Manual 2100-628
Page
22 of 24
TABLE 5
COOLING PRESSURE TABLE
OUTDOOR AMBIENT TEMPERATURE °C
Low side pressure ± 4 PSIG
High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating
charge being in the system, the charge should be removed and the system evacuated and recharged to serial plate
charge weight.
NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear
elevated, check condenser fan wiring. See “Condenser Fan Operation” (page 17).
Model
Return Air
Temperature °C
Pressure
35
37
39
41
43
45
47
49
51
53
55
K36*2
27° DB
19° WB
Low Side
High Side
143
145
147
148
150
152
154
156
158
160
162
368
388
408
429
449
470
489
509
528
547
566
27° DB
19° WB
Low Side
High Side
143
145
147
149
151
153
155
158
160
162
164
368
389
409
430
451
472
492
511
530
549
568
K42*2
27° DB
19° WB
Low Side
High Side
27° DB
19° WB
Low Side
High Side
K48*2
27° DB
19° WB
Low Side
High Side
149
149
149
149
149
149
150
153
156
159
162
377
396
415
435
454
473
494
517
539
562
585
27° DB
19° WB
Low Side
High Side
151
152
152
153
154
154
156
159
162
165
168
378
397
416
436
455
474
495
519
542
565
589
K60*2
27° DB
19° WB
Low Side
High Side
27° DB
19° WB
Low Side
High Side