WIRING  –  MAIN POWER

Refer to the unit rating plate for wire sizing information 
and maximum fuse or circuit breaker size.  Each 
outdoor unit is marked with a “Minimum Circuit 
Ampacity”.  This means that the field wiring used must 
be sized to carry that amount of current. Depending 
on the installed KW of electric heat, there may be 
two field power circuits required.  If this is the case, 
the unit serial plate will so indicate.  All models are 
suitable only for connection with copper wire. Each 
unit and/or wiring diagram will be marked “Use Copper 
Conductors Only”.  These instructions 

must be 

adhered 

to.  Refer to the National Electrical Code (NEC) for 
complete current carrying capacity data on the various 
insulation grades of wiring material.  All wiring must 
conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°C 
copper) for all models including the most commonly 
used heater sizes.  Also shown are the number of field 
power circuits required for the various models with 
heaters.

The unit rating plate lists a maximum time delay relay 
fuse or circuit breaker that is to be used with the 
equipment.  The correct size must be used for proper 
circuit protection and also to assure that there will 
be no nuisance tripping due to the momentary high 
starting current of the compressor motor.

The disconnect access door on this unit may be locked 
to prevent unauthorized access to the disconnect.  To 
convert for the locking capability, bend the tab located 
in the bottom left-hand corner of the disconnect 
opening under the disconnect access panel straight 
out.  This tab will now line up with the slot in the door.  
When shut, a padlock may be placed through the hole 
in the tab preventing entry.

See “Start Up” section for important information on 
three phase scroll compressor start ups.

See Tables 6A and 6B for Electrical Specifications.

WIRING  –  LOW VOLTAGE WIRING 

All 230/208V 1 phase and 3 phase equipment have 
dual primary voltage transformers.  All equipment 
leaves the factory wired on 240V tap.  For 208V 
operation, reconnect from 240V to 208V tap.  The 
acceptable operating voltage range for the 240 and 
208V taps are:

 

TAP RANGE

 

240 

253 – 216

 

208 

220 – 187

NOTE:

  The voltage should be measured at the field 

power connection point in the unit and while 

the unit is operating at full load (maximum 

amperage operating condition).

For wiring size and connections, refer to Wiring Manual 
2100-554.

OPTIONAL OUTDOOR THERMOSTAT 

APPLICATIONS

Since most equipment at the time of manufacture 
is not designated for any specific destination of the 
country and are installed in areas not approaching the 
lower outdoor temperature range, outdoor thermostats 
are not factory installed as standard equipment, but 
are offered as an option.  There are also different 
applications for applying outdoor thermostats.  The set 
point of either type of outdoor thermostat application 
is variable with geographic region and sizing of 
the heating equipment to the individual structure.  
Utilization of the heating Application Data, and the 
heat loss calculation of the building are useful in 
determining the correct set points.

NOTE: 

The additional LAB (low ambient bypass) relay 

is required to prevent heater operation during low 

temperature cooling operation.

Содержание T30S2-A

Страница 1: ...ndard and Dehumidification Models INSTALLATION INSTRUCTIONS T30S2 A T30S2 B T30S2 C T30S2DA T30S2DB T30S2DC Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 718A Supersedes...

Страница 2: ...7 Indoor Blower Performance 23 Table 8 Dehumidification Relay Logic Board 26 Getting Other Information and Publications 3 Wall Mount General Information 4 Wall Mount Model Nomenclature 4 Shipping Dama...

Страница 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Страница 4: ...ion made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Inst...

Страница 5: ...rough RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum ve...

Страница 6: ...l mounting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clea...

Страница 7: ...ctrical Entrances Optional Side Wall Mounting Brackets Built In Location Shipping Return Air Opening Supply Air Opening Top Rain Flashing Bottom Installation Bracket Back View M L O E R S S S S S T 44...

Страница 8: ...ARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULK...

Страница 9: ...rials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Страница 10: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 11: ...best unit performance and efficiency Review duct grille or return duct work Avoid using restrictive duct work to Unit Mount Return Grille Fixed Blade Wall wall Outside Wall Ducted Installations Adjus...

Страница 12: ...of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing e...

Страница 13: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Страница 14: ...reverse operation for over 1 hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal...

Страница 15: ...a special tool is required which can be obtained at www fastestinc com en SCCA07H See the replacement parts manual for replacement core part numbers DEFROST CYCLE The defrost cycle is controlled by t...

Страница 16: ...tificial test condition There is also a 5 minute compressor time delay function built into the HPC This is to protect the compressor from short cycling conditions The board s LED will have a fast blin...

Страница 17: ...Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replac...

Страница 18: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 3875...

Страница 19: ...this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shoul...

Страница 20: ...ntering Outdoor Coil F TABLE 5B Heating Pressures All Temperatures F Model Return Air Temperature Pressure 75 80 85 90 95 100 105 110 115 120 T30S 75 deg DB 62 deg WB Low SIde High Side 124 319 127 33...

Страница 21: ...pecial attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three 3 current carrying conductors are in a raceway Maximum size of the time delay fuse or circuit breaker...

Страница 22: ...erated Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three 3 current carrying conductors are in a raceway Maximum size of the time delay fuse or cir...

Страница 23: ...s and at both 230 208 or 460 volts Maximum ESP inches WC shown is with 2 thick disposable filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant B...

Страница 24: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Chec...

Страница 25: ...ite side of the connector plug and gently pulling the plug out of the connector socket in the control DO NOT PULL ON THE WIRES GRIP THE PLUG ONLY 6 The control module is now completely detached from t...

Страница 26: ...ied X X X X X X X X Y Y1 B G 2nd Heating Unoccupied X X X X X X X Y Y1 B G O1 2nd Heating Occupied X X X X X X X X X Y Y1 B G O1 W3 2nd Heat Dehum Occupied X X X X X X X X X X X Y Y1 B G W3 2nd Heat D...

Отзывы: