131
512

133
542

135
572

137
603

139
642

85/72

Low Side

High Side

121
345

123
368

125
393

127
418

129
445

131
472

134
501

136
530

138
561

140
592

142
624

--*

Содержание W42AC-B

Страница 1: ...42AC B W42AC C W48AC A W48AC B W48AC C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 692E Supersedes 2100 692D Date 3 1 21 W60AC A W60AC B W60AC C W72AC A W72AC B W72AC...

Страница 2: ...4 Sequence of Operation 24 Balanced ClimateTM Mode 24 Vent Connection Plug 25 Compressor Control Module 25 Features 25 Delay on Make Timer 25 Short Cycle Delay on Break 25 Low Pressure Detection 25 Hi...

Страница 3: ...617 984 7057 Figure 21 Non Programmable Thermostat Connections 22 Figure 22 8201 169 Compressor Control Module 26 Figure 23 Motor Connections 27 Figure 24 Motor Connections 28 Figure 25 Fan Blade Set...

Страница 4: ...beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not s...

Страница 5: ...ge 10 and Figures 14 18 pages 13 16 for further details Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations...

Страница 6: ...tray see Figure 7 FIGURE 6 Remove Four Screws 5 Re install the four 4 screws into the upper screw holes on the filter support brackets Then bend the tab up out of the way see Figure 8 FIGURE 7 Re Inst...

Страница 7: ...ade FIGURE 9 Install Right 2 Filter FIGURE 10 Install Left 2 Filter There is an adjustable slide on the side of the fresh air intake that can be adjusted to limit how far the damper opens so that the...

Страница 8: ...hinder unit installation and servicing including outdoor electrical conduits junction boxes wall drains vent hoods windows doors overhangs and posts Condensate Water Drainage Review all codes and requ...

Страница 9: ...ing fresh air dampers ventilators economizers and energy recovery ventilators Be sure to install the return grille with the louvers pointed downward towards the floor This will help ensure return air...

Страница 10: ...he side of the unit 2 Locate and mark bolt hole locations and bottom mounting bracket location Install bottom mounting bracket with field supplied fasteners to wall if it is to be used optional Bracke...

Страница 11: ...48AC W60AC W72AC 20 20 10 TABLE 2 Minimum Clearances Required to Combustible Materials Model Supply Air Duct 1st 3 Cabinet W42AC W48AC W60AC W72AC 1 4 0 FIGURE 12 Vent Installation Removal Clearance R...

Страница 12: ...g MIS 3978 A Condenser Air Outlet Ventilation Air Inlet Cond Air Exhaust Air Brackets Built In Mounting Side Wall Location Shipping Flashing Top Rain DO NOT PLACE ELECTRICAL ENTRANCES IN SHADED AREAS...

Страница 13: ...ng and Hole Location View Supply Opening Return Opening UNITS REQUIRED DIMESIONS A B C D E F G W42AC W48AC UNITS REQUIRED DIMESIONS TO MAINTAIN 1 4 MIN CLEARANCE FROM COMBUSTIBLE MATERIALS 30 1 2 10 1...

Страница 14: ...W OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 CLEARANCE TO COMBUSTIBLE SURFACES Fire hazard Maintain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3...

Страница 15: ...TTACH TO TOP PLATE OF WALL ALL AROUND DUCT MIS 3982 A THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS SUPPY DUCT OPENING RETURN DUC...

Страница 16: ...VE RAFTERS GRILLE FLASHING OR BELOW CEILING RAFTERS AS SHOWN OR BELOW CEILING RAFTERS AS SHOWN FLASHING OUTSIDE SURFACE RAIN FLASHING SLEEVE FINISHED SUPPLY DUCT MAYBE LOCATED IN AN ATTIC GRILLE OUTSI...

Страница 17: ...eld can be removed for wire installation If field power is supplied to the left side of the unit run the high voltage wires under the shield and to the right of the wire shield next to the MIS 4044 US...

Страница 18: ...ons on auxiliary terminal strip Unit Shutdown Feature Standard on All Models The RT terminal is the 24VAC transformer output and the R terminal is the 24VAC hot terminal for the operation of the equip...

Страница 19: ...Feature Controls Option The alarm relay provides a set of NO normally open and NC normally closed pilot duty contacts that operate when the compressor control module locks out compressor operation bec...

Страница 20: ...2 3 18 gauge 16 gauge 14 gauge 12 gauge 60 100 160 250 TABLE 5 Wall Thermostats Part Number Predominate Features 8403 060 1120 445 3 stage Cool 3 stage Heat Electronic Programmable Non Programmable H...

Страница 21: ...upied periods Must be configured for multi stage for Y1 output to be active 1st stage cooling For dehumidification must be configured for No Economizer for YO D to be active for humidity control 4 Fac...

Страница 22: ...See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while blower is energized For ECON CRV V an additional wire change is required See in...

Страница 23: ...A refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to ensure optimal system performance Refer to instructions for the cylinder that is being utiliz...

Страница 24: ...y wired on low speed Service Hints 1 Caution owner operator to maintain clean air filters at all times and also not to needlessly close off supply and return air registers This reduces airflow through...

Страница 25: ...the switch closes again it will then restart the compressor If the switch trips again during the same Y call the compressor will be de energized and the alarm terminal will be energized indicating an...

Страница 26: ...power this could lead to the compressor never starting The control will see the brownout immediately and not start A common scenario and one that has been seen in the field is when a unit or units sw...

Страница 27: ...3302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock back a...

Страница 28: ...utput 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground at the L L1 G N L2 connections then continue with the Model SelecTech Communi...

Страница 29: ...enser coil for cleaning or to service the outdoor fan first remove the side grilles 3 The fan shroud sides can then be removed for ease of access to the coil and the back side of the shroud by removin...

Страница 30: ...55 629 85 72 Low Side High Side 135 333 138 357 140 382 142 407 144 434 146 461 148 489 150 519 152 549 155 580 157 612 W48AC 75 62 Low Side High Side 128 331 131 352 133 374 135 398 137 422 138 448 1...

Страница 31: ...587 149 633 85 72 Low Side High Side 127 331 129 349 131 368 134 390 136 415 139 441 141 470 143 501 146 534 148 569 151 608 W48AC 75 62 Low Side High Side 122 320 123 341 125 365 127 388 129 412 132...

Страница 32: ...W72AC A00 A0Z A05 A10 A15 A20 230 208 1 1 1 1 or 2 1 or 2 1 or 2 56 56 60 86 112 60 60 70 90 125 6 6 6 3 2 10 10 8 8 6 56 60 60 26 26 52 60 60 60 30 30 60 6 6 6 10 10 6 10 10 10 10 10 10 W72AC B00 B0...

Страница 33: ...ire on the blower speed terminal block to either MED or HI Refer to Table 15 on page 37 for the corresponding airflow of each tap Set the unit duct static based on the highest airflow that the unit wi...

Страница 34: ...per between Y1 and Y2 installed and it must be removed to use Balanced Climate mode The unit is shipped with the orange black wire connected to terminal LO rated speed on the blower selection speed te...

Страница 35: ...to the unit Remove the upper front panel and the cover on the airflow switch so that adjustment can be made If the switch tripped before 75 restriction was reached turn the knob slightly clockwise If...

Страница 36: ...2100 692E Page 36 of 42 FIGURE 30 Adjusting Dirty Filter Switch TURN CLOCKWISE TO INCREASE RESTRICTION AMOUNT REQUIRED TO ACTIVATE THE SWITCH AND COUNTER CLOCKWISE TO DECREASE RESTRICTION AMOUNT MIS...

Страница 37: ...1655 1555 1785 1685 1870 1780 0 25 1615 1520 1750 1645 1835 1745 0 30 1575 1485 1715 1610 1800 1710 0 40 1485 1405 1635 1540 1730 1635 0 50 1390 1325 1550 1475 1655 1560 W60AC 0 00 1540 1480 1960 187...

Страница 38: ...5 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 15 62 5 51250 54 0 38400 36 2 51200 31 2 38400 18 0 51200 18 43 3 61430 37 4 46060 20 83 2 68...

Страница 39: ...A 43 ODT X X CMA 44 DDC X X BOP5 Blank Off Plate X X FAD NE5 Fresh Air Damper No Exhaust X X FAD BE5 Fresh Air Damper Barometric Exhaust X X CRV F5 Commercial Ventilator On Off Spring Return X X CRV V...

Страница 40: ...B18 X EHWA42CD B18 X EHWA42C C05 X X EHWA42C C09 X EHWA42CD C09 X EHWA42C C15 X X EHWA48C A05 X X EHWA48CD A05 X EHWA48CD A10 X X EHWA48CD B09 X EHWA48C B15 X EHWA48C B18 X X EHWA48CD B18 X EHWA48C C...

Страница 41: ...Manual 2100 692E Page 41 of 42 GRAPH 1 W42AC FAD NE5 W O Exhaust Ventilation Delivery GRAPH 2 W48AC FAD NE5 W O Exhaust Ventilation Delivery...

Страница 42: ...Manual 2100 692E Page 42 of 42 GRAPH 3 W60AC FAD NE5 W O Exhaust Ventilation Delivery GRAPH 4 W72AC FAD NE5 W O Exhaust Ventilation Delivery...

Отзывы: