background image

Manual

2100-435F

Page

15 of 40

NOTE: The voltage should be measured at the field

power connection point in the unit and while the
unit is operating at full load (maximum
amperage operating condition).

The standard Climate Control 

Option X

 is a remote

thermostat connection terminal block.  See Figure 16 for
wiring diagram.  Compatible thermostats are listed in
Table 4.

The Climate Control 

Option E

 is an electronic,

programmable thermostat and a humidistat.  The sub
base of the thermostat and the humidistat are factory
wired to the front panel of the unit.  See Figure 16A for
wiring diagram.  Compatible for use with Energy
Recovery Ventilator or Ventilator.

The Climate Control 

Option F

 is an electronic, non-

programmable thermostat, timer and a humidistat.  The
sub base of the thermostat and the timer are factory
wired to the front panel of the unit.  See Figure 16B for
wiring diagram.  Compatible for use with Energy
Recovery Ventilator or Ventilator.

The Climate Control 

Option G

 is an electronic,

non-programmable thermostat and humidistat.  The
subbase of the thermostat is factory wired to the front
panel of the unit.  This option is compatible for use with
the optional CS2000A1 Energy Control Monitor and a
terminal block is provided for connection to the
CS2000A1.  See Figure 16C for wiring diagram.
Compatible for use with Energy Recovery Ventilator or
Ventilator.

NOTE:  On options X and G the CS2000A1 (or other

field provided means to control ventilation) must
be used if any of the mechanical (motorized)
ventilation options are installed.

WIRING  –  MAIN POWER

Refer to the unit rating plate and/or Table 2 for wire
sizing information and maximum fuse or “HACR Type”
circuit breaker size.  Each unit is marked with a
“Minimum Circuit Ampacity”.  This means that the
field wiring used must be sized to carry that amount of
current.  Depending on the installed KW of electric
heat, there may be two field power circuits required.  If
this is the case, the unit serial plate will so indicate.  All
models are suitable only for connection with copper
wire.  Each unit and/or wiring diagram will be marked
“Use Copper Conductors Only”.  These instructions

MUST BE

 adhered to.  Refer to the National Electrical

Code (NEC) for complete current carrying capacity data
on the various insulation grades of wiring material.  All
wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°C
copper) for all models, including the most commonly
used heater sizes.  Also shown are the number of field
power circuits required for the various models with
heaters.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR Type” circuit breaker that is to
be used with the equipment.  The correct size must be
used for proper circuit protection, and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.

The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect.

See Start Up section for information on three phase
scroll compressor start-ups.

The field wiring connections are located behind the top
and hinged panel in the circuit breaker panel.  See
Figure 14.

WIRING  –  LOW VOLTAGE WIRING

230/208V, 1 PHASE AND 3 PHASE EQUIPMENT
DUAL PRIMARY VOLTAGE TRANSFORMERS.

All Equipment leaves the factory wired on 240V tap.
For 208V operation, reconnect from 240V to 208V tap.
The acceptable operating voltage range for the 240 and
208V taps are as noted in Table 3.

TABLE  3

OPERATING VOLTAGE RANGE

P

A

T

E

G

N

A

R

V

0

4

2

6

1

2

3

5

2

V

8

0

2

7

8

1

0

2

2

DEHUMIDIFICATION
CONTROL

THERMOSTAT
&  HUMIDISTAT
CONTROLS

ELECTRIC
HEATERS

CIRCUIT BREAKER

PANEL &

CONTROLS

INDOOR
BLOWER

REMOTE

THERMOSTAT

TERMINAL

BLOCK

SIDE FIELD WIRE

ENTRANCE

LOWER
CONTROL
PANEL

FIGURE  14

COMPONENT LOCATION

Содержание QTEC QH244D

Страница 1: ...3D QH423D QH483D QH603D QTEC SERIES PACKAGED HEAT PUMP INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 435F Supersedes 210...

Страница 2: ...croll Compressor Start Up Information 23 Service Hints 24 Mist Eliminator Service 24 Vent Options 25 Sequence of Operation 28 Optional Climate Controls Sequence of Operation 28 29 Refrigerant Tube Sch...

Страница 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Страница 4: ...Motorized w Exhaust Spring Return FILTER OPTIONS X 1 Inch Fiberglass Standard F 2 Inch Fiberglass P 2 Inch Pleated COLOR OPTIONS V Platinum w Slate Front Vinyl 4 Gray paint TABLE 1 FACTORY BUILT IN EL...

Страница 5: ...R E W O P E R I W E Z I S 2 D N U O R G E R I W E Z I S 3 M U M I N I M T I U C R I C Y T I C A P M A 1 M U M I X A M L A N R E T X E R O E S U F T I U C R I C R E K A E R B 2 D L E I F R E W O P E Z...

Страница 6: ...0 B D 3 8 4 H Q 6 0 B D 9 0 B D 5 5 1 B D 3 8 0 2 0 3 2 1 1 1 1 6 2 4 4 3 5 3 5 0 4 0 5 0 6 0 6 8 8 6 6 0 1 0 1 0 1 0 1 Z 0 C D 3 8 4 H Q 6 0 C D 9 0 C D 5 5 1 C D 3 0 6 4 1 1 1 1 4 1 3 2 7 2 7 2 5 1...

Страница 7: ...Manual 2100 435F Page 7 of 40 FIGURE 1 UNIT DIMENSIONS...

Страница 8: ...emoved to provide a place to hold the unit The unit can be slid forward on the skit until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down th...

Страница 9: ...instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure an...

Страница 10: ...Manual 2100 435F Page 10 of 40 FIGURE 6 DUCTEDAPPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...

Страница 11: ...either free blow with the use of QPB Plenum Box or a duct supply air system For hot water coil options a QPBHW F for free blow or QPBHW D for ducted airflow is used The QPB and QPBHW Plenum Box mount...

Страница 12: ...nections on the unit The rear drain is the primary drain and is located on the right lower rear panel of the unit The optional side drain is located on the bottom right side of the unit The side drain...

Страница 13: ...pressure device This indicates that the unit needs to be serviced FIGURE 12 UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL E...

Страница 14: ...to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim up under the rollers with sheets of ste...

Страница 15: ...carry that amount of current Depending on the installed KW of electric heat there may be two field power circuits required If this is the case the unit serial plate will so indicate All models are su...

Страница 16: ...are required 6 if no ventilation system is installed For proper system operation under Emergency Heat conditions where the compressor needs to be deactivated the B W2 E outputs need to be energized Re...

Страница 17: ...P 9 4 0 3 0 4 8 0 8 3 3 9 F 1 t a e H e g a t s 2 l o o C e g a t s 2 c i n o r t c e l E e l b a m m a r g o r P r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0 4 8 1 5 1 1 D 0 2 2 5 H T t a e...

Страница 18: ...2 L C R AUX O B 8 1 2 3 4 5 6 7 E G Y 8403 058 H200 1 E1 R C Plug 4 12 11 10 9 8 7 6 5 4 3 2 1 3 2 Red Black Black Red Red Red Orange Tan Orange Yellow Blue Brown Black Yellow Tan Orange Yellow Red BK...

Страница 19: ...ns to control ventilation must be used if any of the mechanical motorized ventilation options are installed DEHUM CIRCUIT 24 VAC COM DEHUM CIRCUIT COMPRESSOR NOTE FIELD SUPPLIED DEHUMIDISTAT MUST BE D...

Страница 20: ...3 4 5 6 7 8 9 10 11 12 7 6 5 4 3 2 1 Plug 4 8 12 11 10 9 Brown Blue W1 L C R W2 B E1 G A1 Y1 Blue Red Red Tan Orange Yellow Blue Brown Red Black H200 Humidistat IF93 380 Thermostat 4 3 5 6 Yellow Yel...

Страница 21: ...4 3 2 1 3 2 Red Black Black Red Red Red Orange Tan Orange Yellow Blue Brown Black Yellow Tan Orange Yellow Red Purple C Plug 2 Thermostat Relay Logic Board D G W2 A1 W RV G1 E1 L L B Y A2 YO TWV BK E...

Страница 22: ...stat TH5220D1151 1 Terminal O1 Y Y1 Block 1 Black Red Humidistat Black Red Brown Blue Yellow Orange Tan Yellow 4 Red Blue 6 5 3 Blue Black Brown 9 10 11 12 C R AUX O B 8 1 2 3 4 5 6 7 G Red Y Red H200...

Страница 23: ...nitor to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED w...

Страница 24: ...cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease of pulling unit out from the wall you may want to...

Страница 25: ...h the opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed QTEC R ENERGY RECOVERY VENTILATOR Option Before starti...

Страница 26: ...Manual 2100 435F Page 26 of 40 FIGURE 17 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Страница 27: ...Manual 2100 435F Page 27 of 40 FIGURE 18 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 28: ...peration can be restored by turning of the main power supply off and then back on or reset the room thermostat The low pressure control has a bypass to eliminate nuisance lockout on cold start up The...

Страница 29: ...en the humidity is above the setpoint of the humidistat the compressor circuit and the 3 way valve are energized and the evaporator airflow is reduced The 3 way valve directs hot discharge gas into a...

Страница 30: ...Manual 2100 435F Page 30 of 40 FIGURE 20 QTEC DEHUMIDIFICATION MODE CIRCUIT DIAGRAM...

Страница 31: ...Manual 2100 435F Page 31 of 40 FIGURE 21 QTEC COOLING MODE CIRCUIT DIAGRAM...

Страница 32: ...emperature This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region Use a small screwdriver or other metallic object or another 1...

Страница 33: ...d l o r t n o c p m u p t a e h e v i t c e f e D l o r t n o c p m u p t a e h e h t n o 1 L o t C d n a Y o t C m o r f t n e s e r p s i V 4 2 f I t n e s e r p s i V 4 2 o n d n a d e r i p x e r...

Страница 34: ...1 9 9 3 1 8 8 1 7 3 5 8 9 9 6 2 8 1 2 1 0 8 2 3 6 7 7 0 3 2 5 7 0 1 9 2 7 0 7 6 0 7 7 0 5 8 6 8 1 4 6 6 9 9 3 4 6 9 4 4 2 6 5 6 5 0 6 5 4 7 8 5 0 3 1 0 4 1 0 5 1 0 6 1 0 7 1 0 8 1 0 9 1 0 0 2 0 1 2 0...

Страница 35: ...motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop...

Страница 36: ...2 0 CONTROL control in cast aluminum can with air vents on the back of the can WITH AN ECM 2 3 CONTROL control containing black potting for water protection in black deep drawn steel case with no ven...

Страница 37: ...cooling performance will occur with a refrigerant charge resulting in a superheat as shown in Table 8 If correct charge is in doubt recover the refrigerant and recharge per the charge on the unit rati...

Страница 38: ...3 0 8 3 2 3 1 8 1 4 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 9 7 9 1 2 9 7 0 2 2 0 8 9 3 2 1 8 7 5 2 2 8 6 7 2 3 8 4 9 2 4 8 2 1 3 5 8 1 3 3 6 8 0 5 3 B D g e d 5 8 B W g e d 2 7 e...

Страница 39: ...2 2 3 6 3 H Q g e d 0 7 e d i S w o L e d i S h g i H 3 1 7 4 1 7 1 3 5 1 1 2 9 5 1 5 2 4 6 1 7 2 7 6 1 0 3 1 7 1 4 3 6 7 1 8 3 2 8 1 2 4 8 8 1 6 4 4 9 1 2 5 2 0 2 5 5 6 0 2 9 5 1 1 2 3 6 7 1 2 3 2 4...

Страница 40: ...jumper on it to choose between fulltime dehumidification and occupied dehumidification only With the jumper in the 1 2 position dehumidification is available fulltime With the jumper in the 2 3 posit...

Отзывы: