controller can be installed). This will increase the
humidity removal up to 35% and provide a much more
comfortable environment.
If the application is likely to require air conditioning
operation below 60°F outdoor conditions, a low
ambient control (LAC) kit must be installed.
The LAC
kit is equipped with an additional sensor that disables
Balanced Climate mode when the outdoor temperature
drops below 50°F. This prevents potential evaporator
coil freeze up issues.
If the unit is being installed with any ventilation
package, a Bard LAC kit must be installed.
Failure to
utilize an LAC with any air conditioner can cause coil
freeze up.
NOTE:
Economizer will disable Balanced
Climate operation.
Balanced Climate can readily be applied to duct-free
(supply and return air grille) applications. It may also
be applied to ducted applications with
limited static
of 0.20" ESP (total including both supply and return
statics)
. Consult Bard Application Engineering for
details prior to implementation.
CAUTION:
Balanced Climate is not a replacement for
a dehumidification (hot gas reheat) unit for extreme
applications, but rather an enhancement feature for
limited climates and applications.