Manual 2100-670I
Page
19 of 47
Blower Status Switch
The unit is equipped with a differential pressure airflow
switch to monitor the blower (see Figure 30). If the
blower is turned on and the switch doesn't open to
indicate there is differential pressure between the inlet
and outlet of the blower, an alarm will be generated.
For switch settings, see Figure 30.
TABLE 3B
HR58AP* Blower Speeds
TABLE 4
Rated Airflow
Nominal Rated CFM
Nominal Rated ESP
High
Low
HR36AP*
1200
950
0.00
HR58AP*
1800
1400
0.10
TABLE 5
Indoor Blower Performance
Speed
High
Low
ESP
(Inch H
2
0)
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
HR36AP*
0.00
1260
1200
995
950
HR58AP*
0.10
1885
1800
1470
1400
TABLE 6
Maximum ESP of Operation
Electric Heat Only
* Unit is rated for free blow non-ducted
operation with SGR-5W Supply Grille
and RGR-5W Return Grille.
Model
Static Pressure*
-A0Z
-A05
.00"
.00"
-B0Z
-B06
.00"
.00"
Mode
Speed
Percentage
Controller
Output Volts
CFM
Freezestat Active
80.0
8.0 v
2260
High Sensible Full
Load Cooling
75.0
7.5 v
2180
High Sensible Part
Load Cooling
50.0
5.0 v
1705
Standard Full Load
Cooling
55.0
5.5 v
1830
Standard Part Load
Cooling
35.0
3.5 v
1335
Economizer Standard
Economizer High S/T
45.0
75.0
4.5 v
7.5 v
1600
1950
Heating
35.0
3.5 v
1335
Dehumidification
Mode
35.0
3.5 v
1335
FIGURE 30
Dirty Filter Switch and Blower Status Switch
FIGURE 31
Verifying Differential Airflow Status
Differential airflow status can be viewed by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to
I/O Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Digital In
Config (C2)
; press ENTER key.
5. Reference
7
NoAir
row and
Val
column (see Figure
31).