SERVICE

TABLE  3 – Troubleshooting

Sympton

Description, Check & Possible Cause

What & How to Check/Repair

Compressor will not 
start (heating or 
cooling)

1. Check for LED illumination.

Is there an LED illuminated on the board 
(flashing)?

Yes = go to Step #2; No = go to Step #3

2. Check for error codes.

Is the LED flashing a code?

Yes = go to Step #4; No = go to Step #8

3. Check for power at board.

Is there 24 volts AC between R and C?

Yes = go to Step #13; No = go to Step #9

4. Check codes.

What code is blinking?

Code "1", got to Step #6; Code "2", go to Step #7; Fast Blink, go to Step #5

5. Compressor delay active.

Wait for 5 minute delay or jump board's 
"speed up pins".

Check for proper operation; if still needed, go back to Step #1

6. Low pressure fault.

Check wiring circuit and unit pressures.

7. High pressure fault.

Check wiring circuit and unit pressures.

8. Check for Compressor input signal.

Is there 24 volts AC between Y and C?

Yes = go to Step #10; No = go to Step #11

9. No power to board.

The unit either does not have unit voltage, the transformer is bad or the unit wiring 
is incorrect.

10. Check for Compressor output signal.

Is there 24 volts AC between CC and C?

Yes = go to Step #12; No = go to Step #13

11. No "Y" compressor input signal.

Check thermostat wiring, incorrect phase of unit (see section on Phase Monitor) 
and finally unit wiring.

12. No "CC" compressor output signal.

Check compressor contactor for proper operation and finally check compressor.

13. Faulty board.

Replace defrost board.

Fan outdoor motor 
does not run (cool-
ing or heating except 
during defrost)

Heat pump control defective

Check across fan relay on heat pump control. (Com-NC)
Replace heat pump control.

Motor defective

Check for open or shorted motor winding. Replace motor.

Motor capacitor defective

Check capacitor rating. Check for open or shorted capacitor. Replace capacitor.

Reversing valve 
does not energize 
(heating only)

Heat pump control defective

Check for 24 V between RV-C and B-C.
1. Check circuit control wiring.
2. Replace heat pump control.

Reversing valve solenoid coil defective

Check for open or shorted coil.
Replace solenoid coil.

Unit will not go into 
defrost (heating 
only)

Temperature sensor or heat pump control 
defective

Disconnect temperature sensor from board and jumper across "SPEEDUP" terminals 
and "SEN JMP" terminals. This should cause the unit to go through a defrost cycle 
within one minute.
1. If unit goes through defrost cycle, replace temperature sensor.
2. If unit does not go through defrost cycle, replace heat pump control.

Unit will not come 
out of defrost 
(heating only)

Temperature sensor or heat pump control 
defective

Jumper across "SPEEDUP" terminal. This should cause the unit to come out of 
defrost within one minute.
1. If unit goes through defrost cycle, replace temperature sensor.
2. If unit does not go through defrost cycle, replace heat pump control.

SOLID STATE HEAT PUMP CONTROL 

TROUBLESHOOTING PROCEDURE

1. 

NOTE:

 

A thorough understanding of the defrost 

cycle sequence is essential.  Review that section 

(page 16) prior to troubleshooting the control.  

Turn on AC power supply to unit.

2.  Turn thermostat blower switch to “fan on”— 

the indoor blower should start.  (If it doesn’t, 
troubleshoot indoor unit and correct problem.)

3.  Turn thermostat blower to “auto” position.  Indoor 

blower should stop.  

NOTE:

 

Many models have a 

1-minute blower time delay on “off” command; 

wait for this to time out.

4.  Set system switch to “heat” or “cool”.  Adjust 

thermostat to call for heat or cool.  The indoor  
blower, compressor  and outdoor fan should start.

NOTE: 

If there was no power to 24 volt transformer, 

the compressor and outdoor fan motor will not 

start for 5 minutes.  This is because of the 

compressor short cycle protection.

LED BLINK CODES

BLINK

FUNCTION

Slow

Normal function (1.0 sec on/1.0 sec off)

Fast

Compressor Delay timer active  
(0.1 sec on/0.1 sec off)

1

Low pressure switch failure

2

High pressure switch failure/“Soft” Lockout

3

Defrost mode active

4

High pressure switch failure/“Hard” Lockout

Содержание T30S2-A

Страница 1: ...ndard and Dehumidification Models INSTALLATION INSTRUCTIONS T30S2 A T30S2 B T30S2 C T30S2DA T30S2DB T30S2DC Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 718A Supersedes...

Страница 2: ...7 Indoor Blower Performance 23 Table 8 Dehumidification Relay Logic Board 26 Getting Other Information and Publications 3 Wall Mount General Information 4 Wall Mount Model Nomenclature 4 Shipping Dama...

Страница 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Страница 4: ...ion made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Inst...

Страница 5: ...rough RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum ve...

Страница 6: ...l mounting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clea...

Страница 7: ...ctrical Entrances Optional Side Wall Mounting Brackets Built In Location Shipping Return Air Opening Supply Air Opening Top Rain Flashing Bottom Installation Bracket Back View M L O E R S S S S S T 44...

Страница 8: ...ARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULK...

Страница 9: ...rials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Страница 10: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 11: ...best unit performance and efficiency Review duct grille or return duct work Avoid using restrictive duct work to Unit Mount Return Grille Fixed Blade Wall wall Outside Wall Ducted Installations Adjus...

Страница 12: ...of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing e...

Страница 13: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Страница 14: ...reverse operation for over 1 hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal...

Страница 15: ...a special tool is required which can be obtained at www fastestinc com en SCCA07H See the replacement parts manual for replacement core part numbers DEFROST CYCLE The defrost cycle is controlled by t...

Страница 16: ...tificial test condition There is also a 5 minute compressor time delay function built into the HPC This is to protect the compressor from short cycling conditions The board s LED will have a fast blin...

Страница 17: ...Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replac...

Страница 18: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 3875...

Страница 19: ...this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shoul...

Страница 20: ...ntering Outdoor Coil F TABLE 5B Heating Pressures All Temperatures F Model Return Air Temperature Pressure 75 80 85 90 95 100 105 110 115 120 T30S 75 deg DB 62 deg WB Low SIde High Side 124 319 127 33...

Страница 21: ...pecial attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three 3 current carrying conductors are in a raceway Maximum size of the time delay fuse or circuit breaker...

Страница 22: ...erated Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three 3 current carrying conductors are in a raceway Maximum size of the time delay fuse or cir...

Страница 23: ...s and at both 230 208 or 460 volts Maximum ESP inches WC shown is with 2 thick disposable filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant B...

Страница 24: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Chec...

Страница 25: ...ite side of the connector plug and gently pulling the plug out of the connector socket in the control DO NOT PULL ON THE WIRES GRIP THE PLUG ONLY 6 The control module is now completely detached from t...

Страница 26: ...ied X X X X X X X X Y Y1 B G 2nd Heating Unoccupied X X X X X X X Y Y1 B G O1 2nd Heating Occupied X X X X X X X X X Y Y1 B G O1 W3 2nd Heat Dehum Occupied X X X X X X X X X X X Y Y1 B G W3 2nd Heat D...

Отзывы: