Manual 2100-601
Page
4 of 42
TABLE 1
FACTORY BUILT-IN ELECTRIC HEAT TABLE
(See Table 2 for Available Electric Heat by Unit Model)
Nominal
KW
At 240V
At 208V
At 480V
At 460V
KW
1-Ph
Amps
3-Ph
Amps BTUH
KW
1-Ph
Amps
3-Ph
Amps BTUH
KW
3-Ph
Amps BTUH
KW
3-Ph
Amps BTUH
5.0
5.0
20.8
17,065
3.75
18.0
12,799
6.0
6.0
14.4
20,478
4.50
12.5
15,359
6.0
7.2
20,478
5.52
6.9
18,840
9.0
9.0
21.7
30,717
6.75
18.7
23,038
9.0
10.8
30,717
8.28
10.4
28,260
10.0
10.0
41.7
34,130
7.50
36.1
25,598
12.0
12.0
28.9
40,956
9.00
25.0
30,717
12.0
14.4
40,956 11.04
13.9
37,680
15.0
15.0
62.5
36.1
51,195 11.25
54.1
31.2
38,396
15.0
18.0
51,195 13.80
17.3
47,099
These electric heaters are available in 230/208V units only.
These electric heaters are available in 480V units only.
Q-T
ec
S
eries General Information
Q-T
ec
MODEL NOMENCLATURE
Q
36
H
2 – A
10
X
X
V
X
X
X
SPECIAL UNITS |
L - Low Ampacity
Circuit
REVISION
VOLTS & PHASE |
A - 230/208/60/1
B - 230/208/60/3
C - 460/60/3
INTERNAL CONTROLS
X - Standard
• High Pressure Switch
• Low Pressure Switch
• Compressor Time Delay
E - Low Ambient Control
Q - Outdoor Thermostat
R - Low Ambient Control &
Outdoor Thermostat
CLIMATE CONTROL OPTIONS
X - None
D - Electronic/Prog/Man/Auto
H - Electronic/Prog/Man/Auto with CO
2
B - Electronic/Prog/Humidistat/BACNet
C - Electronic/Prog/Humidistat/BACNet/CO
2
MODEL
NUMBER
Q-T
ec
CAPACITY |
24 - 2 Ton
30 - 2½ Ton
36 - 3 Ton
42 - 3½ Ton
48 - 4 Ton
60 - 5 Ton
KW
0Z - 0KW
05 - 5KW
06 - 6KW
09 - 9KW
10 - 10KW
12 - 12KW
15 - 15KW
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard)
B - Blank-off Plate
V - Commercial Ventilator - Motorized w/Exhaust
Spring Return
P - Commercial Ventilator - Motorized w/Exhaust
Power Return
R - Energy Recovery Ventilator w/Exhaust
FILTER OPTIONS
X - 1-Inch Fiberglass
(Standard)
F - 2-Inch Fiberglass
P - 2-Inch Pleated
COLOR OPTIONS
V - Platinum w/Slate
Front (Vinyl)
X - Beige paint
4 - Gray paint
HEAT
PUMP
COIL OPTIONS
X - Standard
1 - Phenolic coated
evaporator*
2 - Phenolic coated
condenser
3 - Phenolic coated
evaporator and
condenser coil*
*and reheat if
applicable
Содержание Q-TEC Q24H2 Series
Страница 6: ...Manual 2100 601 Page 6 of 42 FIGURE 1 UNIT DIMENSIONS Q24H2 Q30H2 Q36H2 Q42H2 Q48H2 Q60H2...
Страница 9: ...Manual 2100 601 Page 9 of 42 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH DUCT FREE PLENUM...
Страница 13: ...Manual 2100 601 Page 13 of 42 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...
Страница 15: ...Manual 2100 601 Page 15 of 42 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...
Страница 31: ...Manual 2100 601 Page 31 of 42 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...