Manual 2100-713A
Page
18 of 44
Model
Rated Volts &
Phase
Operating
Voltage
Range
No. Field
Power
Circuits
Single Circuit
Minimum Circuit
Ampacity
Maximum External
Fuse or Ckt. Brkr.
W24ABPD00, D0Z
D05
D08
240/220-1
254-198
1
1
1
15
28
44
20
30
45
W24ABPF00, F0Z
F05
415/380-3
456-342
1
1
10
11
15
15
W30ABPD00, D0Z
D05
D10
240/220-1
254-198
1
1
1
15
28
54
20
30
60
W30ABPF00, F0Z
F07
F12
415/380-3
456-342
1
1
1
10
16
26
15
20
30
W36ABPD00, D0Z
D05
D10
240/220-1
254-198
1
1
1
17
28
54
25
30
60
W36ABPE00, E0Z
E06
E12
230/200-3
242-180
1
1
1
17
21
39
25
25
40
W36ABPF00, F0Z
F07
F12
415/380-3
456-342
1
1
1
10
14
22
15
15
25
TABLE 3A
Electrical Specifications
−
W**ABP Series − 50Hz Units
Maximum size of the time delay fuse or "D" rated circuit breaker for protection of field wiring conductors.
These “Minimum Circuit Amp” values are to be used for sizing the field power conductors.
415/380-3 Electrical Ratings are 3-phase wye (star) systems requiring three (3) phase legs plus neutral and ground.
NOTE:
The indoor and outdoor motors and 24V transformer primary are connected at 240V derived from one (1) phase leg
to neutral. This is internally connected and no field wiring required.
NOTE:
All wiring must conform to NIC/EIC latest edition.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses
and conductor wires in accordance with the National Electrical Code and all local codes.
Model
Rated Volts &
Phase
Operating
Voltage
Range
No. Field
Power
Circuits
Single Circuit
Minimum Circuit
Ampacity
Maximum External
Fuse or Ckt. Brkr.
W24LBPF00, F0Z
F05
415/380-3
456-342
1
1
10
11
15
15
W30LBPF00, F0Z
F07
F12
415/380-3
456-342
1
1
1
10
16
26
15
20
30
W36LBPF00, F0Z
F07
F12
415/380-3
456-342
1
1
1
10
14
22
15
15
25
TABLE 3B
Electrical Specifications
−
W**LBP Series − 50Hz Units
Содержание MULTI-TEC W18ABP Series
Страница 2: ......
Страница 12: ......
Страница 18: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369 ...
Страница 19: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368 ...
Страница 24: ......
Страница 63: ......
Страница 108: ......
Страница 111: ......
Страница 115: ...Manual 2110 1456A Page 4 of 11 FUNCTIONAL COMPONENTS SEXP 910 12 1 11 4 2 6 8 5 9 7 13 14 10 3 ...
Страница 123: ......
Страница 126: ......