Manual 2100-577C
Page
13 of 50
The
rear drain
can be used with wall thickness of up to
10 inches where a water trap can be installed between
the unit and the interior wall (see Figure 8B). The trap
cannot extend beyond the edge of the unit or it will
interfere with the wall mounting bracket. The drain
can be routed through the floor or through the wall. If
the drain is routed through the wall, the drain line must
be positioned such that it will not interfere with the
sleeve flange or the grille (see Figure 8C).
If the drain
is to be routed through an unconditioned space, it must
be protected from freezing.
Figure 8C
Rear Drain (Top View)
WALL BRACKET
MIST ELIMINATOR SERVICE
(Optional – only used with one of the
vent options)
A mist eliminator is supplied with the wall sleeve. The
mist eliminator is constructed of aluminum frame and
mesh. The mist eliminator is located in the top section
of the wall sleeve and can be removed from the inside
of the building without removing the unit from the wall.
This requires that the ventilation package must be
removed.
The steps necessary to remove each of the vent options
are listed following.
It is recommended that the mist eliminator be
inspected annually and serviced as required. The mist
eliminator can be inspected from the outside of the
building by looking through the outdoor grille. The
mist eliminator can be serviced from the outside. The
outdoor grille must be removed to do so.
The mist eliminator can be cleaned by washing with
soap and water. The excess water should be shaken off
the mist eliminator before it is reinstalled.
Commercial Room Ventilator Option
Before starting the removal make sure the power has
been turned off. The hinged return air grille panel
must be opened. The commercial room ventilator
(CRV) can be seen after the panel has been removed.
The CRV must be removed to gain access to the mist
eliminator.
1. The two mounting screws in the front of the CRV
must be removed.
2. The power connectors for the CRV (located on
the right side of the unit) must be disconnected.
Squeeze the tabs on the sides of the connector and
pull straight out. Unplug both of the connectors.
3. Slide the CRV straight out of the unit.
The mist eliminator can be seen through the opening
in the back of the unit. The mist eliminator must be
raised up and the bottom can be pulled toward the
front of the unit and removed.
WALL (MAXIMUM
10” FOR REAR
DRAIN)
DRAIN LINE
COUPLINGS NOT
SHOWN BUT
RECOMMENDED
FOR EASE OF
REMOVABILITY
FOR SERVICE
SLEEVE
WATER
TRAP
UNIT