Manual     2100-438
Page     20

START UP

DESCRIPTION OF STANDARD

EQUIPMENT

High Pressure Switch

Provides refrigerant circuit high pressure protection.

Includes lockout circuit that is resettable from room

thermostat.

Compressor Control Module

Provides short cycle protection for the compressor

which extends compressor life.  High and low pressure

switch monitoring and alarm functions.

Service Lights

One service light indicates when service is required.

• Check System – detects high or low pressure

switch operation for compressor protection.

OPTIONAL CFM (QA361, QA421, QA481

AND QA601 ONLY)

These units are shipped from the factory set to operate at

the optional CFM level shown in Table 8.  This provides

lower operating sound levels for non-ducted, free

discharge applications.  This CFM level will reduce the

system capacity performance by approximately 2% at

the same energy efficiency.

Rated CFM is required for ducted applications for

maximum performance rating.  To obtain full CFM on

these models, connect jumper wire as follows:

1. Disconnect all power to the unit.  Failure to do so

may result in damage to the motor.

2. Open return air service panel

3. Open inner control panel cover

4. Locate low voltage terminal strip.  There is a pink

jumper wire with both ends attached to terminal

marked “G2”.  Move one end of this jumper to

terminal “Y”.

5. Reverse steps to reassemble.

IMPORTANT INSTALLER NOTE

For improved start-up performance, wash the indoor coil

with a dishwasher detergent.

This unit is equipped with a variable speed ECM motor.

The motor is designed to maintain rated airflow up to

the maximum Static allowed.  

It is important that the

blower motor plugs are not plugged in or unplugged

while the power is on.  Failure to remove power prior

to unplugging or plugging in the motor could result in
motor failure.

PHASE MONITOR

All units with three phase scroll compressors are

equipped with a 3 phase line monitor to prevent

compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two

LEDs.  If the Y signal is present at the phase monitor

and phases are correct the green LED will light and the

compressor contactor is allowed to energize.

If phases are reversed, the red fault LED will be lit and

compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply

leads to the unit.  Do not reverse any of the unit factory

wires as damage may occur.

THREE PHASE SCROLL COMPRESSOR

START UP INFORMATION

Scroll compressors, like several other types of

compressors, will only compress in one rotational

direction.  Direction of rotation is not an issue with

single phase compressors since they will always start

and run in the proper direction.

However, three phase compressors will rotate in either

direction depending upon phasing of the power.  Since

there is a 50-50 chance of connecting power in such a

way as to cause rotation in the reverse direction,

verification of proper rotation must be made.

Verification of proper rotation direction is made by

observing that suction pressure drops and discharge

pressure rises when the compressor is energized.

Reverse rotation also results in an elevated sound level

over that with correct rotation, as well as, substantially

reduced current draw compared to tabulated values.

Verification of proper rotation must be made at the

time the equipment is put into service.  If improper

rotation is corrected at this time there will be no

negative impact on the durability of the compressor.

However, reverse operation for oven one hour may

have a negative impact on the bearing due to oil pump

out.

          CAUTION

Do not plug in or unplug blower motor
connectors while the power is on.  Failure to
do so may result in motor failure.

Содержание QA241D

Страница 1: ...ince 1914 Moving ahead just as planned Manual 2100 438C Supersedes 2100 438B File Vol II Tab 14 Date 06 02 04 Copyright 2004 Models QA241D QA301D QA361D QA421D QA481D QA601D QTEC SERIES PACKAGED AIR C...

Страница 2: ...mostats and Subbase Combinations 16 Table 5 Troubleshooting 29 Table 6 Fan Blade Dimensions 30 Table 7 Super Heat at Compressor 30 Table 8 Indoor Blower Performance 30 Table 9 Cooling Pressure 31 Gett...

Страница 3: ...Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...2 Ton 30 2 1 2 Ton 36 3 Ton 42 3 1 2 Ton 48 4 Ton 60 5 Ton KW 0Z 0KW 05 5KW 06 6KW 09 9KW 10 10KW 12 12KW 15 15KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate V Commer...

Страница 5: ...0 4 2 1 V 8 0 2 1 V 0 4 2 1 V 8 0 2 3 V 0 8 4 W K H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B 0 5 0...

Страница 6: ...I N I M T I U C R I C Y T I C A P M A 1 M U M I X A M L A N R E T X E R O E S U F T I U C R I C R E K A E R B 2 D L E I F R E W O P E Z I S E R I W 2 D N U O R G E Z I S E R I W T K C A T K C B T K C...

Страница 7: ...E R O E S U F T I U C R I C R E K A E R B 2 D L E I F R E W O P E Z I S E R I W 2 D N U O R G E Z I S E R I W T K C A T K C B T K C A T K C B T K C A T K C B T K C A T K C B Z 0 A D 1 2 4 A Q 5 0 A D...

Страница 8: ...Manual 2100 438 Page 6 FIGURE 1 UNIT DIMENSIONS...

Страница 9: ...arded See Figure 3 A The return air grille panel can be removed to provide a place to hold the unit The unit can be slid forward on the skit until the front wheels hang over the edge of the skid See F...

Страница 10: ...ral recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 1 for information on...

Страница 11: ...CEILING FIXED CEILING DUCT DUCT FLANGE 8 FT 7 IN MINIMUM RECOMMENDED CEILING HEIGHT 7 FT 4 IN UNIT HEIGHT 12 IN MINIMUM 2 IN MINIMUM FROM DUCT FLANGE TO DUCT BOTTOM 8 FT 4 5 IN MINIMUM REQUIRED INSTA...

Страница 12: ...asteners and one locking latch The internal filter brackets are adjustable to accommodate 2 inch filters The tabs for the 1 inch filters must be bent down to allow the 2 inch filters to slide in place...

Страница 13: ...d with a plug installed The side drain requires a water trap for proper drainage See Figure 9 The drain can be routed through the floor or through the wall If the drain is to be routed through an unco...

Страница 14: ...e device This indicates that the unit needs to be serviced FIGURE 12 UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS MIS 1576 CABINET SIDE PANEL...

Страница 15: ...it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim up under the rollers with sheets of steel or an...

Страница 16: ...All models are suitable only for connection with copper wire Each unit and or wiring diagram will be marked Use Copper Conductors Only These instructions MUST BE adhered to Refer to the National Elect...

Страница 17: ...terminal is the hot terminal and the C terminal is grounded G terminal or pin 6 of P2 are the fan inputs If the climate control option is abandoned and connections are made directly to P2 pin 6 of P2...

Страница 18: ...RE 15 TABLE 4 WALL THERMOSTATS AND SUBBASE COMBINATIONS t a t s o m r e h T e s a b b u S s e r u t a e F t n a n i m o d e r P 9 4 0 3 0 4 8 0 8 3 3 9 F 1 A N l o o C t a e H o t u A l a u n a M e l...

Страница 19: ...7 FIGURE 16 REMOTE THERMOSTAT WIRING DIAGRAM X THERMOSTAT OPTION NOTE On option X or G the CS2000 or other field provided means to control ventilation must be used if any of the motorized ventilation...

Страница 20: ...IGURE 17 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM G THERMOSTAT OPTION NOTE On option X or G the CS2000 or other field provided means to control ventilation must be used if any of the motorized ventilati...

Страница 21: ...Manual 2100 438 Page 19 FIGURE 18 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM E THERMOSTAT OPTION...

Страница 22: ...lugging in the motor could result in motor failure PHASE MONITOR All units with three phase scroll compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase revers...

Страница 23: ...out Regardless the state of the low pressure switch the contactor will reenergize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer than...

Страница 24: ...It is recommended that the mist eliminator be inspected annually and serviced as required The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille Th...

Страница 25: ...unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed The mist eliminator can be seen through the opening in the back of the unit The mist el...

Страница 26: ...Manual 2100 438 Page 24 FIGURE 19 FRESH AIR DAMPER REMOVAL MIS 1627 MOUNTING SCREW...

Страница 27: ...Manual 2100 438 Page 25 FIGURE 20 QERV REMOVAL MIS 1039 MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 28: ...rmostat pull in the compressor contactor starting the compressor and outdoor motor The G indoor motor circuit is automatically completed on any call for cooling operation or can be energized by manual...

Страница 29: ...Manual 2100 438 Page 27 FIGURE 21 AIR CONDITIONING MODE CIRCUIT DIAGRAM MIS 1200...

Страница 30: ...Manual 2100 438 Page 28 FIGURE 22 DEHUMIDIFICATIONMODE CIRCUIT DIAGRAM MIS 1199...

Страница 31: ...g i h e c a l p e r t e s e r t o n l l i w d n a h c t i w s e r u s s e r p t r o h s r o s s e r p m o C n o i t c e t o r p e l c y c C C C n e e w t e b V 4 2 r o f k c e h C l o r t n o c p m u...

Страница 32: ...n a Super Heat as shown in Table 7 If correct charge is in doubt recover the refrigerant and recharge per the charge on the unit rating plate FIGURE 23 FAN BLADE SETTING MIS 983 TABLE 6 FAN BLADE DIME...

Страница 33: ...1 2 4 7 5 1 2 5 7 3 3 2 6 7 1 5 2 7 7 9 6 2 8 7 7 8 2 9 7 5 0 3 0 8 3 2 3 1 8 1 4 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 9 7 9 1 2 9 7 0 2 2 0 8 9 3 2 1 8 7 5 2 2 8 6 7 2 3 8 4 9 2 4 8 2 1 3...

Отзывы: