background image

Manual 2100-413G
Page

25 of 28

REMOVAL OF FAN SHROUD

1. Disconnect all power to the unit.

2. Remove the screws holding both grilles, one on each

side of unit, and remove grilles.

3. Remove screws holding fan shroud to condenser and

bottom.  Nine (9) screws.

4. Unwire condenser fan motor.

5. Slide complete motor, fan blade, and shroud

assembly out the left side of the unit.

6. Service motor/fan as needed.

7. Reverse steps to reinstall.

G

N

I

L

O

O

C

G

N

I

T

A

E

H

l

e

d

o

M

d

e

t

a

R

w

o

l

f

r

i

A

D

O

5

9

e

r

u

t

a

r

e

p

m

e

T

D

O

2

8

e

r

u

t

a

r

e

p

m

e

T

D

O

7

4

e

r

u

t

a

r

e

p

m

e

T

D

O

7

1

e

r

u

t

a

r

e

p

m

e

T

D

1

8

3

H

S

0

0

1

1

8

1

-

5

1

1

2

-

8

1

8

1

-

4

1

6

1

-

2

1

D

1

3

4

H

S

0

0

3

1

1

2

-

8

1

1

2

-

8

1

2

1

-

8

2

1

-

8

D

1

9

4

H

S

0

5

2

1

8

1

-

5

1

7

1

-

4

1

9

1

-

5

1

6

1

-

2

1

TABLE  8

RECOMMENDED OPERATING RANGES

* Rated CFM and ESP on high speed tap.

l

e

d

o

M

d

e

t

a

R

*

M

F

C

d

e

t

a

R

*

P

S

E

d

e

d

n

e

m

m

o

c

e

R

e

g

n

a

R

w

o

l

f

r

i

A

D

1

8

3

H

S

0

0

1

1

5

1

.

0

5

8

0

5

2

1

D

1

3

4

H

S

0

0

3

1

5

1

.

0

0

1

1

5

7

4

1

D

1

9

4

H

S

0

5

2

1

0

2

.

0

0

1

1

5

7

4

1

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit
rating plate.  Optimum unit performance will occur with
a refrigerant charge shown on the unit serial plate.

If correct charge is in doubt, recover the refrigerant and
recharge per the charge on the unit rating plate.  See
Table 7 for proper subcooling levels for evaluation of
proper charge.

"A"

AIRFLOW

MIS-1724

FIGURE  13

FAN BLADE SETTING

TABLE  6

FAN BLADE SETTING

DIMENSION

l

e

d

o

M

A

n

o

i

s

n

e

m

i

D

D

1

8

3

H

S

D

1

3

4

H

S

D

1

9

4

H

S

5

7

.

1

FAN BLADE SETTING DIMENSIONS

Shown in Figure 13 are the correct fan blade setting
dimensions for proper air delivery across the outdoor
coil.

Any service work requiring removal or adjustment in
the fan and/or motor area will require that the
dimensions below be checked and blade adjusted in or
out on the motor shaft accordingly.

1

Expected subcooling levels during cooling operation.
Above subcooling levels are provided to troubleshoot low
charge or overcharged conditions.  If charge is in doubt,
evacuate and recharge the unit to the refrigerant charge
listed on the serial plate.

TABLE  7  

1

REFRIGERANT CHARGE

SUBCOOLING LEVEL

Содержание SH381D Series

Страница 1: ...ION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Models SH381D SH431D SH491D Manual 2100 413G Supersedes 2100 413F File Volume III Tab 17 Date 09 26 07 Bard Manufacturing Company Inc Bryan Ohio 43506...

Страница 2: ...ing Dimensions 25 Removal of Fan Shroud 25 Refrigerant Charge 25 Pressure Tables 27 Figures Figure 1 Unit Dimensions 6 Figure 2 Fresh Air Damper Assembly 8 Figure 3 Mounting Instructions 10 Figure 4 E...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...d 1 PhenolicCoatedEvaporator 2 PhenolicCoatedCondenser 3 PhenolicCoatedEvaporator andCondenser MODEL NUMBER REVISIONS OUTLET OPTIONS X Front Standard COLOR OPTIONS X Beige Standard 1 White 4 Buckeye G...

Страница 5: ...A 1 m u m i x a M l l a n r e t x E r o e s u F t i u c r i C r e k a e r B 2 r e w o P d l e i F e z i S e r i W 2 e r i W d n u o r G e z i S A t k C B t k C A t k C B t k C A t k C B t k C A t k C...

Страница 6: ...p u S n r u t e R W D H A B C B E F G I J K L M N O P Q R S T D 1 8 3 H S D 1 3 4 H S D 1 9 4 H S 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4...

Страница 7: ...h each unit The filter slides into position making it easy to service This filter can be serviced from the outside by removing the service door A 1 inch washable filter and a 2 inch pleated filter are...

Страница 8: ...unched in the service panel If the unit is equipped with a fresh air damper assembly the assembly is shipped already attached to the unit The damper blade is locked in the closed position To allow the...

Страница 9: ...g would then be 32 x 12 See Figures 3 and 4 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 4 4 Mount bottom mounting bracket 5 Hook top rain flashing...

Страница 10: ...Manual 2100 413G Page 10 of 28 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...s is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mat...

Страница 12: ...Manual 2100 413G Page 12 of 28 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 13: ...Manual 2100 413G Page 13 of 28 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...g current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab locate in th...

Страница 15: ...Manual 2100 413G Page 15 of 28 FIGURE 8 SHXXXDX HOT GAS REHEAT DURING DEHUMIDIFICATION WITH CS2000A2 ENERGY MONITOR FULL TIME DEHUMIDIFICATION...

Страница 16: ...Manual 2100 413G Page 16 of 28 FIGURE 9 SHXXXDX HOT GAS REHEAT DURING DEHUMIDIFICATION WITH PROGRAMMABLE THERMOSTAT FULL TIME DEHUMIDIFICATION...

Страница 17: ...talled FIGURE 10 10KW 1 PH 6 9KW 3 PH TABLE 2 THERMOSTAT WIRE SIZE r e m r o f s n a r T A V A L F e g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 5 3 2 e g u a g 0 2 e g u a g 8 1 e g u...

Страница 18: ...ntrolled outputs are required 6 if no ventilation system is installed For proper system operation under Emergency Heat conditions where the compressor needs to be deactivated the B W2 E outputs need t...

Страница 19: ...or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on...

Страница 20: ...can be energized by manual fan switch on subbase for constant air circulation Refer to Figure 14 HEATING SEQUENCE On a call for heating the compressor and reversing valve of the unit are energized to...

Страница 21: ...river or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instr...

Страница 22: ...c p m u p t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n...

Страница 23: ...0 48 0 49 0 50 0 51 0 52 0 53 0 54 0 55 0 56 0 57 0 58 0 59 0 60 0 61 0 62 0 63 0 64 0 65 0 66 0 67 0 68 0 69 0 70 0 71 0 72 0 73 0 74 0 39898 38757 37652 36583 35548 34545 33574 32634 31723 30840 29...

Страница 24: ...d e i p u c c O X X X X X X X e d o M g n i l o o C m u h e D w X X X X X X g n i t a e H e g a t S t s 1 d e i p u c c o n U X X X X X X X g n i t a e H e g a t S t s 1 d e i p u c c O X X X X X X g...

Страница 25: ...7 4 1 D 1 9 4 H S 0 5 2 1 0 2 0 0 1 1 5 7 4 1 REFRIGERANT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a refrigerant charge shown on...

Страница 26: ...i o C 0 1 2 3 5 2 6 1 5 7 4 1 0 5 3 1 0 5 1 1 5 7 4 1 0 5 3 1 0 5 1 1 5 2 8 5 2 4 1 5 2 3 1 0 0 2 1 5 2 0 1 5 2 3 1 0 0 2 1 5 2 0 1 0 5 7 5 2 1 1 0 0 1 1 0 0 0 1 5 2 8 0 0 1 1 0 0 0 1 0 5 8 5 7 6 0 0...

Страница 27: ...8 8 3 2 4 8 5 5 2 5 8 3 7 2 6 8 2 9 2 8 8 1 1 3 0 9 1 3 3 2 9 2 5 3 D 1 9 4 H S B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 2 7 8 9 1 2 7 3 1 2 8 7 8 2 2 3 7 4 4 2 4 7 0 6 2 5 7 8 7 2 7...

Страница 28: ...Manual 2100 413G Page 28 of 28 FIGURE 14 BARD HEAT PUMP COOLING MODE CIRCUIT DIAGRAM FIGURE 15 BARD HEAT PUMP DEHUMIDIFICATION MODE CIRCUIT DIAGRAM...

Отзывы: