Manual 2100-541D
Page 26 of 28
TABLE 7
T**H INDOOR BLOWER PERFORMANCE - CFM (0.00" — 0.50" H
2
0)
Model
Rated
ESP
Max. ESP
Blower Only
Except for
CRVMP
Vent Options
Blower Only
for
CRVMP
Vent Options
Cooling
& Heat
Pump
Electric
Heat
T24H
.10
.50
800
650
800
1000
T30H
.10
.50
900
700
900
1000
T36H
.15
.50
1100
800
1100
1100
T42H
.15
.50
1250
825
1250
1250
T48H
.20
.50
1550
825
1550
1550
T60H
.20
.50
1650
850
1650
1650
NOTE:
These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain approximately
the same rate of indoor airflow in both heating & cooling, dry & wet coil conditions and at both 230/208 or 460 volts.
Maximum ESP (inches WC) shown is with 2" thick disposable filter.
Blower only CFM is the total air being circulated during continuous fan mode. Airflow remains constant.
Blower only CFM reduces during continuous fan mode. Requires wiring modification; consult Wiring Diagram and unplug and leave
disconnected the insulated male/female connector connecting together the Gray & Orange wires located near the 24V terminal block
enclosure.
CFM output on Cooling or Electric Heat.