PHASE MONITOR

All units with three phase compressors are equipped
with a 3 phase line monitor to prevent compressor
damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor
and phases are correct, the green LED will light.  If
phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  Do not reverse any of the unit factory
wires as damage may occur.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at

all times.  Also, not to needlessly close off supply
and return air registers.  This reduces air flow
through the system, which shortens equipment
service life as well as increasing operating costs.

2. Switching to heating cycle at 75° F or higher outside

temperature may cause a nuisance trip of the remote
reset high pressure switch.  Turn thermostat off then
on to reset the high pressure switch.

3. The heat pump wall thermostats perform multiple

functions.  Be sure that all function switches are
correctly set for the desired operating mode before
trying to diagnose any reported service problems.

4. Check all power fuses or circuit breakers to be sure

they are the correct rating.

5. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

OCCUPIED MODE

VENTILATION SEQUENCE

 –  The ERV and indoor

blower will be continuously energized when the A1
terminal is energized.

COOLING SEQUENCE

  –  On a call for cooling, the

compressor of the unit is energized to provide cooling.
A call for cooling cancels dehumidification mode.
Cooling mode is only available when the timer  is
energized.

Circuit R-Y makes at thermostat pulling in compressor
contactor, starting the compressor and outdoor motor.
The G (indoor motor) circuit is automatically completed
on any call for cooling operation or can be energized by
manual fan switch on subbase for constant air
circulation.  Refer to Figure 14.

HEATING SEQUENCE

  –  On a call for heating, the

compressor and reversing valve of the unit are energized
to provide heat pump heating.  If the room temperature
falls below the 2nd stage heating set point backup
electric heat is energized.  Heat pump heating is only
available when the timer is energized.  If heating is
energized any call for dehumidification is ignored.  If
dehumidification is already energized a call for 2nd
stage heating is needed to cancel dehumidification
mode.

A 24V solenoid coil on reversing valve controls heating
cycle operation.  A thermostat demand for heat
completes R-W1 circuit, pulling in compressor contactor
starting compressor and outdoor motor.  R-G also make
starting indoor blower motor.

DEHUMIDIFICATION SEQUENCE

  –  On a call for

dehumidification the compressor and three way valve of
the unit are energized to provide dehumidification.
Dehumidification mode will continue until the
humidistat is satisfied.  If the room temperature falls
below 1st stage heating setpoint, electric heat will be
energized by the room thermostat and cycle to maintain
room temperature.  If 2nd stage heating setpoint is
reached, dehumidification is de-energized and heat pump
heating is energized.  A call for cooling cancels
dehumidification mode.  Refer to Figure 15.

UNOCCUPIED MODE

Cooling, heating, emergency heat and ventilation are
inhibited.

DEHUMIDIFICATION SEQUENCE

  –  On a call for

dehumidification the compressor and three way valve of
the unit are energized to provide dehumidification.
Dehumidification mode will continue until the
humidistat is satisfied.  If the room temperature falls
below 65 degrees and dehumidification is energized,
electric heat will be energized by the return air
thermostat and cycle to maintain room temperature.

PRESSURE SERVICE PORTS

High and Low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  Pressure tables can be found later in the
manual covering all models on both cooling and heating
cycles.  It is imperative to match the correct pressure
table to the unit by model number.

Содержание SH611D

Страница 1: ...ONS WALL MOUNTED PACKAGE HEAT PUMPS Model SH611D Manual 2100 414C Supersedes 2100 414B File Volume III Tab 17 Date 05 06 05 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as...

Страница 2: ...wer Performance 21 Table 10 Maximum ESP of Operation 21 Table 11 Pressure Table Cooling 22 Table 12 Pressure Table Heating 22 Getting Other Information and Publications For More Information 1 Wall Mou...

Страница 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Co...

Страница 4: ...1 B 230 208 60 3 C 460 60 3 VENTILATIONOPTIONS X Barometric Fresh Air Damper Standard 1 B Blank off Plate M Motorized Fresh Air Damper 1 V Commercial Room Ventilator Motorized with Exhaust E Economize...

Страница 5: ...h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q A B C B D 1 1 6 H S 2 4 4 1 2 2 8 7 4 9 8 7 9 8 7 9 2 8 7 5 1 8 7 9 2 8 7 3 4 9 1 8 5 1 4 0 3 6 1 1 1 2 4 7 3 4 3...

Страница 6: ...should adhere to local codes DUCT WORK Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit All duct work supply and return must...

Страница 7: ...grille filters must be of sufficient size to allow a maximum velocity of 400 fpm FILTERS A 1 inch throwaway filter is supplied with each unit The filter slides into position making it easy to service...

Страница 8: ...ch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 3 and 4 for details WARNING Failur...

Страница 9: ...Manual 2100 414C Page 7 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 10: ...mum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum...

Страница 11: ...Manual 2100 414C Page 9 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS MIS 548 SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 12: ...Manual 2100 414C Page 10 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS MIS 550 FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION...

Страница 13: ...event unauthorized access to the disconnect To convert for the locking capability bend the tab locate in the bottom left hand corner of the disconnect opening under the disconnect access panel straigh...

Страница 14: ...e and in Table 4 will work with this equipment The thermostat and subbase must be matched and the correct operation can be assured only by proper selection and application of these parts FIGURE 8 SHXX...

Страница 15: ...MABLE THERMOSTAT FULL TIME DEHUMIDIFICATION IMPORTANT NOTE Only the thermostat and subbase combinations as shown in Table 4 will work with this equipment The thermostat and subbase must be matched and...

Страница 16: ...or of the equipment must manually place the system switch in this position This is done when there is a known problem with the unit or when the red flashing LED comes on indicating a problem FIGURE 10...

Страница 17: ...low pressure trip by the electronic heat pump control This is a 24 VAC output W2 terminal is second stage heat if equipped O1 terminal is the ventilation input This terminal energizes any factory inst...

Страница 18: ...rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on th...

Страница 19: ...e energized by manual fan switch on subbase for constant air circulation Refer to Figure 14 HEATING SEQUENCE On a call for heating the compressor and reversing valve of the unit are energized to provi...

Страница 20: ...g for time to elapse Use a small screwdriver or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to t...

Страница 21: ...i s a h p r e w o P t c e r r o c e s a h p n o D E L d e r r o f k c e h C y l n o s t i n u e s a h p 3 r o t i n o m t i n u e h t o t s d a e l r e w o p o w t h c t i w S r o t o m r o o d t u o...

Страница 22: ...66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0 44...

Страница 23: ...s n e m i D D 1 1 6 H S 5 7 1 TABLE 7 REFRIGERANTCHARGE l e d o M d e t a R w o l f r i A D O 5 9 e r u t a r e p m e T D O 2 8 e r u t a r e p m e T D 1 1 6 H S 0 5 3 1 1 5 8 4 3 5 0 5 Rated CFM and...

Страница 24: ...S h g i H 9 6 1 8 1 0 7 7 0 2 2 7 9 2 2 3 7 7 4 2 5 7 1 6 2 6 7 2 7 2 6 7 8 7 2 7 7 1 8 2 8 7 0 8 2 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 7 7 8 1 2 7 4 1 2 5 7 7 3 2 6 7 6 5 2 8...

Страница 25: ...Manual 2100 414C Page 23 FIGURE 14 BARD HEAT PUMP COOLING MODE CIRCUIT DIAGRAM FIGURE 15 BARD HEAT PUMP DEHUMIDIFICATION MODE CIRCUIT DIAGRAM...

Отзывы: