background image

Manual 2100-413G
Page

20 of 28

PHASE MONITOR

All units with three phase compressors are equipped
with a 3 phase line monitor to prevent compressor
damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor
and phases are correct, the green LED will light.  If
phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit. Do not reverse any of the unit factory
wires as damage may occur.

SERVICE HINTS

1. Caution owner/operator to maintain clean air filters

at all times.  Also, not to needlessly close off supply
and return air registers.  This reduces airflow
through the system, which shortens equipment
service life as well as increasing operating costs.

2. Switching to heating cycle at 75°F or higher outside

temperature may cause a nuisance trip of the remote
reset high pressure switch.  Turn thermostat off then
on to reset the high pressure switch.

3. The heat pump wall thermostats perform multiple

functions.  Be sure that all function switches are
correctly set for the desired operating mode before
trying to diagnose any reported service problems.

4. Check all power fuses or circuit breakers to be sure

they are the correct rating.

5. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

OCCUPIED MODE

VENTILATION SEQUENCE

 –  The ERV and indoor

blower will be continuously energized when the A1
terminal is energized.

COOLING SEQUENCE

  –  On a call for cooling, the

compressor of the unit is energized to provide cooling.
A call for cooling cancels dehumidification mode.
Cooling mode is only available when the timer  is
energized.

Circuit R-Y makes at thermostat pulling in compressor
contactor, starting the compressor and outdoor motor.
The G (indoor motor) circuit is automatically completed
on any call for cooling operation or can be energized by
manual fan switch on subbase for constant air
circulation.  Refer to Figure 14.

HEATING SEQUENCE

  –  On a call for heating, the

compressor and reversing valve of the unit are energized
to provide heat pump heating.  If the room temperature
falls below the 2nd stage heating set point backup
electric heat is energized.  Heat pump heating is only
available when the timer is energized.  If heating is
energized any call for dehumidification is ignored.  If
dehumidification is already energized a call for 2nd
stage heating is needed to cancel dehumidification
mode.

A 24V solenoid coil on reversing valve controls heating
cycle operation.  A thermostat demand for heat
completes R-W1 circuit, pulling in compressor contactor
starting compressor and outdoor motor.  R-G also make
starting indoor blower motor.

DEHUMIDIFICATION SEQUENCE

  –  On a call for

dehumidification the compressor and three way valve of
the unit are energized to provide dehumidification.
Dehumidification mode will continue until the
humidistat is satisfied.  If the room temperature falls
below 1st stage heating setpoint, electric heat will be
energized by the room thermostat and cycle to maintain
room temperature.  If 2nd stage heating setpoint is
reached, dehumidification is de-energized and heat pump
heating is energized.  A call for cooling cancels
dehumidification mode.  Refer to Figure 15.

UNOCCUPIED MODE

Cooling, heating, emergency heat and ventilation are
inhibited.

DEHUMIDIFICATION SEQUENCE

  –  On a call for

dehumidification the compressor and three way valve of
the unit are energized to provide dehumidification.
Dehumidification mode will continue until the
humidistat is satisfied.  If the room temperature falls
below 65 degrees and dehumidification is energized,
electric heat will be energized by the return air
thermostat and cycle to maintain room temperature.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  Pressure tables can be found later in the
manual covering all models on both cooling and heating
cycles.  It is imperative to match the correct pressure
table to the unit by model number.

Содержание SH381D Series

Страница 1: ...ION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Models SH381D SH431D SH491D Manual 2100 413G Supersedes 2100 413F File Volume III Tab 17 Date 09 26 07 Bard Manufacturing Company Inc Bryan Ohio 43506...

Страница 2: ...ing Dimensions 25 Removal of Fan Shroud 25 Refrigerant Charge 25 Pressure Tables 27 Figures Figure 1 Unit Dimensions 6 Figure 2 Fresh Air Damper Assembly 8 Figure 3 Mounting Instructions 10 Figure 4 E...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...d 1 PhenolicCoatedEvaporator 2 PhenolicCoatedCondenser 3 PhenolicCoatedEvaporator andCondenser MODEL NUMBER REVISIONS OUTLET OPTIONS X Front Standard COLOR OPTIONS X Beige Standard 1 White 4 Buckeye G...

Страница 5: ...A 1 m u m i x a M l l a n r e t x E r o e s u F t i u c r i C r e k a e r B 2 r e w o P d l e i F e z i S e r i W 2 e r i W d n u o r G e z i S A t k C B t k C A t k C B t k C A t k C B t k C A t k C...

Страница 6: ...p u S n r u t e R W D H A B C B E F G I J K L M N O P Q R S T D 1 8 3 H S D 1 3 4 H S D 1 9 4 H S 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4...

Страница 7: ...h each unit The filter slides into position making it easy to service This filter can be serviced from the outside by removing the service door A 1 inch washable filter and a 2 inch pleated filter are...

Страница 8: ...unched in the service panel If the unit is equipped with a fresh air damper assembly the assembly is shipped already attached to the unit The damper blade is locked in the closed position To allow the...

Страница 9: ...g would then be 32 x 12 See Figures 3 and 4 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 4 4 Mount bottom mounting bracket 5 Hook top rain flashing...

Страница 10: ...Manual 2100 413G Page 10 of 28 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...s is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mat...

Страница 12: ...Manual 2100 413G Page 12 of 28 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 13: ...Manual 2100 413G Page 13 of 28 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...g current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab locate in th...

Страница 15: ...Manual 2100 413G Page 15 of 28 FIGURE 8 SHXXXDX HOT GAS REHEAT DURING DEHUMIDIFICATION WITH CS2000A2 ENERGY MONITOR FULL TIME DEHUMIDIFICATION...

Страница 16: ...Manual 2100 413G Page 16 of 28 FIGURE 9 SHXXXDX HOT GAS REHEAT DURING DEHUMIDIFICATION WITH PROGRAMMABLE THERMOSTAT FULL TIME DEHUMIDIFICATION...

Страница 17: ...talled FIGURE 10 10KW 1 PH 6 9KW 3 PH TABLE 2 THERMOSTAT WIRE SIZE r e m r o f s n a r T A V A L F e g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 5 3 2 e g u a g 0 2 e g u a g 8 1 e g u...

Страница 18: ...ntrolled outputs are required 6 if no ventilation system is installed For proper system operation under Emergency Heat conditions where the compressor needs to be deactivated the B W2 E outputs need t...

Страница 19: ...or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on...

Страница 20: ...can be energized by manual fan switch on subbase for constant air circulation Refer to Figure 14 HEATING SEQUENCE On a call for heating the compressor and reversing valve of the unit are energized to...

Страница 21: ...river or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instr...

Страница 22: ...c p m u p t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n...

Страница 23: ...0 48 0 49 0 50 0 51 0 52 0 53 0 54 0 55 0 56 0 57 0 58 0 59 0 60 0 61 0 62 0 63 0 64 0 65 0 66 0 67 0 68 0 69 0 70 0 71 0 72 0 73 0 74 0 39898 38757 37652 36583 35548 34545 33574 32634 31723 30840 29...

Страница 24: ...d e i p u c c O X X X X X X X e d o M g n i l o o C m u h e D w X X X X X X g n i t a e H e g a t S t s 1 d e i p u c c o n U X X X X X X X g n i t a e H e g a t S t s 1 d e i p u c c O X X X X X X g...

Страница 25: ...7 4 1 D 1 9 4 H S 0 5 2 1 0 2 0 0 1 1 5 7 4 1 REFRIGERANT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a refrigerant charge shown on...

Страница 26: ...i o C 0 1 2 3 5 2 6 1 5 7 4 1 0 5 3 1 0 5 1 1 5 7 4 1 0 5 3 1 0 5 1 1 5 2 8 5 2 4 1 5 2 3 1 0 0 2 1 5 2 0 1 5 2 3 1 0 0 2 1 5 2 0 1 0 5 7 5 2 1 1 0 0 1 1 0 0 0 1 5 2 8 0 0 1 1 0 0 0 1 0 5 8 5 7 6 0 0...

Страница 27: ...8 8 3 2 4 8 5 5 2 5 8 3 7 2 6 8 2 9 2 8 8 1 1 3 0 9 1 3 3 2 9 2 5 3 D 1 9 4 H S B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 2 7 8 9 1 2 7 3 1 2 8 7 8 2 2 3 7 4 4 2 4 7 0 6 2 5 7 8 7 2 7...

Страница 28: ...Manual 2100 413G Page 28 of 28 FIGURE 14 BARD HEAT PUMP COOLING MODE CIRCUIT DIAGRAM FIGURE 15 BARD HEAT PUMP DEHUMIDIFICATION MODE CIRCUIT DIAGRAM...

Отзывы: