Bard QA241D Скачать руководство пользователя страница 24

Manual     2100-438
Page     22

6. Some service requires the need to remove the unit

from the wall including replacement of the indoor

coil and/or the outdoor coil.  Also servicing the

outdoor fan motor or fan blade will require

removing the unit from the wall if the unit is

installed at a height that is not easily accessible

from the outside of the building.
In order to remove the unit from the wall the

following procedure must be used:

a. Turn off power to the unit at the remote

location.  Some units may have more than one
power supply.

b. Disconnect field wiring at unit terminal block

and remove from unit.

c. Disconnect condensate drain.

d. Remove the lower skirting around the unit.

e. Remove wall mounting brackets from wall on

each side of the unit.

f. If unit is attached to duct work, remove upper

cabinet extension by removing the top center
screw only from the cabinet side panel.

g. Remove screws that attach the duct work to

the unit flanges.
This unit is equipped with four rollers
mounted to the base.  For ease of pulling unit
out from the wall, you may want to remove
the bottom service door which requires
removal of the return air panel, and grip the
front flange of the base pan then pull straight
out.

7. Annual maintenance is required to make sure that

all of the systems are functioning properly.

a. Check to make sure that the drains are not

obstructed in any way.

b. Remove any debris in the condenser section of

the unit.

c. Inspect and clean mist eliminator as described

below.

d. Inspect and wash outdoor coil as necessary.

MIST ELIMINATOR SERVICE

A mist eliminator is supplied with the wall sleeve.  The
mist eliminator is constructed of an aluminum frame
and mesh.  The mist eliminator is located in the top
section of the wall sleeve and can be removed from the
inside of the building without removing the unit from
the wall.  This requires that the ventilation package must
be removed.

It is recommended that the mist eliminator be inspected
annually and serviced as required.  The mist eliminator
can be inspected from the outside of the building by
looking through the outdoor grille.  The mist eliminator
can be serviced from the outside by using a vacuum
cleaner.  The outdoor grille must be removed.  Use the
vacuum to remove dirt and debris from the surface of
the mist eliminator.  If additional cleaning is required,
the mist eliminator will have to be removed from the
sleeve.

The ventilation package will have to be removed to gain
access to the mist eliminator.  If the blank off plate
option is used, it is not necessary to service the mist
eliminator.  The steps necessary to remove each of the
vent options are listed on the following pages.

The mist eliminator can be cleaned by washing with
soap and water.  The excess water should be shaken off
the mist eliminator before it is reinstalled.

VENT OPTIONS

BAROMETRIC FRESH AIR DAMPER  (Standard)

Before starting, make sure the power has been turned
off.  The return air grille panel must be removed.  The
fresh air damper assembly can be seen on the back of
the unit.  See Figure 19.

1. The fresh air damper is attached to the back of the

unit with one screw on either side of the
assembly.  Both of the screws must be removed.

2. Once the mounting screws are removed, tilt the

assembly down and lift it out.

The mist eliminator can be seen through the opening.
The mist eliminator must be raised up and the bottom
can be pulled toward the front of the unit.

COMMERCIAL ROOM VENTILATOR  (Option)

Before starting, make sure the power has been turned
off.  The return air grille panel must be removed.  The
commercial room ventilator (CRV) can be seen after the
panel has been removed.  The CRV must be removed to
gain access to the mist eliminator.

1. The two mounting screws in the front of the

CRV must be removed.

2. The power connectors for the CRV (located on

the right side of the unit) must be disconnected.
Squeeze the tabs on the sides of the connector
and pull straight out.  Unplug both of the
connectors.

3. Slide the CRV straight out of the unit.

Содержание QA241D

Страница 1: ...ince 1914 Moving ahead just as planned Manual 2100 438C Supersedes 2100 438B File Vol II Tab 14 Date 06 02 04 Copyright 2004 Models QA241D QA301D QA361D QA421D QA481D QA601D QTEC SERIES PACKAGED AIR C...

Страница 2: ...mostats and Subbase Combinations 16 Table 5 Troubleshooting 29 Table 6 Fan Blade Dimensions 30 Table 7 Super Heat at Compressor 30 Table 8 Indoor Blower Performance 30 Table 9 Cooling Pressure 31 Gett...

Страница 3: ...Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...2 Ton 30 2 1 2 Ton 36 3 Ton 42 3 1 2 Ton 48 4 Ton 60 5 Ton KW 0Z 0KW 05 5KW 06 6KW 09 9KW 10 10KW 12 12KW 15 15KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate V Commer...

Страница 5: ...0 4 2 1 V 8 0 2 1 V 0 4 2 1 V 8 0 2 3 V 0 8 4 W K H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B 0 5 0...

Страница 6: ...I N I M T I U C R I C Y T I C A P M A 1 M U M I X A M L A N R E T X E R O E S U F T I U C R I C R E K A E R B 2 D L E I F R E W O P E Z I S E R I W 2 D N U O R G E Z I S E R I W T K C A T K C B T K C...

Страница 7: ...E R O E S U F T I U C R I C R E K A E R B 2 D L E I F R E W O P E Z I S E R I W 2 D N U O R G E Z I S E R I W T K C A T K C B T K C A T K C B T K C A T K C B T K C A T K C B Z 0 A D 1 2 4 A Q 5 0 A D...

Страница 8: ...Manual 2100 438 Page 6 FIGURE 1 UNIT DIMENSIONS...

Страница 9: ...arded See Figure 3 A The return air grille panel can be removed to provide a place to hold the unit The unit can be slid forward on the skit until the front wheels hang over the edge of the skid See F...

Страница 10: ...ral recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 1 for information on...

Страница 11: ...CEILING FIXED CEILING DUCT DUCT FLANGE 8 FT 7 IN MINIMUM RECOMMENDED CEILING HEIGHT 7 FT 4 IN UNIT HEIGHT 12 IN MINIMUM 2 IN MINIMUM FROM DUCT FLANGE TO DUCT BOTTOM 8 FT 4 5 IN MINIMUM REQUIRED INSTA...

Страница 12: ...asteners and one locking latch The internal filter brackets are adjustable to accommodate 2 inch filters The tabs for the 1 inch filters must be bent down to allow the 2 inch filters to slide in place...

Страница 13: ...d with a plug installed The side drain requires a water trap for proper drainage See Figure 9 The drain can be routed through the floor or through the wall If the drain is to be routed through an unco...

Страница 14: ...e device This indicates that the unit needs to be serviced FIGURE 12 UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS MIS 1576 CABINET SIDE PANEL...

Страница 15: ...it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim up under the rollers with sheets of steel or an...

Страница 16: ...All models are suitable only for connection with copper wire Each unit and or wiring diagram will be marked Use Copper Conductors Only These instructions MUST BE adhered to Refer to the National Elect...

Страница 17: ...terminal is the hot terminal and the C terminal is grounded G terminal or pin 6 of P2 are the fan inputs If the climate control option is abandoned and connections are made directly to P2 pin 6 of P2...

Страница 18: ...RE 15 TABLE 4 WALL THERMOSTATS AND SUBBASE COMBINATIONS t a t s o m r e h T e s a b b u S s e r u t a e F t n a n i m o d e r P 9 4 0 3 0 4 8 0 8 3 3 9 F 1 A N l o o C t a e H o t u A l a u n a M e l...

Страница 19: ...7 FIGURE 16 REMOTE THERMOSTAT WIRING DIAGRAM X THERMOSTAT OPTION NOTE On option X or G the CS2000 or other field provided means to control ventilation must be used if any of the motorized ventilation...

Страница 20: ...IGURE 17 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM G THERMOSTAT OPTION NOTE On option X or G the CS2000 or other field provided means to control ventilation must be used if any of the motorized ventilati...

Страница 21: ...Manual 2100 438 Page 19 FIGURE 18 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM E THERMOSTAT OPTION...

Страница 22: ...lugging in the motor could result in motor failure PHASE MONITOR All units with three phase scroll compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase revers...

Страница 23: ...out Regardless the state of the low pressure switch the contactor will reenergize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer than...

Страница 24: ...It is recommended that the mist eliminator be inspected annually and serviced as required The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille Th...

Страница 25: ...unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed The mist eliminator can be seen through the opening in the back of the unit The mist el...

Страница 26: ...Manual 2100 438 Page 24 FIGURE 19 FRESH AIR DAMPER REMOVAL MIS 1627 MOUNTING SCREW...

Страница 27: ...Manual 2100 438 Page 25 FIGURE 20 QERV REMOVAL MIS 1039 MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 28: ...rmostat pull in the compressor contactor starting the compressor and outdoor motor The G indoor motor circuit is automatically completed on any call for cooling operation or can be energized by manual...

Страница 29: ...Manual 2100 438 Page 27 FIGURE 21 AIR CONDITIONING MODE CIRCUIT DIAGRAM MIS 1200...

Страница 30: ...Manual 2100 438 Page 28 FIGURE 22 DEHUMIDIFICATIONMODE CIRCUIT DIAGRAM MIS 1199...

Страница 31: ...g i h e c a l p e r t e s e r t o n l l i w d n a h c t i w s e r u s s e r p t r o h s r o s s e r p m o C n o i t c e t o r p e l c y c C C C n e e w t e b V 4 2 r o f k c e h C l o r t n o c p m u...

Страница 32: ...n a Super Heat as shown in Table 7 If correct charge is in doubt recover the refrigerant and recharge per the charge on the unit rating plate FIGURE 23 FAN BLADE SETTING MIS 983 TABLE 6 FAN BLADE DIME...

Страница 33: ...1 2 4 7 5 1 2 5 7 3 3 2 6 7 1 5 2 7 7 9 6 2 8 7 7 8 2 9 7 5 0 3 0 8 3 2 3 1 8 1 4 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 9 7 9 1 2 9 7 0 2 2 0 8 9 3 2 1 8 7 5 2 2 8 6 7 2 3 8 4 9 2 4 8 2 1 3...

Отзывы: