background image

Manual 2100-416J
Page 

23 of 27

MODEL

RATED  

ESP

MAX. ESP

RATED CFM

OPTIONAL CFM

CONTINUOUS 

CFM

CFM @ MAX. 

ESP

QC501

0.0

0.8

1200

1000

1000

1175

  Maximum ESP (" WC) shown is with 1" thick disposable filter (reduced by .2 for 2" filter). 

  Rated CFM for ducted applications – required for maximum performance rating.  To obtain full CFM, locate low  

 

voltage terminal strip in the circuit breaker box.  There is a pink jumper wire with both ends attached to terminal  

 

marked “G2”.  Move one end of the jumper to terminal “Y1”.

  Optional CFM – the unit is shipped from the factory set to operate at the optional CFM level shown.  This provides lower  

 

operating sound levels for non-ducted, free discharge applications .  This reduces system capacity performance by  

 

approximately 2% at the same energy efficiency.

  Continuous fan CFM is the total air being circulated during continuous fan mode.

OPTIONAL CFM 

These units are shipped from the factory set to operate 
at the optional CFM level shown in Table 5.  This 
provides lower operating sound levels for non-ducted, 
free discharge applications.  This CFM level will reduce 
the system capacity performance by approximately 2% 
at the same energy efficiency.

Rated CFM is required for ducted applications for 
maximum performance rating.  To obtain full CFM on 
these models, connect jumper wire as follows:

1.  Disconnect all power to the unit.  Failure to do so 

may result in damage to the motor.

2.  Open hinged return air grille panel.

3.  Open control panel cover.

4.  Add pink jumper wire (provided) to terminals  

5 and 6 on the terminal board.

5.  Reverse steps to reassemble.

IMPORTANT INSTALLER NOTE

For improved start up performance, wash the indoor 
coil with dishwashing detergent.

SERVICE HINTS

1.  Caution user to maintain clean air filters at all 

times and to not close off supply air registers 
needlessly.  This may reduce airflow through the 
system, which shortens equipment service life as 
well as increasing operating costs and noise levels.

2.  The wall thermostat perform multiple functions.  

Be sure that all function switches are correctly set 
for the desired operating mode before trying to 
diagnose any reported service problems.

SEQUENCE OF OPERATION

FIRST STAGE COOLING

 – Circuit R-Y1 makes the 

thermostat open the first stage cooling water valve.  

SECOND STAGE COOLING 

– Circuit R-Y2 makes the 

thermostat open the second stage cooling water valve.  
The G (indoor motor) circuit is automatically completed 
on any call for cooling operation, or can be energized 
by manual fan switch on subbase for constant air 
circulation.

CAUTION:

  Second stage cooling must always be    

 

energized in conjunction with first stage.   

 

If the second state were energized alone,  

 

the condensate from the upper part of the 

 

coil could be blown off or re-evaporated as  

 

it passes down over the dry portion of the  

 coil.

HEATING

 –  A thermostat demand for heating makes 

R-W1 circuit as well as R-G circuit.  This starts the 
indoor blower as well as turns on the electric heater.

SECOND STAGE HEATING

 (15 KW only) – Circuit 

R-W2 energizes the second contactor and brings on the 
last 5 KW of heat.

START UP

TABLE 5

Indoor Blower Performance

NOTE:  These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to 

maintain approximately the same rate of indoor air flow in both heating and cooling, dry and wet coil 

conditions, and at both 230/208 or 460 volts.

Содержание QC501

Страница 1: ...Page 1 of 27 INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual No 2100 416J Supersedes 2100 416I Date 6 14 16 QC SERIES CHILLED WATER UNIT Model QC501...

Страница 2: ...Top View 12 Figure 10 Fresh Air Damper Removal 14 Figure 11 Removal of QTec ERV 15 Figure 12 Remove Locking Screws from Wheels 16 Figure 13 Unit Mounting Without Wall Sleeve 17 Figure 14 Component Loc...

Страница 3: ...Procedures for Ground Source IGSHPA Heat Pump Systems Soil and Rock Classification for the Design IGSHPA of Ground Coupled Heat Pump Systems Ground Source Installation Standards IGSHPA Closed Loop Geo...

Страница 4: ...l codes These Minimum Circuit Ampacity values are to be used for sizing the field power conductors Refer to the National Electric Code latest revision article 310 for power conductor sizing CAUTION Wh...

Страница 5: ...3 3 7 5 10 14 7 10 6 4 1 36 9 24 6 12 3 4 9 11 3 6 48 1000 11 6 9 1 2 5 30 3 21 9 8 4 1 9 4 4 8 12 6 9 6 3 0 32 2 22 6 9 6 3 3 7 5 10 46 6 10 0 3 3 33 7 23 2 10 5 4 9 11 3 6 42 1200 15 9 11 5 4 4 42...

Страница 6: ...Manual 2100 416J Page 6 of 27 FIGURE 1 Unit Dimensions...

Страница 7: ...NT WHEELS ON FLOOR The unit will have to be turned sideways and removed from the skid to fit through a 36 doorway If the door height allows the unit can be slid sideways through the door If the unit c...

Страница 8: ...and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdi...

Страница 9: ...Manual 2100 416J Page 9 of 27 FIGURE 4 Installation of Unit through Wall with Wall Sleeve...

Страница 10: ...Manual 2100 416J Page 10 of 27 FIGURE 6 Ducted Application FIGURE 5 Installation with Free Blow Plenum CEILING FLOOR FLOOR...

Страница 11: ...low with the use of QPB Plenum Box or a duct supply air system The QPB Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille FI...

Страница 12: ...llations the drain tube is to be slipped over the pipe connection inside of the cabinet FIGURE 9B Optional Rear Drain See Figures 9A 9B and 9C NOTE Whichever type of drain connection is used a P trap...

Страница 13: ...bottom can be pulled toward the front of the unit and removed The rear drain can be used where there is a distance of 4 1 2 available between the unit and wall to install a trap see Figure 9B The tra...

Страница 14: ...Manual 2100 416J Page 14 of 27 FIGURE 10 Fresh Air Damper Removal MOUNTING SCREW...

Страница 15: ...covery Ventilator 3 Underneath the heat recovery cassette there is a power connector for the lower blower assembly To disconnect this plug the tabs on both sides of the plug must be squeezed to releas...

Страница 16: ...nfines of this bracket See Figure 1 for cabinet openings and location of fluid coil connection points 2 Position the unit in front of the wall mounting bracket 3 Remove the locking screws from the whe...

Страница 17: ...6J Page 17 of 27 FIGURE 13 Unit Mounting without Ventilation Wall Sleeve Refer to Mounting Instructions on page 16 SIDE TRIM 2 PIECES SIDE TRIM 2 PIECES WALL MOUNTING BRACKET BOTTOM TRIM EXTENSION BOT...

Страница 18: ...there may be two field power circuits required If this is the case the unit serial plate will so indicate All models are suitable only for connection with copper wire Each unit and or wiring diagram w...

Страница 19: ...he front panel of the unit Compatible for use with energy recovery ventilator or economizer GENERAL This unit is equipped with a variable speed ECM motor The motor is designed to maintain rated airflo...

Страница 20: ...l or pin 7 of P2 is the first stage cooling input W1 terminal or pin 8 of P2 is the first stage heating input R terminal or pin 10 of P2 is 24 VAC hot C terminal or pin 11 of P2 is 24 VAC grounded Y2...

Страница 21: ...Manual 2100 416J Page 21 of 27 FIGURE 16 Remote Thermostat Wiring Diagram X Option...

Страница 22: ...Manual 2100 416J Page 22 of 27 FIGURE 17 Remote Thermostat Wiring Diagram D Thermostat Option...

Страница 23: ...PORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with dishwashing detergent SERVICE HINTS 1 Caution user to maintain clean air filters at all times and to not close off su...

Страница 24: ...ne if it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down...

Страница 25: ...rer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted into the socket in the...

Страница 26: ...Manual 2100 416J Page 26 of 27 FIGURE 21 Internal 2 Way Valve Piping NO side of valve NC side of valve COM side of valve Valve Detail MIS 1899 A Valve Location Water Valves WATER OUT WATER IN...

Страница 27: ...Manual 2100 416J Page 27 of 27 FIGURE 22 Internal 3 Way Valve Piping NC side of valve COM side of valve NO side of valve Valve Detail MIS 1900 A Valve Location WATER OUT Water Valves WATER IN...

Отзывы: