Manual 2100-713A
Page
29 of 44
FIGURE 22
Communication Wiring: Termination at the First Wall-Mount Unit
1. From the controller, extend the shielded cable through a separate conduit
and route to the provided terminal block next to the wall-mount control
board.
Note that the terminal block label is clearly marked “+” and “-”. These
connections are polarity-sensitive. Two-wire communication from control
board is prewired to terminal block. Make sure to match "+" and "-"
symbols on controller terminal blocks.
2. Connect the wires matching the terminal
designations (+/-) of the controller terminals.
Leave the drain wire loose.
3. Connect another cable in a similar
fashion (“daisy chain”) to route in
conduit to the second wall-mount unit.
Connect both drain wires with wire nut.
Maximum two wires per terminal.
From LC6000
Controller
From LC6000 Controller
To Wall-Mount Unit 2
Control Board RS485
0
RS485
R+T+ / R-T-
RS485
R+T+ / R-T-
RS485
R+T+ / R-T-
From LC6000 Controller
PLAN
PLAN
PLAN
Wall-Mount Unit 1
Control Board
Wall-Mount Unit 1
Control Board
Wall-Mount Unit 1
Control Board
Содержание MULTI-TEC W18ABP Series
Страница 2: ......
Страница 12: ......
Страница 18: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369 ...
Страница 19: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368 ...
Страница 24: ......
Страница 63: ......
Страница 108: ......
Страница 111: ......
Страница 115: ...Manual 2110 1456A Page 4 of 11 FUNCTIONAL COMPONENTS SEXP 910 12 1 11 4 2 6 8 5 9 7 13 14 10 3 ...
Страница 123: ......
Страница 126: ......