background image

Manual 2100-541D 

Page  28 of 28

Manual

2100-522B

Page

36 of 38

TROUBLESHOOTING  GE  ECM

 MOTORS CONT’D.

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove

Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              

Use the shorter 

bolts and 

alignment pin 

supplied when 

replacing an 

ECM 2.0 

control.

Figure 3

ECM 

2.3/2.5

Power Connector

(5-pin)

Control Connector

(16-pin)

Hex-head Screws

Motor Connector

(3-pin)

Motor Connector

(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats

Over Ramp

From Motor

Circuit

Board

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower

motor you need to take the following steps:

1. You MUST have the correct replacement module.  The controls are

factory programmed for specific operating modes.  Even though they look

alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT

WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the furnace or air handler being

serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER

APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect

power and wait at least 5 minutes before opening motor.

3. It is usually not necessary to remove the motor from the blower

assembly.  However, it is recommended that the whole blower assembly,

with the motor, be removed from the furnace/air handler.  (Follow the

manufacturer’s procedures).  Unplug the two cable connectors to the motor.

There are latches on each connector.  

DO NOT PULL ON THE WIRES.

The plugs remove easily when properly released.

4. Locate  the  two  standard  ¼"  hex  head  bolts  at  the  rear  of  the  control

housing  (at  the  back  end  of  the  control  opposite  the  shaft  end).   

Refer  to

Figure  24.   

Remove  these  two  bolts  from  the  motor  and  control  assembly

while  holding  the  motor  in  a  way  that  will  prevent  the  motor  or  control

from  falling  when  the  bolts  are  removed.    If  an  ECM2.0  control  is  being

replaced  (recognized  by  an  aluminum  casting  rather  that  a  deep-drawn

black  steel  can  housing  the  electronics),  remove  only  the  hex-head  bolts.

DO  NOT  REMOVE  THE  TORX-HEAD  SCREWS.

5. The  control  module  is  now  free  of  mechanical  attachment  to  the

motor  endshield  but  is  still  connected  by  a  plug  and  three  wires  inside

the  control.    Carefully  rotate  the  control  to  gain  access  to  the  plug  at

the  control  end  of  the  wires.    With  thumb  and  forefinger,  reach  the

latch  holding  the  plug  to  the  control  and  release  it  by  squeezing  the

latch  tab  and  the  opposite  side  of  the  connector  plug  and  gently  pulling

the  plug  out  of  the  connector  socket  in  the  control.   

DO  NOT  PULL

ON  THE  WIRES.    GRIP  THE  PLUG  ONLY.

6. The  control  module  is  now  completely  detached  from  the  motor.

Verify  with  a  standard  ohmmeter  that  the  resistance  from  each  motor

lead  (in  the  motor  plug  just  removed)  to  the  motor  shell  is  >100K  ohms.

Refer to Figure 25.  

(Measure to unpainted motor end plate.)  If any

motor  lead  fails  this  test,  do  not  proceed  to  install  the  control  module.

THE  MOTOR  IS  DEFECTIVE  AND  MUST  BE  REPLACED.

Installing  the  new  control  module  will  cause  it  to  fail  also.

7. Verify  that  the  replacement  control  is  correct  for  your

application.    Refer  to  the  manufacturer's  authorized  replacement  list.

USING  THE  WRONG  CONTROL  WILL  RESULT  IN

IMPROPER  OR  NO  BLOWER  OPERATION.

    Orient  the  control

module  so  that  the  3-wire  motor  plug  can  be  inserted  into  the  socket  in

the  control.    Carefully  insert  the  plug  and  press  it  into  the  socket  until

it  latches.   

A  SLIGHT  CLICK  WILL  BE  HEARD  WHEN

PROPERLY  INSERTED.

    Finish  installing  the  replacement  control  per

one  of  the  three  following  paragraphs,  8a,  8b  or  8c.

8a. 

IF  REPLACING  AN  ECM  2.0  CONTROL

  (control  in  cast

aluminum  can  with  air  vents  on  the  back  of  the  can) 

WITH  AN  ECM

2.3  CONTROL

  (control  containing  black  potting  for  water  protection  in

black  deep-drawn  steel  case  with  no  vents  in  the  bottom  of  the  can),

locate  the  two  through-bolts  and  plastic  tab  that  are  packed  with  the

replacement  control.    Insert  the  plastic  tab  into  the  slot  at  the  perimeter

of the open end of the can so that the pin is located on the inside of the

perimeter of the can.  Rotate the can so that the tab inserts into the tab

locater  hole  in  the  endshield  of  the  motor.    Using  the  two  through-bolts

provided  with  the  replacement  control,  reattach  the  can  to  the  motor.

THE  TWO  THROUGH-BOLTS  PROVIDED  WITH  THE

REPLACEMENT  ECM  2.3  CONTROL  ARE  SHORTER  THAN

THE  BOLTS  ORIGINALLY  REMOVED  FROM  THE  ECM  2.0

CONTROL  AND  MUST  BE  USED  IF  SECURE  ATTACHMENT

OF  THE  CONTROL  TO  THE  MOTOR  IS  TO  BE  ACHIEVED.

DO  NOT  OVERTIGHTEN  THE  BOLTS.

8b. 

IF  REPLACING  AN  ECM  2.3  CONTROL

 

WITH  AN  ECM  2.3

CONTROL

,  the  plastic  tab  and  shorter  through-bolts  are  not  needed.    The

control  can  be  oriented  in  two  positions  180°  apart.   

MAKE  SURE  THE

ORIENTATION  YOU  SELECT  FOR  REPLACING  THE

CONTROL  ASSURES  THE  CONTROL'S  CABLE  CONNECTORS

WILL  BE  LOCATED  DOWNWARD  IN  THE  APPLICATION  SO

THAT  WATER  CANNOT  RUN  DOWN  THE  CABLES  AND  INTO

THE  CONTROL.

    Simply  orient  the  new  control  to  the  motor's  endshield,

insert bolts, and tighten.  

DO  NOT  OVERTIGHTEN  THE  BOLTS.

8c. 

IF  REPLACING  AN  ECM  2.0  CONTROL  WITH  AN  ECM  2.0

CONTROL 

(It  is  recommended  that  ECM  2.3  controls  be  used  for  all

replacements), 

the  new  control  must  be  attached  to  the  motor  using

through  bolts  identical  to  those  removed  with  the  original  control.   

DO

NOT  OVERTIGHTEN  THE  BOLTS.

9. Reinstall  the  blower/motor  assembly  into  the  HVAC  equipment.

Follow  the  manufacturer's  suggested  procedures.

10.  Plug  the  16-pin  control  plug  into  the  motor.    The  plug  is  keyed.

Make  sure  the  connector  is  properly  seated  and  latched.

11.  Plug  the  5-pin  power  connector  into  the  motor.    Even  though  the

plug  is  keyed, 

OBSERVE  THE  PROPER  ORIENTATION.    DO  NOT

FORCE  THE  CONNECTOR.

    It  plugs  in  very  easily  when  properly

oriented.   

REVERSING  THIS  PLUG  WILL  CAUSE  IMMEDIATE

FAILURE  OF  THE  CONTROL  MODULE.

12.  Final  installation  check.    Make  sure  the  motor  is  installed  as  follows:

a. Unit  is  as  far  INTO  the  blower  housing  as  possible.

b. Belly  bands  are  not  on  the  control  module  or  covering  vent  holes.

c. Motor  connectors  should  be  oriented  between  the  4  o’clock  and  8

o’clock  positions  when  the  blower  is  positioned  in  its  final

location  and  orientation.

d. Add  a  drip  loop  to  the  cables  so  that  water  cannot  enter  the  motor

by  draining  down  the  cables.   

Refer  to  Figure  26.

The  installation  is  now  complete.    Reapply  the  AC  power  to  the  HVAC

equipment  and  verify  that  the  new  motor  control  module  is  working

properly.    Follow  the  manufacturer's  procedures  for  disposition  of  the  old

control  module.

Figure 25

Figure 24

Figure 26

TROUBLESHOOTING  ECM

 MOTORS CONT’D.

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower motor 
you need to take the following steps:
 

1.  You MUST have the correct replacement module.  The controls are 

factory programmed for specific operating modes.  Even though they look 

alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT 
WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

 

2.  Begin by removing AC power from the furnace or air handler being 

serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER 

APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect 

power and wait at least 5 minutes before opening motor.

 

3.  It is usually not necessary to remove the motor from the blower 

assembly.  However, it is recommended that the whole blower assembly, 
with the motor, be removed from the furnace/air handler.  (Follow the 
manufacturer’s procedures).  Unplug the two cable connectors to the motor.  
There are latches on each connector.  

DO NOT PULL ON THE WIRES.  

The plugs remove easily when properly released.

 

4.  Locate the two standard ¼" hex head bolts at the rear of the control 

housing (at the back end of the control opposite the shaft end).  

Refer to 

Figure 14.  

Remove these two bolts from the motor and control assembly 

while holding the motor in a way that will prevent the motor or control 
from falling when the bolts are removed.  If an ECM2.0 control is being 
replaced (recognized by an aluminum casting rather that a deep-drawn 
black steel can housing the electronics), remove only the hex-head bolts.  

DO NOT REMOVE THE TORX-HEAD SCREWS.

 

5.  The control module is now free of mechanical attachment to the 

motor endshield but is still connected by a plug and three wires inside 
the control.  Carefully rotate the control to gain access to the plug at 

the control end of the wires.  With thumb and forefinger, reach the latch 

holding the plug to the control and release it by squeezing the latch tab 
and the opposite side of the connector plug and gently pulling the plug 
out of the connector socket in the control.  

DO NOT PULL ON THE 

WIRES.  GRIP THE PLUG ONLY.

 

6.  The control module is now completely detached from the motor.  

Verify with a standard ohmmeter that the resistance from each motor 
lead (in the motor plug just removed) to the motor shell is >100K ohms.  

Refer to Figure 15.  

(Measure to unpainted motor end plate.)  If any motor 

lead fails this test, do not proceed to install the control module.  

THE 

MOTOR IS DEFECTIVE AND MUST BE REPLACED.

  Installing 

the new control module will cause it to fail also.

 

7.  Verify that the replacement control is correct for your application.  

Refer to the manufacturer's authorized replacement list.  

USING THE 

WRONG CONTROL WILL RESULT IN IMPROPER OR NO 
BLOWER OPERATION.

  Orient the control module so that the 3-wire 

motor plug can be inserted into the socket in the control.  Carefully insert 
the plug and press it into the socket until it latches.  

A SLIGHT CLICK 

WILL BE HEARD WHEN PROPERLY INSERTED.

  Finish installing 

the replacement control per one of the three following paragraphs, 8a, 8b or 8c.

 8a. 

IF REPLACING AN ECM 2.0 CONTROL

 (control in cast 

aluminum can with air vents on the back of the can) 

WITH AN ECM 

2.3 CONTROL

 (control containing black potting for water protection in 

black deep-drawn steel case with no vents in the bottom of the can), locate 
the two through-bolts and plastic tab that are packed with the replacement 
control.  Insert the plastic tab into the slot at the perimeter of the open end 
of the can so that the pin is located on the inside of the perimeter of the 
can.  Rotate the can so that the tab inserts into the tab locator hole in the 
endshield of the motor.  Using the two through-bolts provided with the 
replacement control, reattach the can to the motor.

THE TWO THROUGH-BOLTS PROVIDED WITH THE 
REPLACEMENT ECM 2.3 CONTROL ARE SHORTER THAN 
THE BOLTS ORIGINALLY REMOVED FROM THE ECM 2.0 
CONTROL AND MUST BE USED IF SECURE ATTACHMENT OF 
THE CONTROL TO THE MOTOR IS TO BE ACHIEVED.
DO NOT OVERTIGHTEN THE BOLTS.

 

 8b. 

IF REPLACING AN ECM 2.3 CONTROL

 

WITH AN ECM 2.3 

CONTROL

, the plastic tab and shorter through-bolts are not needed.  The 

control can be oriented in two positions 180° apart.  

MAKE SURE THE 

ORIENTATION YOU SELECT FOR REPLACING THE CONTROL 
ASSURES THE CONTROL'S CABLE CONNECTORS WILL 
BE LOCATED DOWNWARD IN THE APPLICATION SO THAT 
WATER CANNOT RUN DOWN THE CABLES AND INTO THE 
CONTROL.

  Simply orient the new control to the motor's endshield, insert 

bolts, and tighten.  

DO NOT OVERTIGHTEN THE BOLTS.

 

8c. 

IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM 2.0 

CONTROL (It is recommended that ECM 2.3 controls be used for all 
replacements), 

the new control must be attached to the motor using through 

bolts identical to those removed with the original control.  

DO NOT 

OVERTIGHTEN THE BOLTS.

 

9.  Reinstall the blower/motor assembly into the HVAC equipment.  

Follow the manufacturer's suggested procedures.

 

10. Plug the 16-pin control plug into the motor.  The plug is keyed.  

Make sure the connector is properly seated and latched.

 

11. Plug the 5-pin power connector into the motor.  Even though the 

plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  DO NOT 

FORCE THE CONNECTOR.

  It plugs in very easily when properly 

oriented.  

REVERSING THIS PLUG WILL CAUSE IMMEDIATE 

FAILURE OF THE CONTROL MODULE.

 12. 

Final installation check.  Make sure the motor is installed as follows:

 

 

a. Unit is as far INTO the blower housing as possible.

 

 

b. Belly bands are not on the control module or covering vent holes.

 

 

c. Motor connectors should be oriented between the 4 o’clock and 8  

      o’clock positions when the blower is positioned in its final    

 

 

  location and orientation.

 

 

d. Add a drip loop to the cables so that water cannot enter the motor  

 

 

  by draining down the cables.  

Refer to Figure 16.

The installation is now complete.  Reapply the AC power to the HVAC 
equipment and verify that the new motor control module is working 
properly.  Follow the manufacturer's procedures for disposition of the old 
control module.

Figure 15

Figure 16

Figure 14

Содержание T24H1

Страница 1: ...T PUMPS Standard Dehumidification MODELS T24H1 T24H1D T30H1 T30H1D T36H1 T36H1D T42H1 T42H1D T48H1 T48H1D T60H1 T60H1D Manual 2100 541D Supersedes 2100 541C File Volume III Tab 17 Date 03 28 14 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned ...

Страница 2: ...e 5B Heating Pressure 23 Table 6A Electrical Specifications T H 24 Table 6B Electrical Specifications T H Dehum 25 Table 7 Indoor Blower Performance 26 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Fresh Air Intake 5 Condensate Drain 5 Installation Instructions Wall Mounting Information ...

Страница 3: ...nter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 T...

Страница 4: ...ss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Conditioning Systems NFPA No 90B Where local r...

Страница 5: ...ct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air duct is used applicable installation codes may limit this cabinet to installation only in a single story structure FILTERS A 1 inch throwaway filter is standard with each unit The filter slides into po...

Страница 6: ...combustible material See Figure 3 for details on opening sizes 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figures 3A 3B 4 Mount bottom mounting bracket 5 Hook top rain flashing attached to front right of supply flange for shipping under back bend of top 6 Position unit in opening and secure with 5 16 lag bolts use 7 8 inch diameter flat washers on the lag bolts 7...

Страница 7: ...cket Back View M L O E R S S S S S T 44 N Q P B FIGURE 2 All dimensions are in inches Dimensional drawings are not to scale T H RIGHT UNIT Dimensions of Basic Unit for Architectural and Installation Requirements Nominal Model Width W Depth D Height H Supply Return A B C B E F G I J K L M N O P Q R S T T24H T30H 38 200 17 125 70 563 7 88 27 88 13 88 27 88 40 00 10 88 25 75 17 93 26 75 28 75 29 25 2...

Страница 8: ... CLEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAULKING ALONG PANEL FOAM AIR SEAL FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE WALL STRUCTURE TOP MIS 311 C Wall Opening and Hole Location View Right Side View WALL HEATER ACCESS SEAL WI...

Страница 9: ...9 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION TOP PANEL HEATER ACCESS FOUR SIDES OF SUPPLY AIR DUCT IS REQUIRED FROM COMBUSTABLE WALL 1 4 CLEARANCE ON ALL MATERIALS Supply Opening FOAM...

Страница 10: ...s This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 INCH CLEARANCE TO COMBUSTIBLE SURFACES ...

Страница 11: ...AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR STRUCTURAL STEEL ATTACH TO TOP 1 000 CLEARANCE 1 000 CLEARANCE PLATE OF WALL C SEE UNIT DIMENSIONS FIGURE 2 OPENING RETURN DUCT 2 x 6 ATTACH TO BOTTOM OVER FRAME...

Страница 12: ... WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE WALL INSTALLATION DUCTED SUPPLY GRILLE OUTSIDE SPACE FALSE WALL RETURN AIR GRILLE OUTSIDE OR BELOW CEILING RAFTERS AS SHOWN FINISHED CEILING SURFACE RAIN FLASHING RAIN FLASHING RETURN AT UNIT NO DUC...

Страница 13: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab locate...

Страница 14: ...g the correct set points NOTE The additional LAB low ambient bypass relay is required to prevent heater operation during low temperature cooling operation OPTIONAL COMPRESSOR CUTOFF THERMOSTAT See Figures 8 9 Heat pump compressor operation at outdoor temperatures below 0 F are neither desirable nor advantageous in term of efficiency An outdoor thermostat can be applied to take the mechanical heati...

Страница 15: ...rmostat This is done to maximize FIGURE 11 ELECTRIC HEAT HOLD OFF WIRING 15 20KW 1 PH 3 PH FIGURE 10 ELECTRIC HEAT HOLD OFF WIRING 4 10KW 1 PH 6 9KW 3 PH efficiency by utilizing the heat pump to bring the conditioned space temperature up rather than cycling on the electric heat due a second stage call for heat from the thermostat on start up coming off a night set back condition or someone increas...

Страница 16: ...ltiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrigerant it must come out o...

Страница 17: ...mpact on the durability of the compressor However reverse operation for over one hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal protector will trip All three phase ZP compressors are wired identically internally As a result once the correct phasing is determined for a specific...

Страница 18: ...cumstances require a change to another time remove the wire from the 60 minute terminal and reconnect to the desired terminal Refer to Figure 12 There is a cycle speed up jumper on the control This can be used for testing purposes to reduce the time between defrost cycle operation without waiting for time to elapse Use a small screwdriver or other metallic object or another inch QC to short betwee...

Страница 19: ... 28 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN ON FIGURE 12 DEFROST CONTROL BOARD ...

Страница 20: ...pump control defective Check for 24V between RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not go into defrost heating only Temperature sensor or heat pump control defective Disconnect temperature sensor from board and jumper across SPEEDUP terminals and SEN JMP terminal...

Страница 21: ... 29986 73 0 11031 111 0 4562 2 0 91008 36 0 29157 74 0 10762 112 0 4464 1 0 88139 37 0 28355 75 0 10501 113 0 4367 0 0 85371 38 0 27577 76 0 10247 114 0 4274 1 0 82699 39 0 26823 77 0 10000 115 0 4182 2 0 80121 40 0 26092 78 0 9760 116 0 4093 3 0 77632 41 0 25383 79 0 9526 117 0 4006 4 0 75230 42 0 24696 80 0 9299 118 0 3921 5 0 72910 43 0 24030 81 0 9077 119 0 3838 6 0 70670 44 0 23384 82 0 8862 ...

Страница 22: ...testing with this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance They shall not be used to adjust charge If charge is in doubt reclaim evacuate and recharge the ...

Страница 23: ... DB 72 WB Low Side High Side 147 345 150 362 152 382 154 403 156 425 157 450 159 477 160 506 162 536 164 568 T60H 75 DB 62 WB Low Side High Side 129 353 130 362 132 374 133 390 134 410 136 432 137 458 137 488 139 522 140 559 80 DB 67 WB Low Side High Side 138 362 139 371 141 384 142 400 144 428 145 443 146 470 147 501 149 535 150 573 85 DB 72 WB Low Side High Side 143 375 144 384 146 397 147 414 1...

Страница 24: ...B0Z B06 B09 230 208 60 3 1 1 1 16 34 42 20 35 45 12 8 8 12 10 10 T24H1 C0Z C06 C09 460 60 3 1 1 1 9 18 23 15 20 25 14 12 10 14 12 10 T30H1 A00 A0Z A04 m AS8 p AF8 230 208 60 1 1 1 1 1 or 2 24 45 48 66 35 50 50 70 8 8 8 4 10 10 10 8 24 42 35 45 8 8 10 10 T30H1 B00 B0Z B06 B09 230 208 60 3 1 1 1 18 36 45 25 40 45 10 8 8 10 10 10 T30H1 C0Z C06 C09 460 60 3 1 1 1 10 19 24 15 20 25 14 12 10 14 12 10 T3...

Страница 25: ...8 60 3 1 1 1 16 34 42 20 35 45 12 8 8 12 10 10 T24H1DC0Z DC06 DC09 460 60 3 1 1 1 9 18 23 15 20 25 14 12 10 14 12 10 T30H1DA00 DA0Z DA04 m DAS8 p DAF8 230 208 60 1 1 1 1 1 or 2 24 45 48 66 35 50 50 70 8 8 8 4 10 10 10 8 24 42 35 45 8 8 10 10 T30H1DB00 DB0Z DB06 DB09 230 208 60 3 1 1 1 18 36 45 25 40 45 10 8 8 10 10 10 T30H1DC0Z DC06 DC09 460 60 3 1 1 1 10 19 24 15 20 25 14 12 10 14 12 10 T36H1DA00...

Страница 26: ...CM indoor motor that automatically adjusts itself to maintain approximately the same rate of indoor airflow in both heating cooling dry wet coil conditions and at both 230 208 or 460 volts Maximum ESP inches WC shown is with 2 thick disposable filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant Blower only CFM reduces during continuous fan m...

Страница 27: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop filter Check correct duct restrictions Symptom Cause Procedure Noisy blower or cabinet Check for loose blower housing panels etc High static creating high blower speed Ch...

Страница 28: ...tion d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVAC equipment and verify that the new motor control module is working properly Follow the manufacturer s procedures for disposition of the old control module Figure 25 Figure 24 Figure 26 TROUBLESHOOTING ECM MOTORS CO...

Отзывы: