DIGITAL THERMOSTAT/CONTROLLER
Refer to the unit rating plate for wire sizing information
and maximum fuse or circuit breaker size. Each
outdoor unit is marked with a “Minimum Circuit
Ampacity”. This means that the field wiring used must
be sized to carry that amount of current. Depending
on the installed KW of electric heat, there may be
two field power circuits required. If this is the case,
the unit serial plate will so indicate. All models are
suitable only for connection with copper wire. Each
unit and/or wiring diagram will be marked “Use Copper
Conductors Only”. These instructions
must be
adhered
to. Refer to the National Electrical Code (NEC) for
complete current carrying capacity data on the various
insulation grades of wiring material. All wiring must
conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75° C
copper) for all models including the most commonly
used heater sizes. Also shown are the number of field
power circuits required for the various models with
heaters.
The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or circuit breaker that is to be used with
the equipment. The correct size must be used for
proper circuit protection and also to assure that there
will be no nuisance tripping due to the momentary high
starting current of the compressor motor.
The control access door on this unit may be locked
to prevent unauthorized access to the disconnect. To
lock, insert a padlock through the hole in the lower
portion of one or both of the door latches. This will
prevent the latches from being turned.
See “Start Up” section for important information on
three phase scroll compressor start ups.
See Table 3 on page 22 for Electrical Specifications.
WIRING – MAIN POWER
These units are rated for 60/50 Hz operation as follows.
NOTE:
This system must be controlled only by the
Bard 8403-066 Digital Thermostat/Controller
that is supplied with the unit. See below
for wiring and pages 17-18 for operating
sequences.
Electrical
Code
Volts
Hz
Phase
Operating
Voltage
Range
-R
230/208-60-1
220/200-50-1
197 - 253
180 - 242
-S
230/208-60-3
220/200-50-3
197 - 253
180 - 242
-T
460-60-3
400-50-3
414 - 506
380 - 440
IMPORTANT INSTALLER NOTE
Must be followed for proper operation of all controls.
These models are designed for dual 60/50Hz
operation. –R and –S models use a 240/208Vx24V
control transformer, and are shipped from the factory
on the 208V tap. The –R and –S models may require
reconnection of the 24V transformer primary from 240
to 208V tap for either 60 or 50Hz:
Supply Voltage
Hz
Transformer Primary Tap
253-216
60 or 50
240
220-180
60 or 50
208
Terminal
Function
Type
Form
+B
MSTP + (not used)
Communications
-A
MSTP - (not used)
Communications
IN4
Outdoor Temperature Sensor
Input
10K OHM Type 3
IN3
Pressure Transducer
Input
0-5 VDC, 0-700
PSIG
GND
Sensor Grounds
Input
IN2
Lockout Alarm
Input
Relay Closure
24 COM
24VAC Com
Power
24V
24VAC
Power
OUT 9
Fan Motor Control
Analog Output
0-10VDC
GND7-9
Control Ground
Analog Output
OUT 8
Unloader Solenoid Control
Analog Output
0 or 5VDC PWM
OUT 7
Blower Motor Control
Analog Output
0-10VDC
RLY 4
Heater Contactor #1
Relay Output
Relay
SC 4-6
24VAC to Relay Outputs 4-6
Power
RLY 5
Heater Contactor #2
Relay Output
Relay
RLY 6
(not used)
RLY 3
(not used)
SC1-3
24VAC to Relay Outputs 1-3
Power
RLY 2
Compressor Contactor
Relay Output
Relay
RLY 1
(not used)
WIRING – LOW VOLTAGE
Содержание W3LV2-R
Страница 2: ......
Страница 27: ......
Страница 34: ......
Страница 43: ......
Страница 46: ......
Страница 68: ......
Страница 74: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 75: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 80: ......
Страница 82: ...Manual 2110 1418G Page 2 of 16 CABINET COMPONENTS RIGHT EXTREME DUTY DOOR...
Страница 84: ...Manual 2110 1418G Page 4 of 16 CABINET COMPONENTS RIGHT MODERATE DUTY DOOR...
Страница 86: ...Manual 2110 1418G Page 6 of 16 CABINET COMPONENTS LEFT EXTREME DUTY DOOR...
Страница 88: ...Manual 2110 1418G Page 8 of 16 CABINET COMPONENTS LEFT MODERATE DUTY DOOR...
Страница 90: ...Manual 2110 1418G Page 10 of 16 FUNCTIONAL COMPONENTS RIGHT HAND This exploded view references table on page 12...
Страница 91: ...Manual 2110 1418G Page 11 of 16 FUNCTIONAL COMPONENTS LEFT HAND This exploded view references table on page 12...
Страница 97: ......
Страница 100: ......