Sequence of Operation

Check for proper operation of the unit by energizing in 
cooling mode. The condenser fan motor should not run 
until the discharge pressure has exceeded 280 PSI. 
Should the liquid pressure fall below 180 PSI while 
running, the condenser fan motor will de-energize until 
the head pressure again builds to 280 PSI. Switch to 
heating mode. The condenser fan motor should run 
anytime the compressor is running regardless of the 

discharge pressure. Run unit through defrost cycle. 
The condenser fan motor should de-energize during the 
defrost cycle.

FIGURE 1

Unit Control Panel

MIS-4106

MULTIPLIER

RELAY

BLACK/WHITE WIRE TO C

BLACK WIRE TO RELAY

BLUE WIRE TO B

SCREWS

LOW AMBIENT CONTROL

CONNECT OD TEMP. SWITCH TO

TAB FROM MAIN WIRE HARNESS

PURPLE WIRE WITH INSULATED

(TERMINAL #1)

BLACK WIRES FOR LAC