Manual 2100-601
Page
41 of 42
MODEL
RETURN
AIR
TEMP.
PRESSURE
AIR TEMPERATURE ENTERING OUTDOOR COIL
75°
80°
85°
90°
95°
100°
105°
110°
115°
Q24H2
75 DB
62 WB
Low Side
High Side
118
326
119
340
121
358
122
377
125
399
128
422
132
449
135
477
138
508
80 DB
67 WB
Low Side
High Side
126
334
127
349
129
367
131
387
134
418
137
433
141
460
144
489
148
521
85 DB
72 WB
Low Side
High Side
130
346
131
361
134
380
136
401
139
423
142
448
146
476
149
506
153
539
Q30H2
75 DB
62 WB
Low Side
High Side
124
351
125
368
126
386
127
407
129
430
131
454
134
482
137
511
139
543
80 DB
67 WB
Low Side
High Side
133
360
134
377
135
396
136
417
136
442
140
466
143
494
146
524
149
557
85 DB
72 WB
Low Side
High Side
138
373
139
390
140
410
141
432
143
456
145
482
148
511
151
542
154
576
Q36H2
75 DB
62 WB
Low Side
High Side
131
351
132
369
133
389
134
410
136
434
137
459
138
486
140
514
142
543
80 DB
67 WB
Low Side
High Side
140
360
141
378
142
399
143
421
143
448
147
471
148
498
150
527
152
557
85 DB
72 WB
Low Side
High Side
145
373
146
391
147
413
148
436
150
461
152
487
153
515
155
545
157
576
Q42H2
75 DB
62 WB
Low Side
High Side
126
371
128
388
130
408
132
430
133
453
134
479
135
507
136
536
136
568
80 DB
67 WB
Low Side
High Side
135
380
137
398
139
418
139
441
139
471
143
491
144
520
145
550
145
583
85 DB
72 WB
Low Side
High Side
140
393
142
412
144
433
146
456
147
481
148
508
149
538
150
569
150
603
Q48H2
75 DB
62 WB
Low Side
High Side
123
373
125
392
128
412
130
435
133
459
136
486
139
514
143
543
147
575
80 DB
67 WB
Low Side
High Side
132
383
134
402
137
423
139
446
139
458
145
498
149
527
153
557
157
590
85 DB
72 WB
Low Side
High Side
137
396
139
416
142
438
144
462
147
487
150
515
154
545
158
576
162
611
Q60H2
75 DB
62 WB
Low Side
High Side
123
378
123
395
124
413
124
434
126
455
127
479
129
504
131
530
133
559
80 DB
67 WB
Low Side
High Side
132
388
132
405
133
424
133
445
133
467
136
491
138
517
140
544
142
573
85 DB
72 WB
Low Side
High Side
137
402
137
419
138
439
138
461
140
483
141
508
143
535
145
563
147
593
Low side pressure ± 4 psig
High side pressure ± 10 psig
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct
operating charge being in the system, the charge should be removed, system evacuated and recharged to serial
plate instructions.
75°F outdoor temperature condenser fan motor is running on low speed.
TABLE 9
COOLING PRESSURE
(ALL TEMPERATURES IN DEGREES F)
Содержание Q-TEC Q24H2 Series
Страница 6: ...Manual 2100 601 Page 6 of 42 FIGURE 1 UNIT DIMENSIONS Q24H2 Q30H2 Q36H2 Q42H2 Q48H2 Q60H2...
Страница 9: ...Manual 2100 601 Page 9 of 42 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH DUCT FREE PLENUM...
Страница 13: ...Manual 2100 601 Page 13 of 42 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...
Страница 15: ...Manual 2100 601 Page 15 of 42 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...
Страница 31: ...Manual 2100 601 Page 31 of 42 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...