Manual 2100-720E
Page
18 of 42
Wiring – Low Voltage
All 230/208V 1 phase and 3 phase equipment have
dual primary voltage transformers. All equipment leaves
the factory wired on 240V tap. For 208V operation,
reconnect from 240V to 208V tap. The acceptable
operating voltage range for the 240 and 208V taps are:
Tap: 240
Range: 253 – 216
Tap: 208
Range: 220 – 187
NOTE:
The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
For low voltage wiring, an 18 gauge copper, color-coded
cable is recommended. See Table 8 on page 20 for
more information.
Low Voltage (24VAC) Connections
These units use a 24-volt AC low voltage circuit.
C
terminal is the
24VAC common and is grounded.
G
terminal is the
indoor blower input
.
Y1
terminal is the
1st Stage input for cooling.
Y2
terminal is the
2nd Stage compressor input for
cooling, and disables Balanced Climate mode if jumper is
installed
.
Y3
If Y2-Y3 jumper is installed, Y2 terminal is the
2nd
Stage compressor input for cooling.
If the Y2-Y3 jumper
is removed,
Y3 will increase blower to rated airflow.
B/W1
terminal is the
1st stage electric heat
.
W2
terminal is the
2nd stage heat
(if equipped).
A
terminal is the
ventilation input
. This terminal
energizes any factory-installed ventilation option and
indoor blower.
D
terminal is the
dehumidification input
. If installed, this
terminal energizes any factory-installed dehumidification
option.
L
terminal is
24 volt alarm active output
.
For units equipped with an alarm relay:
1 terminal
is the
normally closed contact on the relay.
2 terminal
is the
normally open contact on the relay.
3 terminal
is the
common contact on the relay.
See Table 3 for additional low voltage connections.
Unit Shutdown Feature (Standard on All Models)
The RT terminal is the 24VAC transformer output,
and the R terminal is the 24VAC hot terminal for the
operation of the equipment. RT and R are connected
with a brass jumper bar which can be removed and RT
and R connected to an external NC (normally closed)
contact such as a fire/smoke detector that will cause
shutdown of the equipment upon activation.
Balanced Climate™ Feature (Standard on All Models)
All units are equipped with the capability of running
in Balanced Climate mode. This mode is designed
to enhance the comfort level by reducing the indoor
airflow amount and extending the run time to help
extract more humidity during cooling operation. The
Y1 and Y2 terminals are the 24VAC input for Balanced
Climate compressor cooling operation. The Y2 terminal
is the 24VAC input for second stage compressor cooling
standard operation. Y2 and Y3 are connected with
a brass jumper bar which can be removed to enable
Balanced Climate mode.
Units with an economizer must
have the Y2-Y3 jumper installed.
Refer to vent manuals
for instructions on how Balanced Climate works with
each vent.
To operate in Balanced Climate mode, a 3-stage cooling
thermostat is required (no economizer with JADE
controller can be installed). The lower indoor airflow
operation is overridden by utilizing a 3-stage thermostat.
If the call for cooling is not satisfied within a given
time frame or temperature differential (specified by
the thermostat), the thermostat will send a signal to
Y3 which then increases the blower speed back to the
selected speed. See pages 34 – 35 for blower speed
selection options.
Refer to page 26 for additional Balanced Climate
requirements and limitations.
TABLE 3
Additional Low Voltage Connections (if applicable)
Terminal
Unit
Description
9
V Control
Option Only
Discharge Air Sensor,
10K Ohm
10
V Control
Option Only
Discharge Air Sensor,
10K Ohm
11
F, V Control
Options
Filter Switch,
Normally Open Contact
12
F, V Control
Options
Filter Switch,
Normally Open Contact
13
V Control
Option Only
Blower Airflow Switch,
Normally Open Contact
14
V Control
Option Only
Blower Airflow Switch,
Normally Open Contact
15
V Control
Option Only
Compressor Current Sensor,
Normally Open Contact
16
V Control
Option Only
Compressor Current Sensor,
Normally Open Contact