
Manual 2100-559A
Page
5 of 6
Model Selection, System Enabling and
Temperature Setpoints
Model Selection
To select specific HVAC unit model from the Home
screen:
1. Press
RIGHT button to access Main Menu screen.
2. Press
DOWN button to scroll to ADVANCED. Press
ENTER button.
3. In the ADVANCED menu screen, press ENTER
button to enter the APPLICATION menu.
4. Controller will ask for Admin Level Password. Enter
BARD. Press ENTER button.
5. Press DOWN button to scroll to ADDITIONAL
SETUP. Press ENTER button.
6. Press ENTER button again to select/enter Unit
Model screen.
7. Press ENTER button again to highlight current
model.
8. Press UP or DOWN button to choose from available
models:
-
W3*V
Model – Wall Mount 3 Ton Variable
Capacity System (factory default)
-
W5/6*V
Models – Wall Mount 4/5 Ton Variable
Capacity Systems
-
P60/72*V
Models – Packaged 5/6 Ton Variable
Capacity Systems
9. Press ENTER button to select/save appropriate
model.
10. Press LEFT button five (5) times to return to the
Home screen.
System Enabling
To access system types from the Home screen:
1. Press RIGHT button to access the Main Menu
screen.
2. Press DOWN button to scroll to SYSTEM. Press
ENTER button.
3. Press ENTER button again to select System
Enable.
4. Press UP or DOWN button to choose between six
(6) options.
QUICK START PROGRAMMING
• AUTO = Conventional system in “Auto-
Changeover” mode. HVAC system will cycle
heating and cooling automatically to stay
within preset heating and cooling setpoints.
• HEATING = Conventional system in “Heating-
Only” mode. HVAC system will cycle heating in
reference to heating setpoint only. Unit will not
activate cooling sequence.
• COOLING = Conventional system in “Cooling-
Only” mode. HVAC system will cycle cooling in
reference to cooling setpoint only. Unit will not
activate heating sequence.
• OFF = HVAC system is inactive.
• CCVC = “Continuous Compressor, Variable
Capacity” application in “Auto-Changeover”
mode. HVAC system will cycle heating and
cooling automatically to stay within preset
heating and cooling setpoints. Compressor
will modulate from 100% to 20%, but will
not shut off. Typically used for applications
such as an MRI mobile trailer where cycling
of compressor is not allowable due to use of
onsite generators.
• CCFC = “Continuous Compressor, Full
Capacity” application in “Auto-Changeover”
mode. HVAC system will cycle heating and
cooling automatically to stay within preset
heating and cooling setpoints. Compressor will
not modulate, but will stay at 100% capacity
and will not shut off. Typically, this mode is
selected foer testing purposes only.
NOTE:
Upon initial start-up of any system-enable
utilizing compressor, the unit may undergo
a series of self-diagnostics, wherein a series
of audible “clicks” are heard. This may delay
compressor function for up to 5 minutes.
4. Press ENTER button to save choice.
5. Press LEFT button two (2) times to return to Home
screen.
Temperature Setpoints
To access temperature setpoints from the Home screen:
1. Press RIGHT button to access the Main Menu
screen.
2. Press DOWN button to scroll to SETPOINTS. Press
ENTER button.
4. Press UP or DOWN button to scroll through
setpoint options.
Содержание W3LV2-R
Страница 2: ......
Страница 27: ......
Страница 34: ......
Страница 43: ......
Страница 46: ......
Страница 68: ......
Страница 74: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 75: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 80: ......
Страница 82: ...Manual 2110 1418G Page 2 of 16 CABINET COMPONENTS RIGHT EXTREME DUTY DOOR...
Страница 84: ...Manual 2110 1418G Page 4 of 16 CABINET COMPONENTS RIGHT MODERATE DUTY DOOR...
Страница 86: ...Manual 2110 1418G Page 6 of 16 CABINET COMPONENTS LEFT EXTREME DUTY DOOR...
Страница 88: ...Manual 2110 1418G Page 8 of 16 CABINET COMPONENTS LEFT MODERATE DUTY DOOR...
Страница 90: ...Manual 2110 1418G Page 10 of 16 FUNCTIONAL COMPONENTS RIGHT HAND This exploded view references table on page 12...
Страница 91: ...Manual 2110 1418G Page 11 of 16 FUNCTIONAL COMPONENTS LEFT HAND This exploded view references table on page 12...
Страница 97: ......
Страница 100: ......