Manual 2100-601
Page
5 of 42
MODEL
Rated
Volts &
Phase
No.
Field
Power
Circuits
Single Circuit
Dual Circuit
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Ckt. Brkr.
Field
Power
Wire
Size
Ground
Wire
Minimum
Circuit
Ampacity
Maximum
External Fuse
or Ckt. Breaker
Field Power
Wire Size
Ground
Wire Size
Ckt. A Ckt. B
Ckt. A Ckt. B
Ckt. A Ckt. B
Ckt. A Ckt. B
Q24H2-A0Z
A05
A10
230/208-1
1
1
1 or 2
22
47
72
30
50
80
10
8
4
10
10
8
22
50
30
50
10
8
10
10
Q24H2-B0Z
B06
B09
230/208-3
1
1
1
17
35
44
20
35
45
12
8
8
12
10
10
Q24H2-C0Z
C06
C09
460-3
1
1
1
10
19
23
15
20
25
14
12
10
14
12
10
Q30H2-A0Z
A05
A10
230/208-1
1
1
1 or 2
25
50
75
35
50
80
8
8
4
10
10
8
25
50
30
50
10
8
10
10
Q30H2-B0Z
B06
B09
B12
230/208-3
1
1
1
1
18
37
45
55
25
40
45
60
10
8
8
6
10
10
10
10
Q30H2-C0Z
C06
C09
C12
460-3
1
1
1
1
12
21
25
30
15
25
25
30
14
10
10
10
14
10
10
10
Q36H2-A0Z
A05
A10
A15
230/208-1
1
1
1 or 2
1 or 2
31
56
81
83
45
60
90
90
8
6
4
4
10
10
8
8
31
33
50
50
45
45
50
50
8
8
8
8
10
10
10
10
Q36H2-B0Z
B06
B09
B15
230/208-3
1
1
1
1
25
43
52
53
30
50
60
60
10
8
6
6
10
10
10
10
Q36H2-C0Z
C06
C09
C15
460-3
1
1
1
1
12
21
26
27
15
25
30
30
14
10
10
10
14
10
10
10
Q42H2-A0Z
A05
A10
A15
230/208-1
1
1
1 or 2
1 or 2
34
59
84
84
50
60
90
90
8
6
4
4
10
10
8
8
34
34
50
50
45
45
50
50
8
8
8
8
10
10
10
10
Q42H2-B0Z
B06
B09
B15
230/208-3
1
1
1
1
25
43
52
53
35
50
60
60
8
8
6
6
10
10
10
10
Q42H2-C0Z
C06
C09
C15
460-3
1
1
1
1
13
22
26
27
15
25
30
30
14
10
10
10
14
10
10
10
Q48H2-A0Z
A05
A10
A15
230/208-1
1
1 or 2
1 or 2
1 or 2
38
63
88
88
50
70
90
90
8
6
3
3
10
8
8
8
38
38
38
25
50
50
50
50
50
25
50
50
8
8
8
10
8
8
10
10
10
10
10
10
Q48H2-B0Z
B06
B09
B15
230/208-3
1
1
1
1
29
47
56
56
40
50
60
60
8
8
6
6
10
10
10
10
Q48H2-C0Z
C06
C09
C15
460-3
1
1
1
1
15
24
28
28
20
25
30
30
12
10
10
10
12
10
10
10
Q60H2-A0Z
A05
A10
A15
230/208-1
1
1 or 2
1 or 2
1 or 2
45
70
95
95
60
90
100
100
8
4
3
3
10
8
8
8
45
45
45
25
50
50
60
60
60
25
50
50
8
8
8
10
8
8
10
10
10
10
10
10
Q60H2-B0Z
B09
B15
230/208-3
1
1
1
31
58
58
45
60
60
8
6
6
10
10
10
Q60H2-C0Z
C09
C15
460-3
1
1
1
17
31
31
25
35
35
10
8
8
10
10
10
TABLE 2
ELECTRICAL SPECIFICATIONS
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest
revision), article 310 for power conductor sizing.
Caution
: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special
attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
Maximum KW that can operate with heat pump on is 10KW. Other 5KW energizes during emergency heat only.
Maximum KW that can operate with heat pump on is 9KW. Other 6KW energizes during emergency heat only.
Содержание Q-TEC Q24H2 Series
Страница 6: ...Manual 2100 601 Page 6 of 42 FIGURE 1 UNIT DIMENSIONS Q24H2 Q30H2 Q36H2 Q42H2 Q48H2 Q60H2...
Страница 9: ...Manual 2100 601 Page 9 of 42 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH DUCT FREE PLENUM...
Страница 13: ...Manual 2100 601 Page 13 of 42 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...
Страница 15: ...Manual 2100 601 Page 15 of 42 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...
Страница 31: ...Manual 2100 601 Page 31 of 42 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...