BLADE ADJUSTMENT FOR DESIRED 

VENTILATOR AIR

The amount of ventilation air supplied by the 

commercial room ventilator is dependent on five (5) 

factors.

  1.  Return air duct static pressure drop.

  2.  Supply air duct static pressure drop.

  3.  Indoor blower motor speed.

  4.  Damper blade open position setting for each mode 

of operation.

  5.  Tightness or looseness of building envelope.

You will have to set the damper position for each mode 
of operation using the set-point potentiometers on the 
Damper Position Step Control Board.  See Figure 5.

Refer to the graphs on the following pages to determine 
the necessary blade setting to achieve the ventilation 
air required based upon blower only, Stage #1 and 
Stage #2 modes of operation.  These charts are model 

specific, so you will have to match the chart to the 

specific model you are working with.

  1.  Set the damper position for blower only operation.

   

A.  Energize the evaporator blower by switching  

   

 

thermostat to the manual fan position with   

   

 

heat/cool in OFF position 

(or Jumper “R” to  

   

 

“G” with thermostat disconnected at unit)

.

   

B.  Locate potentiometer “R1” on the Damper   

   

 

Position Step Control Board.  See Figure 5.

   

C.  Using a small screwdriver, adjust  

   

 

potentiometer until damper position aligns   

   

 

with numerical location on the label interior  

   

 

of the sheet metal damper assembly.

  2.  Set the damper position for Stage #1 cooling/   
   

heating operation.

   

A.  Energize the evaporator blower and  

   

 

compressor by switching thermostat to the heat  

   

 

or cool mode, and setting it to a minimal offset  

   

 

to the room temperature to engage the mode of  

 

  operation 

desired 

(or Jumper “R” to “G”  

   

 

and “Y1” with thermostat disconnected at  

 

  unit)

.

   

B.  Locate potentiometer “R2” on the Damper   

   

 

Position Step Control Board.  See Figure 5.

   

C.  Using a small screwdriver, adjust  

   

 

potentiometer until damper position aligns  

   

 

with numerical location on the label interior of  

   

 

the sheet metal damper assembly.  (Make sure  

   

 

there is not a call on “Y2” or “W2”.)

  3.  Set the damper position for Stage #2 cooling/   
   

heating operation.

   

A.  Energize the evaporator blower and  

   

 

compressor by switching thermostat to the heat  

   

 

or cool mode and set a large temperature offset  

   

 

to the room temperature to engage the mode of  

 

  operation 

desired 

(or Jumper “R” to “G”,  

     “Y1” and “Y2” with thermostat disconnected  
 

  at 

unit)

.

   

B.  Locate potentiometer “R3” on the Damper   

   

 

Position Step Control Board.  See Figure 5.

   

C.  Using a small screwdriver, adjust  

   

 

potentiometer until damper position aligns  

   

 

with numerical location on the label interior of  

   

 

the sheet metal damper assembly per the chart.

Содержание CRVMP-5

Страница 1: ...EL CRVMP 5 For Use with Bard 3 through 5 Ton WA S Series Wall Mount Air Conditioners INSTALLATION INSTRUCTIONS Manual 2100 457D Supersedes 2100 457C File Volume III Tab 19 Date 01 24 14 Bard Manufactu...

Страница 2: ...igures Figure 1 Removal of Exterior Panels 4 Figure 2 Remove Air Filter Exhaust Cover Plate 5 Figure 3 Install Ventilator 6 Figure 4 Step Control Installation 8 Figure 5 Damper Control Board 9 Figure...

Страница 3: ...eived and that there is no visible damage Note any shortages or damage on all copies of the freight bill The receiving party must contact the last carrier immediately preferably in writing requesting...

Страница 4: ...embly which includes the integral ventilator with attached electrical harness step control assembly and miscellaneous hardware WARNING Open and lock unit disconnect switch before installing this acces...

Страница 5: ...00 457D Page 5 of 16 FIGURE 2 REMOVE AIR FILTER AND EXHAUST COVER PLATE 3 Remove and save existing unit air filter and screws from front center grille See Figure 2 4 Remove and discard the exhaust cov...

Страница 6: ...ntilator into the unit to the far left side clearing the right filter bracket Once the ventilator is fully inserted slide the ventilator to the right until it is tight against the back of the control...

Страница 7: ...he control panel through the wire looms and route them into the low voltage box through the bushing See Figure 4 Make connections following the wiring diagram enclosed in Literature Assembly or on ven...

Страница 8: ...t damper blade for required ventilation See next section 16 Replace mist eliminator filter Be sure that it is installed with the drain holes to the bottom 17 Remove blank off plate or barometric fresh...

Страница 9: ...TENTIOMETER FOR STAGE 1 HEATING OR COOLING DAMPER POSITION G AND Y1 CONTROL SIGNALS FOR STAGE 2 HEATING OR COOLING DAMPER POSITION G Y1 AND Y2 CONTROL SIGNALS R3 ADJUSTMENT POTENTIOMETER R1 ADJUSTMENT...

Страница 10: ...See Figure 5 C Using a small screwdriver adjust potentiometer until damper position aligns with numerical location on the label interior of the sheet metal damper assembly 2 Set the damper position fo...

Страница 11: ...Ventilation Airflow CFM Vent Position WA3S Ventilation Airflow Stage 2 Operation Blower Only Stage 1 Operation 0 100 200 300 400 500 600 700 800 900 1000 0 2 5 5 7 5 10 12 5 15 17 5 20 22 5 25 27 5 30...

Страница 12: ...Page 12 of 16 0 100 200 300 400 500 600 700 800 900 1000 0 2 5 5 7 5 10 12 5 15 17 5 20 22 5 25 27 5 30 Ventilation Airflow CFM Vent Position WA5S Ventilation Airflow Stage 2 Operation Stage 1 Operat...

Страница 13: ...rd rate to ASHRAE standards BASIC INSTALLATION 1 Make sure power is turned off to the unit 2 Follow steps beginning on page 2 for installation for standard control and vent assembly then proceed with...

Страница 14: ...on with Controller For High Altitude Installations CAL Used for Field Calibration 1 Damper should be fully closed at 700 ppm if not Potentiometer R7 can be adjusted clockwise CW to close it If it is f...

Страница 15: ...ir damper built in with positive closed position Provides exhaust air capability to prevent pressurization of tight buildings Actuator motor 24 volt power open spring return with built in torque limit...

Страница 16: ...al 2100 457D Page 16 of 16 A call for cooling cycles the compressor and dampers remain in the ventilation mode On loss of blower operation CRV closes fully See Figure 8 FIGURE 8 CALL FOR COOLING OPERA...