HANDLING UNIT AFTER REMOVAL
FROM SKID

The unit will have to be turned sideways and removed
from the skid to fit through a 36” doorway.  If the door
height allows, the unit can be slid sideways through the
door.

If the unit can not be slid through the door, then the unit
will have to be put on a cart and tipped down to roll
through the door.  It is recommended that an appliance
cart by used with a strap to hold the unit on the cart.

MINIMUM INSTALLATION HEIGHT

The minimum installation height of the unit with a Free
Blow Plenum is 8 ft. 6 in.   This provides enough
clearance for the plenum to be removed.  See Figure 5.

The minimum installation height for ducted applications
is 8 ft. 4-1/2 in.   This provides enough clearance to
install the duct work.  See Figure 6.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The unit is designed for use with or without duct work.
For use without duct work, Plenum Box QPB42 is
recommended.

These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.

These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation.  Note particularly “Start
Procedure” and any tags and/or labels attached to the
equipment.

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way.  Authorities having
jurisdiction should be consulted before the installation
is made.  See Page 1 for information on codes and
standards.

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA).
The air duct should be installed in accordance with the
Standards of the National Fire Protection Systems of
Other Than Residence Type, NFPA No. 90A, and
Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B.  Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

The wheels of the unit 

must be locked

.  If the wheels

were allowed to roll, the unit could roll off the cart.  

The

unit should always be carted from the left side

.  This is

the side where the compressor is located.  See Figure 4.
The blade of the appliance cart should be slid under the
wheels of the unit.  The strap of the appliance cart
should be placed around the unit and strapped tightly.
Help will be required to tip the unit back onto the cart.
The unit can be leaned far enough back to be rolled
through the door.  Be careful when setting the unit back
up to keep from damaging the unit.

FIGURE  4

UNIT ON APPLIANCE CART

        WARNING

Exercise extreme caution when pushing the
unit on the rollers.  Handle and push from the
lower 1/3 of the unit.  Insure that debris is not
on the floor where the unit is to be moved on
the rollers.  Failure to do so could result in the
unit tipping over and causing bodily injury and/
or damage to the unit.

QT

EC

 UNIT

(Right Side)

APPLIANCE

CART

COMPRESSOR

MIS-1555

STRAP

Содержание QA241D

Страница 1: ...ince 1914 Moving ahead just as planned Manual 2100 438C Supersedes 2100 438B File Vol II Tab 14 Date 06 02 04 Copyright 2004 Models QA241D QA301D QA361D QA421D QA481D QA601D QTEC SERIES PACKAGED AIR C...

Страница 2: ...mostats and Subbase Combinations 16 Table 5 Troubleshooting 29 Table 6 Fan Blade Dimensions 30 Table 7 Super Heat at Compressor 30 Table 8 Indoor Blower Performance 30 Table 9 Cooling Pressure 31 Gett...

Страница 3: ...Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...2 Ton 30 2 1 2 Ton 36 3 Ton 42 3 1 2 Ton 48 4 Ton 60 5 Ton KW 0Z 0KW 05 5KW 06 6KW 09 9KW 10 10KW 12 12KW 15 15KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate V Commer...

Страница 5: ...0 4 2 1 V 8 0 2 1 V 0 4 2 1 V 8 0 2 3 V 0 8 4 W K H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B 0 5 0...

Страница 6: ...I N I M T I U C R I C Y T I C A P M A 1 M U M I X A M L A N R E T X E R O E S U F T I U C R I C R E K A E R B 2 D L E I F R E W O P E Z I S E R I W 2 D N U O R G E Z I S E R I W T K C A T K C B T K C...

Страница 7: ...E R O E S U F T I U C R I C R E K A E R B 2 D L E I F R E W O P E Z I S E R I W 2 D N U O R G E Z I S E R I W T K C A T K C B T K C A T K C B T K C A T K C B T K C A T K C B Z 0 A D 1 2 4 A Q 5 0 A D...

Страница 8: ...Manual 2100 438 Page 6 FIGURE 1 UNIT DIMENSIONS...

Страница 9: ...arded See Figure 3 A The return air grille panel can be removed to provide a place to hold the unit The unit can be slid forward on the skit until the front wheels hang over the edge of the skid See F...

Страница 10: ...ral recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 1 for information on...

Страница 11: ...CEILING FIXED CEILING DUCT DUCT FLANGE 8 FT 7 IN MINIMUM RECOMMENDED CEILING HEIGHT 7 FT 4 IN UNIT HEIGHT 12 IN MINIMUM 2 IN MINIMUM FROM DUCT FLANGE TO DUCT BOTTOM 8 FT 4 5 IN MINIMUM REQUIRED INSTA...

Страница 12: ...asteners and one locking latch The internal filter brackets are adjustable to accommodate 2 inch filters The tabs for the 1 inch filters must be bent down to allow the 2 inch filters to slide in place...

Страница 13: ...d with a plug installed The side drain requires a water trap for proper drainage See Figure 9 The drain can be routed through the floor or through the wall If the drain is to be routed through an unco...

Страница 14: ...e device This indicates that the unit needs to be serviced FIGURE 12 UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS MIS 1576 CABINET SIDE PANEL...

Страница 15: ...it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim up under the rollers with sheets of steel or an...

Страница 16: ...All models are suitable only for connection with copper wire Each unit and or wiring diagram will be marked Use Copper Conductors Only These instructions MUST BE adhered to Refer to the National Elect...

Страница 17: ...terminal is the hot terminal and the C terminal is grounded G terminal or pin 6 of P2 are the fan inputs If the climate control option is abandoned and connections are made directly to P2 pin 6 of P2...

Страница 18: ...RE 15 TABLE 4 WALL THERMOSTATS AND SUBBASE COMBINATIONS t a t s o m r e h T e s a b b u S s e r u t a e F t n a n i m o d e r P 9 4 0 3 0 4 8 0 8 3 3 9 F 1 A N l o o C t a e H o t u A l a u n a M e l...

Страница 19: ...7 FIGURE 16 REMOTE THERMOSTAT WIRING DIAGRAM X THERMOSTAT OPTION NOTE On option X or G the CS2000 or other field provided means to control ventilation must be used if any of the motorized ventilation...

Страница 20: ...IGURE 17 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM G THERMOSTAT OPTION NOTE On option X or G the CS2000 or other field provided means to control ventilation must be used if any of the motorized ventilati...

Страница 21: ...Manual 2100 438 Page 19 FIGURE 18 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM E THERMOSTAT OPTION...

Страница 22: ...lugging in the motor could result in motor failure PHASE MONITOR All units with three phase scroll compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase revers...

Страница 23: ...out Regardless the state of the low pressure switch the contactor will reenergize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer than...

Страница 24: ...It is recommended that the mist eliminator be inspected annually and serviced as required The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille Th...

Страница 25: ...unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed The mist eliminator can be seen through the opening in the back of the unit The mist el...

Страница 26: ...Manual 2100 438 Page 24 FIGURE 19 FRESH AIR DAMPER REMOVAL MIS 1627 MOUNTING SCREW...

Страница 27: ...Manual 2100 438 Page 25 FIGURE 20 QERV REMOVAL MIS 1039 MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 28: ...rmostat pull in the compressor contactor starting the compressor and outdoor motor The G indoor motor circuit is automatically completed on any call for cooling operation or can be energized by manual...

Страница 29: ...Manual 2100 438 Page 27 FIGURE 21 AIR CONDITIONING MODE CIRCUIT DIAGRAM MIS 1200...

Страница 30: ...Manual 2100 438 Page 28 FIGURE 22 DEHUMIDIFICATIONMODE CIRCUIT DIAGRAM MIS 1199...

Страница 31: ...g i h e c a l p e r t e s e r t o n l l i w d n a h c t i w s e r u s s e r p t r o h s r o s s e r p m o C n o i t c e t o r p e l c y c C C C n e e w t e b V 4 2 r o f k c e h C l o r t n o c p m u...

Страница 32: ...n a Super Heat as shown in Table 7 If correct charge is in doubt recover the refrigerant and recharge per the charge on the unit rating plate FIGURE 23 FAN BLADE SETTING MIS 983 TABLE 6 FAN BLADE DIME...

Страница 33: ...1 2 4 7 5 1 2 5 7 3 3 2 6 7 1 5 2 7 7 9 6 2 8 7 7 8 2 9 7 5 0 3 0 8 3 2 3 1 8 1 4 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 9 7 9 1 2 9 7 0 2 2 0 8 9 3 2 1 8 7 5 2 2 8 6 7 2 3 8 4 9 2 4 8 2 1 3...

Отзывы: