TABLE 6
ELECTRICAL SPECIFICATIONS
Model
Rated Volts,
Hertz & Phase
No. Field
Power
Circuits
Single Circuit
Minimum
Circuit
Ampacity
Maximum
External Fuse
or Ckt. Brkr.
Field Power
Wire Size
Ground Wire
K36A2-A0Z
208/230-60-1
1
-A05
1
K36A2-N0Z
400-60-3
1
8.2
10
14
14
-N05
1
9.8
15
14
14
K42A2-A0Z
208/230-60-1
1
-A05
1
K42A2-N0Z
400-60-3
1
-N05
1
K48A2-A0Z
208/230-60-1
1
-A05
1
K48A2-N0Z
400-60-3
1
12.7
15
14
14
-N05
1
12.7
15
14
14
K60A2-A0Z
208/230-60-1
1
-A05
1
K60A2-N0Z
400-60-3
1
14.1
20
12
12
-N05
1
14.1
20
12
12
Model
Rated Volts,
Hertz & Phase
No. Field
Power
Circuits
Single Circuit
Minimum
Circuit
Ampacity
Maximum
External Fuse
or Ckt. Brkr.
Field Power
Wire Size
Ground Wire
K36L2-A0Z
208/230-60-1
1
-A05
1
K36L2-N0Z
400-60-3
1
8.2
10
14
14
-N05
1
9.8
15
14
14
K42L2-A0Z
208/230-60-1
1
-A05
1
K42L2-N0Z
400-60-3
1
-N05
1
K48L2-A0Z
208/230-60-1
1
-A05
1
K48L2-N0Z
400-60-3
1
12.7
15
14
14
-N05
1
12.7
15
14
14
K60L2-A0Z
208/230-60-1
1
-A05
1
K60L2-N0Z
400-60-3
1
14.1
20
12
12
-N05
1
14.1
20
12
12
These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the
National Electric Code (latest version), Article 310 for power conductor sizing.
Maximum Size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electric Code and all local codes.