Manual 2100-416J
Page
12 of 27
CONDENSATE DRAIN
The condensate drain hose is routed down from the
evaporator drain pan on the right side of the unit
into the compressor compartment. There are three
locations that the drain can exit the cabinet. For a
stand pipe type of drain, the drain hose can exit the
rear of the cabinet. There is adequate hose length to
reach the floor on the right hand side of the unit.
If the drain is to be hard plumbed, there is a 3/4" pipe
connection located on the right hand cabinet side near
the rear and one on the cabinet rear panel. In these
installations the drain tube is to be slipped over the
pipe connection inside of the cabinet.
FIGURE 9B
Optional Rear Drain
See Figures 9A, 9B and 9C.
NOTE:
Whichever type of drain connection is used a
“P” trap must be formed.
The
side drain
requires a water trap for proper drainage
(see Figure 9A). The drain can be routed through the floor
or through the wall.
If the drain is to be routed through an
unconditioned space, it must be protected from freezing.
The drain line must be able to be removed from the unit
if it is necessary to remove the unit from the wall.
FIGURE 9A
Side Drain (Side View)
FIGURE 9C
Rear Drain (Top View)
SLEEVE
WALL BRACKET
WALL
(MAXIMUM
10" FOR REAR
DRAIN)
DRAIN LINE
COUPLINGS NOT
SHOWN BUT
RECOMMENDED
FOR EASE OF
REMOVABILITY FOR
SERVICE
WATER
TRAP
UNIT
Q-TEC UNIT
Содержание QC501
Страница 6: ...Manual 2100 416J Page 6 of 27 FIGURE 1 Unit Dimensions...
Страница 9: ...Manual 2100 416J Page 9 of 27 FIGURE 4 Installation of Unit through Wall with Wall Sleeve...
Страница 14: ...Manual 2100 416J Page 14 of 27 FIGURE 10 Fresh Air Damper Removal MOUNTING SCREW...
Страница 21: ...Manual 2100 416J Page 21 of 27 FIGURE 16 Remote Thermostat Wiring Diagram X Option...
Страница 22: ...Manual 2100 416J Page 22 of 27 FIGURE 17 Remote Thermostat Wiring Diagram D Thermostat Option...