background image

Manual 2100-639A 

Page 

6 of 28

INSTALLATION

        WARNING

Failure to provide the 1/4" clearance between 

the supply duct and a combustible surface 

for the first 3' of duct can result in fire causing 

damage, injury or death.

WALL MOUNTING INFORMATION

1.  Two holes for the supply and return air openings 

must be cut through the wall as shown in Figure 2.

2.  On wood frame walls, the wall construction must 

be strong and rigid enough to carry the weight of 
the unit without transmitting any unit vibration.

3.  Concrete block walls must be thoroughly inspected 

to insure that they are capable of carrying the 
weight of the installed unit.

MOUNTING THE UNIT

1.  These units are secured by wall mounting brackets 

which secure the unit to the outside wall surface at 
both sides.  A bottom mounting bracket, attached 
to skid for shipping, is provided for ease of 
installation, but is not required.

2.  The unit itself is suitable for 0 clearance, but the 

supply air duct flange and the first 3' of supply 
air duct require a minimum of 1/4" clearance 
to combustible material for Model Series H36, 
H42, H48 and H60.  However, it is generally 
recommended that a 1" clearance is used for 
ease of installation and maintaining the required 
clearance to combustible material.  See Figures 
2A-C for details on opening sizes.

3.  Locate and mark lag bolt locations and bottom 

mounting bracket location (see Figure 2).

4.  Mount bottom mounting bracket.

5.  Hook top rain flashing, attached to front-right 

corner of supply flange for shipping, under back 
bend of top.

 6.   Position unit in opening and secure with 5/16 lag 

bolts; use 7/8" diameter flat washers on the lag 
bolts.

7.  Secure rain flashing to wall and caulk across entire 

length of top (see Figure 2).

8.  For additional mounting rigidity, the return air 

and supply air frames or collars can be drilled 
and screwed or welded to the structural wall itself 
(depending upon wall construction).  Be sure to 
observe required clearance if combustible wall.

9.  On side-by-side installations, maintain a minimum 

of 20" clearance on right side to allow access to 
control panel and heat strips, and to allow proper 
airflow to the outdoor coil.  Additional clearance 
may be required to meet local or national codes.

10. Care should be taken to ensure that the 

recirculation and obstruction of condenser 
discharge air does not occur.  Recirculation of 
condenser discharge air can be from either a 
single unit or multiple units.  Any object such as 
shrubbery, a building or other large object can 
cause obstructions to the condenser discharge 
air. Recirculation or reduced airflow caused by 
obstructions will result in reduced capacity, 
possible unit pressure safety lockouts and reduced 
unit service life.

 

For units with blow through condensers, it is 
recommended there be a minimum distance of 10' 
between the front of the unit and any barrier or 20' 
between the fronts of two opposing (facing) units.

NOTE: For side by side installation of two (2) H**A models there 
must be 20" between units.  This can be reduced to 15" by using 
a H**L model (left side compressor and controls) for the left unit 
and H**A (right side compressor and controls) for right unit.

Clearances Required for Service Access and 

Adequate Condenser Airflow

MODELS

LEFT

SIDE

RIGHT

SIDE

DISCHARGE 

SIDE

H24A, H36A

15"

20"

10'

H24L, H36L

20"

15"

10'

H42A, H48A, H60A

20"

20"

10'

H42L, H48L, H60L

20"

20"

10'

Minimum Clearances Required to

Combustible Materials

MODELS

SUPPLY AIR DUCT

FIRST 3'

CABINET

H24A, H24L

0"

0"

H36A, H36L

1/4"

0"

H42A, H42L
H48A, H48L
H60A, H60L

1/4"

0"

Содержание H24A4-A

Страница 1: ...CONDITIONER Models INSTALLATION INSTRUCTIONS H24A4 A H36A4 A H42A4 A H48A4 A H60A4 A H24L4 A H36L4 A H42L4 A H48L4 A H60L4 A Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 210...

Страница 2: ...ional Accessories 22 Table 10 Vent and Control Options 22 Table 11 Unit Low Voltage Terminal Connection Chart MV Series Controller 23 Table 12 Unit Low Voltage Terminal Connection Chart MC Series Cont...

Страница 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Страница 4: ...hould be consulted before the installation is made See page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to...

Страница 5: ...be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return air grille is required with in...

Страница 6: ...ng to wall and caulk across entire length of top see Figure 2 8 For additional mounting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural...

Страница 7: ...ting Side Wall Location Shipping Flashing Entrances Electrical Optional Entrance Electrical High Voltage Entrance Electrical Low Voltage Top Rain models non Econ vent door for Standard flush Lockable...

Страница 8: ...F TOP TOP WALL OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE OPENING TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER DUCT Wall Opening and Hole Location View Right Side...

Страница 9: ...4 CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER ACCESS...

Страница 10: ...1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE S...

Страница 11: ...ls This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible materia...

Страница 12: ...TURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH...

Страница 13: ...ssure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to...

Страница 14: ...oor 3 Replace filter 4 Press Reset button 5 Verify filter light is off 6 Replace filter door 7 Turn on unit power For units equipped with economizer 1 Turn off unit power 2 Remove hood cover 3 Remove...

Страница 15: ...eing an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charg...

Страница 16: ...all models covered by this manual The compressor control module is an anti short cycle lockout timer with high and low pressure switch monitoring and alarm relay output Adjustable Delay on Make and De...

Страница 17: ...ntacts Economizer Only 9 14 Occupied Signal Input Econ Emergency Open Open Blade 100 Economizer Only E 15 Econ Open Output 6V HOT 24V HOT after Blade Open 100 and delay Economizer Only 10 16 Alarm Rel...

Страница 18: ...this refrigerant charge quantity The pressure table on the following page shows nominal pressures for the units Since many installation specific situations can affect the pressure readings this infor...

Страница 19: ...3 132 501 134 529 135 558 136 586 80 67 Low Side High Side 128 348 130 375 133 402 135 429 138 457 139 485 141 514 143 543 144 572 145 601 85 72 Low Side High Side 132 360 135 388 138 416 140 444 143...

Страница 20: ...10 50 50 60 90 125 8 8 6 4 2 10 10 10 8 6 58 58 26 52 60 60 30 60 6 6 10 6 10 10 10 10 H60A2 A00 A0Z A05 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 42 42 60 86 112 60 60 60 90 125 8 8 6 3 2 10 10 10 8...

Страница 21: ...s shown are for units equipped with standard 1 throwaway filter or 1 washable filter Derate ESP by 15 for 2 pleated filters Model H24A L H36A L H42A L H48A L H60A L Outlet FRONT FRONT TOP FRONT FRONT...

Страница 22: ...02 A10L X EHWA03 A05L X EHWA03 A10L X EHWA03 A15L X EHWA05 A05L X X X EHWA05 A10L X X X EHWA05 A15L X X X Circuit Breakers WMCB Pull Disconnects WMPD WMCB 03A X WMCB 05A X WMCB 08A X X WMCB 09A X TABL...

Страница 23: ...losed Dry Contacts MV Signals Blade Switch Fail Alarm 8 on Relay Board 8 13 Blade Switch Delay Relay Normally Closed Dry Contacts MV Signals Blade Switch Fail Alarm 9 on Relay Board 9 14 Occupied Sign...

Страница 24: ...sed Dry Contacts Not Used on MC 8 13 Blade Switch Delay Relay Normally Closed Dry Contacts Not Used on MC 9 14 Occupied Signal Input Econ Emergency Open Open Blade 100 Unit Receives Signal from MC E o...

Страница 25: ...ter Switch Normally Closed Dry Contacts Not Used 5 12 Blade Switch Delay Relay Normally Closed Dry Contacts Not Used 8 13 Blade Switch Delay Relay Normally Closed Dry Contacts Not Used 9 14 Occupied S...

Страница 26: ...1 C R COM 208V 240V 2 500 NC NO COM T1 HPC R Y CC ALR 30 C Module Black White Low Press Control Hi Press Control Hi Voltage Field Connections Green Brown White Yellow White Pink Purple Blue White Yell...

Страница 27: ...2 NC 3 2 1 NO 12 PIN PLUG COM DAMPER MOTOR DAMPER BLADE IN RED BLACK BLACK IS SHOWN WITH THE CONTACT POSITION IAQ AUX1 O Y2 I 8 S BUS ACT 24V ACT RED YELLOW IAQ R MAT PLUG PLUG PLUG PLUG BROWN WHITE G...

Страница 28: ...Vent Plug Pin 2 on Vent Plug Pin 5 on Vent Plug Pin 7 on Vent Plug Pin 10 on Vent Plug Time Delay Relay T1 T2 Y HPC Lo Press Sw LPC LPC Alarm Relay ALR CC Comp Control Module R MV Controller C 4 5 W...

Отзывы: