12. Press UP or DOWN button to toggle ENABLE/

DISABLE. Press ENTER button to select/save choice.

13. Press DOWN button to scroll through additional 

DEHUMIDIFICATION screen choices:

 • 

ALLOW HTG DEHUM = Allows 
dehumidification in heating:  YES/NO (default 
is YES).

 • 

DEHUM SETPT = Relative Humidity (RH) 
setpoint: 45% RH to 80% RH, 1% increments 
(default is 60%RH).

 

• 

DEHUM SPAN = Amount of RH% removal 
allowed past setpoint: 5% to 10%, 1% 
increments (default is 5%RH).

14. Press ENTER button to save changes.

15. Press LEFT button to return to the home screen. 

Proceed to 

System Enable

 on page 9 to continue 

the setup process.

Heat Pump Applications

 (see Figure 7)

NOTE:

 

The following is for heat pump applications. 
A/C application information can be found in the 
previous section.

1. Press 

RIGHT button to access Main Menu screen.

2. Press 

DOWN button to scroll to TECHNICIAN. 

Press ENTER button. 

3.  Controller will ask for password. Press UP and RIGHT 

buttons to enter ‘BARD’. Press ENTER button.

4.  In the TECHNICIAN menu screen, press ENTER 

button to enter the APPLICATION menu.

5.  Press DOWN button to scroll to ADDITIONAL 

SETUP. Press ENTER button.

6.  Press ENTER button again to choose AUX 

ELECTRIC HEAT.

7.  Press ENTER button again to highlight current AUX 

HEAT choices (see Figure 8).

8.  Press UP or DOWN button to scroll through AUX 

HEAT screen choices:

 • 

W/O LOCKOUT = Auxiliary heat will activate 
regardless of compressor operation or outdoor 
air temperature (factory default). If W/O 
LOCKOUT is chosen, proceed to set delay-on 
time (Step 9).

 

• 

COMP LOCKOUT = Compressor locks out 
below the selected outdoor air temperature. 

Requires optional Bard 8403-061 Outdoor Air 
Temperature Sensor.

 

• 

NONE = No auxiliary strip heat; controller will 
not energize W2. If NONE is chosen, press 
LEFT button to return to the home screen.

9.  Press DOWN button to highlight DELAY (MINS).

10. Press ENTER button to highlight default DELAY 

minutes.

11. Press UP or DOWN button to select amount 

of minutes desired to delay the electric heat 
before activation: 10-120 minutes, in 10 minute 
increments (factory default 15 minutes). Press 
ENTER button to save choice.

12. Press LEFT button to return to ADDITIONAL 

SETUP.

DEHUMIDIFICATION

DEHUM: 

ENABLE

ALLOW HEATING DEHUM: YES
DEHUM SETPT: 60%RH
DEHUM SPAN: 5%RH

FIGURE 6

Dehumidification (Air Conditioner)

ADDITIONAL SETUP

AUX ELECTRIC HEAT

VENTILATION
FAN
HUMIDITY
MOTION SENSOR
SENSORS
STAGING

FIGURE 7

Additional Setup (Heat Pump)

Auxiliary Electric Heat Setup

If the heat pump selection is chosen, electric heat 
must be configured. These steps do not apply to air 
conditioners or other types of conventional heating. To 
configure the auxiliary heat from the home screen:

DEHUMIDIFICATION

AUX HEAT: 

W/O LOCKOUT

DELAY (MINS): 15

FIGURE 8

Aux Heat Setup

Содержание CompleteStat CS9B-THOA

Страница 1: ...ION OPERATION QUICK START GUIDE Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 684B Supersedes 2100 684A Date 1 12 22 CompleteStatTM Controller Models CS9B THOA CS9B THOCA CS9BE THOA CS9BE THOCA ...

Страница 2: ...t Buttons and Screens 5 Figure 3 Application Menu 5 Figure 4 Additional Setup Air Conditioner 6 Figure 5 Fan Setup Air Conditioner 6 Figure 6 Dehumidification Air Conditioner 7 Figure 7 Additional Setup Heat Pump 7 Figure 8 Aux Heat Setup 7 Figure 9 Fan Setup Heat Pump 8 Figure 10 Dehumidification Heat Pump 9 Figure 11 Additional Setup Heat Pump 9 Figure 12 System Enable 9 Figure 13 Setpoints 9 NO...

Страница 3: ...inward until they clear the cover Remove base plate from controller INSTALLATION 3 Route control wiring through base plate 4 With the embossed UP arrows of the base plate pointing in the appropriate direction fasten the base plate to the desired wall location A vertical horizontal 2x4 wall handybox can be used for the CO2 sensing CompleteStat and a vertical only 2x4 wall handybox can be used for n...

Страница 4: ...l Setback 15 Heat Setback 16 Standby Time Minutes 17 Motion Sensing Daily Schedule 18 Date 19 Time 20 Occupied Minimum Cooling 21 Occupied Maximum Cooling 22 Unoccupied Minimum Cooling 23 Unoccupied Maximum Cooling 24 CO2 Setpoint 25 CO2 Span NOTES _______________________________________________________________________________________ _______________________________________________________________...

Страница 5: ...conds factory default is 120 seconds See page 14 in the latest version of CompleteStat Controller Advanced Programming Features 2100 685 for information on adjusting the inactivity setting NOTE If the screen includes up and down arrows in the upper corners as shown in Figure 7 on page 7 additional choices can be found by continuing to press the UP or DOWN buttons MAIN MENU SYSTEM SETPOINTS DATE TI...

Страница 6: ...NE No economizer or standard vent package ERV CRV MFAD EN DIS Economizer in system FAN SETUP SPEEDS CONSTANT SPEED OFF DELAY SECS 0 UNOCC AUTO OCC AUTO FIGURE 5 Fan Setup Air Conditioner 3 Press ENTER button to select save appropriate economizer option 4 Press LEFT button to go back to ADDITIONAL SETUP 5 The indoor blower can be set for ON or AUTO in either occupied or unoccupied conditions To acc...

Страница 7: ...e 8 8 Press UP or DOWN button to scroll through AUX HEAT screen choices W O LOCKOUT Auxiliary heat will activate regardless of compressor operation or outdoor air temperature factory default If W O LOCKOUT is chosen proceed to set delay on time Step 9 COMP LOCKOUT Compressor locks out below the selected outdoor air temperature Requires optional Bard 8403 061 Outdoor Air Temperature Sensor NONE No ...

Страница 8: ...TIONAL SETUP 7 The indoor blower can be set for ON or AUTO in either occupied or unoccupied conditions To access or change blower settings press DOWN button to scroll to FAN Press ENTER button to enter FAN SETUP see Figure 9 8 Press DOWN button to scroll through selections adjust as necessary Speeds Constant speed nonadjustable Off Delay 0 System fan will run for specified time after call ends 0 6...

Страница 9: ...ns use UP or DOWN buttons to scroll through choices AUTO factory default System is in Auto Changeover mode HVAC system will cycle heating and cooling automatically to stay within preset heating and cooling setpoints EMER HT Aux heat only Only available with unit type HP OFF HVAC system is inactive COOLING System is in Cooling Only mode HVAC system will cycle cooling in reference to cooling setpoin...

Страница 10: ... The controller will not allow heating cooling setpoints to contradict one another or to be within a degree of conflicting operation NOTE Any system startup with indoor ambient temperatures lower than 56 F or above 86 F or humidity higher than 65 will experience an internal Low Temperature or High Temperature alarm This will not affect normal operation and can be cleared easily Bard CompleteStat s...

Отзывы: