Manual 2100-577C
Page
5 of 50
QW
S
ERIES GEOTHERMAL R-410A STAGED CAPACITY GENERAL INFORMATION
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National
Electric Code (latest revision), article 310 for power conductor sizing.
CAUTION:
When more than one field power conductor circuit is run through one conduit, the conductors must be
derated. Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more
than three conductors are in a raceway.
TABLE 1
Electrical Specifications
MODEL
RATED
VOLTS, Hz
& PHASE
SINGLE CIRCUIT
NO. FIELD
POWER
CIRCUITS
MINIMUM
CIRCUIT
AMPACITY
MAXIMUM EXTERNAL
FUSE OR CIRCUIT
BREAKER
QW2S2-A0Z
QW2S2-B0Z
QW2S2-C0Z
230/208-60-1
230/208-60-3
460-60-3
1
1
1
19
12
7.5
30
20
15
QW3S2-A0Z
QW3S2-B0Z
QW3S2-C0Z
230/208-60-1
230/208-60-3
460-60-3
1
1
1
25
20
11
40
30
15
QW4S2-A0Z
QW4S2-B0Z
QW4S2-C0Z
230/208-60-1
230/208-60-3
460-60-3
1
1
1
33
24
13
50
35
20
QW5S2-A0Z
QW5S2-B0Z
QW5S2-C0Z
230/208-60-1
230/208-60-3
460-60-3
1
1
1
41
28
13
60
40
20
NOTES
Insert “D” for dehumidification with hot gas reheat.
Reference 7960-612 for complete details.
If “X” control option is selected, then thermostat and humidistat, if
applicable, or DDC control system must be field supplied.
l
CS9B-THO and -THOC are BACnet w/shielded twisted pair wiring.
m
CS9BE-THO and -THOC are BACnet w/shielded twisted pair wiring
and Ethernet port.
Not available for dehumidification models.
FILTER OPTIONS
X – 2-Inch Pleated
(MERV8)
STEP CAPACITY |
CAPACITY |
2 – 2 Ton
3 – 3 Ton
4 – 4 Ton
5 – 5 Ton
MODEL NUMBER |
Q-TEC™ Model
REVISION |
COLOR
4 – Buckeye Gray paint
X – Beige paint
V – Platinum w/Slate
Front (Vinyl)
FACTORY-INSTALLED PUMP & PIPING OPTIONS
X – None; all pump and water connections field installed, requires field piping to the coaxial
water coil using double o-ring fittings, which must be ordered separately.
P – Threaded water connections
1 – DORFC-1 double o-ring flow center, single Grundfos UP26-99F pump piped to water coil
with 150 PSI reinforced hose
2 – DORFC-2 double o-ring flow center, double Grundfos UP26-99F pump piped to water coil
with 150 PSI reinforced hose
3 – Single Grundfos UPS15-42F pump, isolation valves both ends, piped with copper to double
o-ring fittings back corners of unit
4 – Single Grundfos UP26-64F pump, isolation valves both ends, piped with copper to double
o-ring fittings back corners of unit
5 – Single Grundfos UPS26-99-FC pump, isolation valves both ends, piped with copper to
double o-ring fittings back corners of unit
VOLTS & PHASE
A – 230/208/60/1
B – 230/208/60/3
C – 460/60/3
COIL OPTIONS
C – Copper water
N – Cupronickel
KW
0Z – OKW
QW
3
S
2
A
0Z
B
X
V
X
C
X
SPECIALTY
PRODUCTS
(Non-Standard)
|
VENTILATION OPTIONS |
B - Blank-off Plate
V - Commercial Ventilator - Motorized w/Exhaust Spring Return
R - Energy Recovery Ventilator w/Independent Intake & Exhaust Control
S - Energy Recovery Ventilator w/Intelligent Frost Control Option
CLIMATE CONTROL OPTIONS (Factory Mounted)
X – 24V Terminal Block Only
D – 8403-060 Electronic/Programmable Thermostat w/Humidity Control
H – 8403-060 Prog. Thermostat w/Humidity C 8403-067 CO2 Controller
K – 24V Terminal Block + 8403-067 CO2 Controller Only
1 – CompleteStat CS9B-THO (Temp, Humidity & Occupancy)
l
2 – CompleteStat CS9B-THOC (THO + CO2)
l
3 – CompleteStat CS9BE-THO (THO w/Ethernet)
m
4 – CompleteStat CS9BE-THOC (THO + CO2 w/Ethernet)
m
5 – 8403-069 Viconics VT7652H5000B w/BACnet
6 – 8403-069 Vi 8403-067 CO2 Controller