START UP

THESE UNITS REQUIRE R-410A 
REFRIGERANT AND POLYOL 
ESTER OIL.

GENERAL:

1.  Use separate service equipment to avoid cross    
 

contamination of oil and refrigerants.

2.  Use recovery equipment rated for R-410A  

 

 refrigerant.

3.  Use manifold gauges rated for R-410A (800 psi/250  
 

psi low).

4.  R-410A is a binary blend of HFC-32 and HFC-125.

5.  R-410A is nearly azeotropic - similar to R-22 and  
 

R-12.  Although nearly azeotropic, charge with   

 

liquid refrigerant.

6.  R-410A operates at 40-70% higher pressure than   
 

R-22, and systems designed for R-22 cannot  

 

 

withstand this higher pressure.

7.  R-410A has an ozone depletion potential of zero,  
 

but must be reclaimed due to its global warming  

 potential.

8.  R-410A compressors use Polyol Ester oil.

9.  Polyol Ester oil is hygroscopic; it will rapidly absorb  
 

moisture and strongly hold this moisture in the oil.

10. A liquid line dryer must be used - even a deep    
 

vacuum will not separate moisture from the oil.

11. Limit atmospheric exposure to 15 minutes.

12. If compressor removal is necessary, always plug   
 

compressor immediately after removal.  Purge with  

 

small amount of nitrogen when inserting plugs.

TOPPING OFF SYSTEM CHARGE

If a leak has occurred in the system, Bard 
Manufacturing recommends reclaiming, evacuating 
(see criteria above), and charging to the nameplate 
charge.  If done correctly, topping off the system charge 
can be done without problems.

With R-410A, there are no significant changes in the 

refrigerant composition during multiple leaks and 
recharges.  R-410A refrigerant is close to being an 
azeotropic blend (it behaves like a pure compound 
or single component refrigerant).  The remaining 
refrigerant charge, in the system, may be used after 
leaks have occurred and then “top-off” the charge by 
utilizing the pressure charts on the inner control panel 
cover as a guideline.

REMEMBER:  

When adding R-410A refrigerant, it 

must come out of the charging cylinder/tank as a liquid 
to avoid any fractionation, and to insure optimal system 
performance.  Refer to instructions for the cylinder that 
is being utilized for proper method of liquid extraction.

SAFETY PRACTICES:

1.  Never mix R-410A with other refrigerants.

2.  Use gloves and safety glasses, Polyol Ester oils can  
 

be irritating to the skin, and liquid refrigerant will  

 

freeze the skin.

3.  Never use air and R-410A to leak check; the  

 

 

mixture may become flammable.

4.  Do not inhale R-410A – the vapor attacks the    
 

nervous system, creating dizziness, loss of  

 

 

coordination and slurred speech.  Cardiac  

 

 

irregularities, unconsciousness and ultimate death  

 

can result from breathing this concentration.

5.  Do not burn R-410A.  This decomposition  

 

 

produces hazardous vapors.  Evacuate the area if  

 exposed.

6.  Use only cylinders rated DOT4BA/4BW 400.

7.  Never fill cylinders over 80% of total capacity.

8.  Store cylinders in a cool area, out of direct  

 

 sunlight.

9.  Never heat cylinders above 125°F.

10. Never trap liquid R-410A in manifold sets, gauge  

 

lines or cylinders.  R-410A expands significantly  

 

at warmer temperatures.  Once a cylinder or line is  

 

full of liquid, any further rise in temperature will  

 

cause it to burst.

        WARNING

Failure to conform to these practices 

could lead to damage, injury or death.

Содержание W18H2

Страница 1: ...PACKAGE HEAT PUMPS MODELS W18H2 W24H2 W24H2D W30H2 W30H2D W36H2 W36H2D W42H2 W42H2D W48H2 W48H2D W60H2 W60H2D Manual 2100 604 Supersedes NEW File Volume III Tab 17 Date 10 01 13 Bard Manufacturing Co...

Страница 2: ...rmance 25 Tables 7 Maximum ESP Electric Heat Only 26 Table 8 Electric Heat 26 Table 9 Optional Accessories 27 Table 10 Vent Control Options 28 Getting Other Information and Publications 3 Wall Mount G...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...ation on codes and standards Size of unit for a proposed installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air du...

Страница 5: ...G 2W through RG 5W or RFG 2W through RFG 5W be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of suff...

Страница 6: ...elf is suitable for 0 inch clearance but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1 4 inch clearance to combustible material for model series W30 W36 W42...

Страница 7: ...t factory installed only for W30H and W36H models only FIGURE 2 All dimensions are in inches Dimensional drawings are not to scale W H RIGHT UNIT SIDE VIEW BACK VIEW FRONT VIEW Dimensions of Basic Uni...

Страница 8: ...ING ENTIRE LENGTH OF TOP TOP WALL OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE NOTES RAIN FLASHING HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICO...

Страница 9: ...CLEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CA...

Страница 10: ...4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTI...

Страница 11: ...tible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating...

Страница 12: ...PPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMEN...

Страница 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 14: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high...

Страница 15: ...e leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be use...

Страница 16: ...eral minutes the compressor s internal protector will trip All three phase ZP compressors are wired identically internally As a result once the correct phasing is determined for a specific system or i...

Страница 17: ...cumstances require a change to another time remove the wire from the 60 minute terminal and reconnect to the desired terminal Refer to Figure 8 There is a cycle speed up jumper on the control This can...

Страница 18: ...28 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN ON FIG...

Страница 19: ...e transformer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check th...

Страница 20: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757...

Страница 21: ...testing with this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this infor...

Страница 22: ...573 85 DB 72 WB Low Side High Side 136 349 138 373 140 398 142 423 144 450 146 477 149 505 151 534 153 563 156 593 W42H2 75 DB 62 WB Low Side High Side 127 354 130 372 132 392 134 413 135 437 136 461...

Страница 23: ...W24H2 B00 B0Z B06 230 208 3 1 1 17 35 20 40 12 8 12 10 W24H2 C00 C0Z C06 460 3 1 1 11 21 15 25 14 10 14 10 W30H2 A00 A0Z A05 A10 230 208 1 1 1 1 or 2 24 50 76 35 50 80 8 8 4 10 10 8 50 26 50 30 8 10...

Страница 24: ...Ckt A Ckt B Ckt A Ckt B W24H2DA00 A0Z A04 A08 230 208 1 1 1 1 or 2 24 44 65 25 50 70 10 8 6 10 10 8 44 21 45 25 8 10 10 10 W24H2DB00 B0Z B06 230 208 3 1 1 17 35 20 40 12 8 12 10 W24H2DC00 C0Z C06 460...

Страница 25: ...igh Speed Low Speed High Speed Low Speed Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil 0 1 2 3 4 5 102...

Страница 26: ...W24H B00 B06 50 50 W24H C00 C06 50 50 Model Front Outlet Top Outlet Low Speed High Speed Low Speed High Speed W30H W36H A00 A05 A10 A15 50 40 35 35 50 50 40 40 50 40 25 NA 50 50 40 NA W30H W36H B00 B0...

Страница 27: ...EHWH36 A05 X EHWH36 A10 X EHWH36 A15 X EHWH03 B06 X EHW36H B06 X EHWH03 B09 X X EHW30H B15 X EHWC03A C06 X X EHWH42 A05 X X EHWH42 A10 X X EHWH42 A15 X X EHWH 04 A20 X X EHWH05 B06 X X EHWH05 B09 X X...

Страница 28: ...Commercial Ventilator Power Return X EIFM 3C Economizer X ERVF A3 Energy Recovery Ventilator 230 Volt X ERVF C3 Energy Recovery Ventilator 460 Volt X BFAD 5 Barometric Fresh Air Damper Standard X BOP...

Отзывы: