FIGURE 18
Adjusting Freeze Alarm Values
6. Press UP or DOWN keys to adjust value.
7. Press ENTER key to save.
Freezestat
When the coil temperature is below 30°F, the unit will
generate a Freeze alarm on the TEC-EYE and a Freeze
Temp alarm on the LC6000. This will operate the
blower and turn off the compressor.
The alarm will be automatically reset when the coil
temperature rises above 55°F or after a 5-minute delay
while the temperature is above 30°F.
To adjust freezestat values:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to
Sys Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Alarm Config
(A9)
; press ENTER key.
5. Press ENTER key to scroll to desired value
Low
Temp
,
Delay
,
Reset Temp
or
Reset Del
(see Figure
18).
6. Press UP or DOWN keys to adjust value.
7. Press ENTER key to save.