IMPORTANT INSTALLER NOTE

For improved start up performance wash the indoor coil 
with a dish washing detergent.

HIGH AND LOW PRESSURE SWITCH

All T**S wall mounted air conditioner series models 
are supplied with a remote reset for the high and low 
pressure switch.  If tripped, this pressure switch may 
be reset by turning the thermostat off then back on 
again.

THREE PHASE SCROLL COMPRESSOR 

START UP INFORMATION

Scroll compressors, like several other types of 
compressors, will only compress in one rotational 
direction.  Direction of rotation is not an issue with 
single phase compressors since they will always start 
and run in the proper direction.

However, three phase compressors will rotate in either 
direction depending upon phasing of the power.  
Since there is a 50-50 chance of connecting power 
in such a way as to cause rotation in the reverse 
direction, verification of proper rotation must be made.  
Verification of proper rotation direction is made by 
observing that suction pressure drops and discharge 
pressure rises when the compressor is energized.  
Reverse rotation also results in an elevated sound level 
over that with correct rotation, as well as substantially 
reduced current draw compared to tabulated values.

Verification of 

proper rotation

 must be made at the 

time the equipment is put into service.  If improper 
rotation is corrected at this time, there will be no 
negative impact on the durability of the compressor. 
However, reverse operation for over 1 hour may have a 
negative impact on the bearing due to oil pump out.

NOTE:

  If compressor is allowed to run in reverse 

rotation for several minutes, the compressor’s 

internal protector will trip.

All three phase ZP compressors are wired identically 
internally.  As a result, once the correct phasing 
is determined for a specific system or installation, 
connecting properly phased power leads to the same 
Fusite terminal should maintain proper rotation 
direction.

The direction of rotation of the compressor may be 
changed by reversing any two line connections to the 
unit.

PHASE MONITOR

All units with three phase scroll compressors are 
equipped with a three phase line monitor to prevent 
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two 
LEDs.  If the Y signal is present at the phase monitor 
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and 
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply 
leads to the unit.  

Do not reverse any of the unit factory 

wires as damage may occur.

SERVICE HINTS

1.  Caution owner/operator to maintain clean air filters 

at all times and to not needlessly close off supply 
and return air registers.  This reduces airflow 
through the system, which shortens equipment 
service life as well as increasing operating costs.

2.  Check all power fuses or circuit breakers to be sure 

they are the correct rating.

3.  Periodic cleaning of the outdoor coil to permit full 

and unrestricted airflow circulation is essential.

        CAUTION

Remove service panels carefully.  Falling 
panels could cause lacerations.

Содержание T30S2-A

Страница 1: ...ndard and Dehumidification Models INSTALLATION INSTRUCTIONS T30S2 A T30S2 B T30S2 C T30S2DA T30S2DB T30S2DC Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 718A Supersedes...

Страница 2: ...7 Indoor Blower Performance 23 Table 8 Dehumidification Relay Logic Board 26 Getting Other Information and Publications 3 Wall Mount General Information 4 Wall Mount Model Nomenclature 4 Shipping Dama...

Страница 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Страница 4: ...ion made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Inst...

Страница 5: ...rough RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum ve...

Страница 6: ...l mounting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clea...

Страница 7: ...ctrical Entrances Optional Side Wall Mounting Brackets Built In Location Shipping Return Air Opening Supply Air Opening Top Rain Flashing Bottom Installation Bracket Back View M L O E R S S S S S T 44...

Страница 8: ...ARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULK...

Страница 9: ...rials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Страница 10: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 11: ...best unit performance and efficiency Review duct grille or return duct work Avoid using restrictive duct work to Unit Mount Return Grille Fixed Blade Wall wall Outside Wall Ducted Installations Adjus...

Страница 12: ...of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing e...

Страница 13: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Страница 14: ...reverse operation for over 1 hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal...

Страница 15: ...a special tool is required which can be obtained at www fastestinc com en SCCA07H See the replacement parts manual for replacement core part numbers DEFROST CYCLE The defrost cycle is controlled by t...

Страница 16: ...tificial test condition There is also a 5 minute compressor time delay function built into the HPC This is to protect the compressor from short cycling conditions The board s LED will have a fast blin...

Страница 17: ...Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replac...

Страница 18: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 3875...

Страница 19: ...this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shoul...

Страница 20: ...ntering Outdoor Coil F TABLE 5B Heating Pressures All Temperatures F Model Return Air Temperature Pressure 75 80 85 90 95 100 105 110 115 120 T30S 75 deg DB 62 deg WB Low SIde High Side 124 319 127 33...

Страница 21: ...pecial attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three 3 current carrying conductors are in a raceway Maximum size of the time delay fuse or circuit breaker...

Страница 22: ...erated Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three 3 current carrying conductors are in a raceway Maximum size of the time delay fuse or cir...

Страница 23: ...s and at both 230 208 or 460 volts Maximum ESP inches WC shown is with 2 thick disposable filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant B...

Страница 24: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Chec...

Страница 25: ...ite side of the connector plug and gently pulling the plug out of the connector socket in the control DO NOT PULL ON THE WIRES GRIP THE PLUG ONLY 6 The control module is now completely detached from t...

Страница 26: ...ied X X X X X X X X Y Y1 B G 2nd Heating Unoccupied X X X X X X X Y Y1 B G O1 2nd Heating Occupied X X X X X X X X X Y Y1 B G O1 W3 2nd Heat Dehum Occupied X X X X X X X X X X X Y Y1 B G W3 2nd Heat D...

Отзывы: