WIRING  –  MAIN POWER

Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR” type circuit breaker
size.  Each outdoor unit is marked with a “Minimum
Circuit Ampacity”.  This means that the field wiring
used must be sized to carry that amount of current.
Depending on the installed KW of electric heat, there
may be two field power circuits required.  If this is the
case, the unit serial plate will so indicate.  All models
are suitable only for connection with copper wire.  Each
unit and/or wiring diagram will be marked “Use Copper
Conductors Only”.  These instructions 

must be 

adhered

to.

  

Refer to the National Electrical Code (NEC) for

complete current carrying capacity data on the various
insulation grades of wiring material.  All wiring must
conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°C
copper) for all models including the most commonly
used heater sizes.  Also shown are the number of field
power circuits required for the various models with
heaters.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is to
be used with the equipment.  The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.

The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect.  To
convert for the locking capability, bend the tab locate in
the bottom left hand corner of the disconnect opening
under the disconnect access panel straight out.  This tab
will now line up with the slot in the door.  When shut, a
padlock may be placed through the hole in the tab
preventing entry.  See “Start Up” section for important
information on three phase scroll compressor start ups.

WIRING  –  LOW VOLTAGE WIRING

230 / 208V, 1 phase and 3 phase equipment dual
primary voltage transformers.  All equipment leaves the
factory wired on 240V tap.  For 208V operation,
reconnect from 240V to 208V tap.  The acceptable
operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field

power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).

Ten (10) wires should be run from thermostat subbase to
the 24V terminal board in the unit.  A nine conductor,
18 gauge copper color-coded thermostat cable is
recommended.  The connection points are shown in
Figures 8 and 9.

IMPORTANT

Only the thermostats shown in this Manual
have been tested with this equipment for
proper operation.  Proper unit operation with
thermostats not listed in this Manual, cannot
be assured.

You assume responsibility for proper
operation of the unit when using thermostats
other than those listed above.

Содержание SH381D Series

Страница 1: ...ION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Models SH381D SH431D SH491D Manual 2100 413G Supersedes 2100 413F File Volume III Tab 17 Date 09 26 07 Bard Manufacturing Company Inc Bryan Ohio 43506...

Страница 2: ...ing Dimensions 25 Removal of Fan Shroud 25 Refrigerant Charge 25 Pressure Tables 27 Figures Figure 1 Unit Dimensions 6 Figure 2 Fresh Air Damper Assembly 8 Figure 3 Mounting Instructions 10 Figure 4 E...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...d 1 PhenolicCoatedEvaporator 2 PhenolicCoatedCondenser 3 PhenolicCoatedEvaporator andCondenser MODEL NUMBER REVISIONS OUTLET OPTIONS X Front Standard COLOR OPTIONS X Beige Standard 1 White 4 Buckeye G...

Страница 5: ...A 1 m u m i x a M l l a n r e t x E r o e s u F t i u c r i C r e k a e r B 2 r e w o P d l e i F e z i S e r i W 2 e r i W d n u o r G e z i S A t k C B t k C A t k C B t k C A t k C B t k C A t k C...

Страница 6: ...p u S n r u t e R W D H A B C B E F G I J K L M N O P Q R S T D 1 8 3 H S D 1 3 4 H S D 1 9 4 H S 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4...

Страница 7: ...h each unit The filter slides into position making it easy to service This filter can be serviced from the outside by removing the service door A 1 inch washable filter and a 2 inch pleated filter are...

Страница 8: ...unched in the service panel If the unit is equipped with a fresh air damper assembly the assembly is shipped already attached to the unit The damper blade is locked in the closed position To allow the...

Страница 9: ...g would then be 32 x 12 See Figures 3 and 4 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 4 4 Mount bottom mounting bracket 5 Hook top rain flashing...

Страница 10: ...Manual 2100 413G Page 10 of 28 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...s is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mat...

Страница 12: ...Manual 2100 413G Page 12 of 28 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 13: ...Manual 2100 413G Page 13 of 28 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...g current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab locate in th...

Страница 15: ...Manual 2100 413G Page 15 of 28 FIGURE 8 SHXXXDX HOT GAS REHEAT DURING DEHUMIDIFICATION WITH CS2000A2 ENERGY MONITOR FULL TIME DEHUMIDIFICATION...

Страница 16: ...Manual 2100 413G Page 16 of 28 FIGURE 9 SHXXXDX HOT GAS REHEAT DURING DEHUMIDIFICATION WITH PROGRAMMABLE THERMOSTAT FULL TIME DEHUMIDIFICATION...

Страница 17: ...talled FIGURE 10 10KW 1 PH 6 9KW 3 PH TABLE 2 THERMOSTAT WIRE SIZE r e m r o f s n a r T A V A L F e g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 5 3 2 e g u a g 0 2 e g u a g 8 1 e g u...

Страница 18: ...ntrolled outputs are required 6 if no ventilation system is installed For proper system operation under Emergency Heat conditions where the compressor needs to be deactivated the B W2 E outputs need t...

Страница 19: ...or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on...

Страница 20: ...can be energized by manual fan switch on subbase for constant air circulation Refer to Figure 14 HEATING SEQUENCE On a call for heating the compressor and reversing valve of the unit are energized to...

Страница 21: ...river or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instr...

Страница 22: ...c p m u p t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n...

Страница 23: ...0 48 0 49 0 50 0 51 0 52 0 53 0 54 0 55 0 56 0 57 0 58 0 59 0 60 0 61 0 62 0 63 0 64 0 65 0 66 0 67 0 68 0 69 0 70 0 71 0 72 0 73 0 74 0 39898 38757 37652 36583 35548 34545 33574 32634 31723 30840 29...

Страница 24: ...d e i p u c c O X X X X X X X e d o M g n i l o o C m u h e D w X X X X X X g n i t a e H e g a t S t s 1 d e i p u c c o n U X X X X X X X g n i t a e H e g a t S t s 1 d e i p u c c O X X X X X X g...

Страница 25: ...7 4 1 D 1 9 4 H S 0 5 2 1 0 2 0 0 1 1 5 7 4 1 REFRIGERANT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a refrigerant charge shown on...

Страница 26: ...i o C 0 1 2 3 5 2 6 1 5 7 4 1 0 5 3 1 0 5 1 1 5 7 4 1 0 5 3 1 0 5 1 1 5 2 8 5 2 4 1 5 2 3 1 0 0 2 1 5 2 0 1 5 2 3 1 0 0 2 1 5 2 0 1 0 5 7 5 2 1 1 0 0 1 1 0 0 0 1 5 2 8 0 0 1 1 0 0 0 1 0 5 8 5 7 6 0 0...

Страница 27: ...8 8 3 2 4 8 5 5 2 5 8 3 7 2 6 8 2 9 2 8 8 1 1 3 0 9 1 3 3 2 9 2 5 3 D 1 9 4 H S B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 2 7 8 9 1 2 7 3 1 2 8 7 8 2 2 3 7 4 4 2 4 7 0 6 2 5 7 8 7 2 7...

Страница 28: ...Manual 2100 413G Page 28 of 28 FIGURE 14 BARD HEAT PUMP COOLING MODE CIRCUIT DIAGRAM FIGURE 15 BARD HEAT PUMP DEHUMIDIFICATION MODE CIRCUIT DIAGRAM...

Отзывы: