HIGH PRESSURE AND LOW PRESSURE 

SWITCHES

All H**A/H**L wall mounted air conditioner series 
models are supplied with a remote reset for the high 
and low pressure switches.  The first time the high 
or low pressure switches are tripped, they will reset 
automatically. If tripped a second time, reset the 
switches by turning the thermostat off, then back on 
again, resetting the compressor control module. 

CONDENSER FAN OPERATION

NOTE: Certain models may be equipped with a 

low ambient control (LAC), and if so equipped the 

condenser fan motor may have a delayed start until 

system refrigerant operating pressure builds up.  

After starting, the fan motor may or may not cycle 

depending upon ambient conditions.  This is normal 

operation.

  The condenser fan motor on 230/208 

volt, one and three phase, 60 HZ units is a two-speed 
motor that comes factory wired on high speed for peak 
performance.  If ambient conditions permit, it can be 
reconnected to low speed (red wire) for lower sound 
level.  See unit wiring diagram.  

SERVICE HINTS

1.  Caution owner/operator to maintain clean air filters 

at all times and to not needlessly close off supply 
and return air registers.  This reduces airflow 
through the system, which shortens equipment 
service life as well as increasing operating costs.

2.  Check all power fuses or circuit breakers to be sure 

they are the correct rating.

3.  Periodic cleaning of the outdoor coil to permit full 

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

COOLING – 24VAC from MV controller at terminal 4 (Y)
pulls in compressor contactor, starting the compressor 
and outdoor motor.  (See Note under Condenser Fan 
Operation if equipped with low ambient control.)  
Terminal 9 (G) indoor motor circuit is energized by 
the MV controller on any call for cooling operation or 
can be energized by manual fan switch on subbase for 
constant air circulation.  On a call for heating from the 
MV controller makes at the relay board pulling in heat 
contact for the strip heat and blower operation.  On a 
call for second stage heat, R-W2 makes bringing on 
second heat contactor, if so equipped.  See Table 1 on 
following page.

COMPRESSOR CONTROL MODULE

The compressor control module (CCM) is standard on 
all models covered by this manual.  The compressor 

control module is an anti-short cycle/lockout timer with 
high and low pressure switch monitoring and alarm 
relay output.

Adjustable Delay-on-Make and Delay-on-Break Timer

On initial power up and any time power is interrupted 
to the unit, the delay-on-make period begins, which 
is the time set on the potentiometer (delay-on-break 
time) plus 10% of the delay-on-break setting.  When 
the delay-on-make period is complete and the high 
pressure switch and low pressure switch are closed, the 
compressor contactor is energized.  Upon shutdown 
(end of the call for cooling), the delay-on-break timer 
starts and prevents restart (next call for cooling) until 
the delay-on-break period has expired. 

During routine operation of the unit with no power 
interruptions, the compressor will operate on demand 
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor 
contactor will de-energize immediately.  The lockout 
timer will go into a 

soft lockout

 and stay in soft lockout 

until the high pressure switch closes and the delay-on-
break time has expired.  If the high pressure switch 
opens again in this same operating cycle, the unit will go 
into 

manual lockout

 condition and the alarm relay circuit 

will energize.  Recycling the wall thermostat or main 
power resets the manual lockout. 

Low Pressure Switch, Bypass and Lockout Sequence

If the low pressure switch opens for more than 120 
seconds, the compressor contactor will de-energize and 
go into a soft lockout.  Regardless the state of the low 
pressure switch, the contactor will re-energize after 
the delay-on-make time delay has expired.  If the low 
pressure switch remains open, or opens again for longer 
than 120 seconds, the unit will go into manual lockout 
condition and the alarm relay circuit will energize.  
Recycling the wall thermostat or main power resets the 
manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications 
where alarm relay is employed.  This terminal is 
powered whenever the compressor is locked out due to 
HPC or LPC sequences as described.

NOTE:  Both high and low pressure switch controls are 

inherently automatic reset devices.  The high 

pressure switch and low pressure switch cut 

out and cut in settings are fixed by specific air 

conditioner unit model.  The lockout features, 

both soft and manual, are a function of the 

compressor control module.

Содержание H24A4-A

Страница 1: ...CONDITIONER Models INSTALLATION INSTRUCTIONS H24A4 A H36A4 A H42A4 A H48A4 A H60A4 A H24L4 A H36L4 A H42L4 A H48L4 A H60L4 A Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 210...

Страница 2: ...ional Accessories 22 Table 10 Vent and Control Options 22 Table 11 Unit Low Voltage Terminal Connection Chart MV Series Controller 23 Table 12 Unit Low Voltage Terminal Connection Chart MC Series Cont...

Страница 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Страница 4: ...hould be consulted before the installation is made See page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to...

Страница 5: ...be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return air grille is required with in...

Страница 6: ...ng to wall and caulk across entire length of top see Figure 2 8 For additional mounting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural...

Страница 7: ...ting Side Wall Location Shipping Flashing Entrances Electrical Optional Entrance Electrical High Voltage Entrance Electrical Low Voltage Top Rain models non Econ vent door for Standard flush Lockable...

Страница 8: ...F TOP TOP WALL OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE OPENING TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER DUCT Wall Opening and Hole Location View Right Side...

Страница 9: ...4 CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER ACCESS...

Страница 10: ...1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE S...

Страница 11: ...ls This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible materia...

Страница 12: ...TURN AIR SUPPLY AIR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH...

Страница 13: ...ssure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to...

Страница 14: ...oor 3 Replace filter 4 Press Reset button 5 Verify filter light is off 6 Replace filter door 7 Turn on unit power For units equipped with economizer 1 Turn off unit power 2 Remove hood cover 3 Remove...

Страница 15: ...eing an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charg...

Страница 16: ...all models covered by this manual The compressor control module is an anti short cycle lockout timer with high and low pressure switch monitoring and alarm relay output Adjustable Delay on Make and De...

Страница 17: ...ntacts Economizer Only 9 14 Occupied Signal Input Econ Emergency Open Open Blade 100 Economizer Only E 15 Econ Open Output 6V HOT 24V HOT after Blade Open 100 and delay Economizer Only 10 16 Alarm Rel...

Страница 18: ...this refrigerant charge quantity The pressure table on the following page shows nominal pressures for the units Since many installation specific situations can affect the pressure readings this infor...

Страница 19: ...3 132 501 134 529 135 558 136 586 80 67 Low Side High Side 128 348 130 375 133 402 135 429 138 457 139 485 141 514 143 543 144 572 145 601 85 72 Low Side High Side 132 360 135 388 138 416 140 444 143...

Страница 20: ...10 50 50 60 90 125 8 8 6 4 2 10 10 10 8 6 58 58 26 52 60 60 30 60 6 6 10 6 10 10 10 10 H60A2 A00 A0Z A05 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 42 42 60 86 112 60 60 60 90 125 8 8 6 3 2 10 10 10 8...

Страница 21: ...s shown are for units equipped with standard 1 throwaway filter or 1 washable filter Derate ESP by 15 for 2 pleated filters Model H24A L H36A L H42A L H48A L H60A L Outlet FRONT FRONT TOP FRONT FRONT...

Страница 22: ...02 A10L X EHWA03 A05L X EHWA03 A10L X EHWA03 A15L X EHWA05 A05L X X X EHWA05 A10L X X X EHWA05 A15L X X X Circuit Breakers WMCB Pull Disconnects WMPD WMCB 03A X WMCB 05A X WMCB 08A X X WMCB 09A X TABL...

Страница 23: ...losed Dry Contacts MV Signals Blade Switch Fail Alarm 8 on Relay Board 8 13 Blade Switch Delay Relay Normally Closed Dry Contacts MV Signals Blade Switch Fail Alarm 9 on Relay Board 9 14 Occupied Sign...

Страница 24: ...sed Dry Contacts Not Used on MC 8 13 Blade Switch Delay Relay Normally Closed Dry Contacts Not Used on MC 9 14 Occupied Signal Input Econ Emergency Open Open Blade 100 Unit Receives Signal from MC E o...

Страница 25: ...ter Switch Normally Closed Dry Contacts Not Used 5 12 Blade Switch Delay Relay Normally Closed Dry Contacts Not Used 8 13 Blade Switch Delay Relay Normally Closed Dry Contacts Not Used 9 14 Occupied S...

Страница 26: ...1 C R COM 208V 240V 2 500 NC NO COM T1 HPC R Y CC ALR 30 C Module Black White Low Press Control Hi Press Control Hi Voltage Field Connections Green Brown White Yellow White Pink Purple Blue White Yell...

Страница 27: ...2 NC 3 2 1 NO 12 PIN PLUG COM DAMPER MOTOR DAMPER BLADE IN RED BLACK BLACK IS SHOWN WITH THE CONTACT POSITION IAQ AUX1 O Y2 I 8 S BUS ACT 24V ACT RED YELLOW IAQ R MAT PLUG PLUG PLUG PLUG BROWN WHITE G...

Страница 28: ...Vent Plug Pin 2 on Vent Plug Pin 5 on Vent Plug Pin 7 on Vent Plug Pin 10 on Vent Plug Time Delay Relay T1 T2 Y HPC Lo Press Sw LPC LPC Alarm Relay ALR CC Comp Control Module R MV Controller C 4 5 W...

Отзывы: