manualshive.com logo in svg
background image

Manual 7960-860A
Page 

2 of 6

Installation

1.  Disconnect all power to the unit. 
2.  Remove outer and inner control panel covers, upper 

front panel and right-side condenser inlet grille.

3.  Mount 910-2011 relay assembly to control panel 

as shown in Figure 1 on page 3. Use phillips head 
screws included with kit to attach relay to control 
panel.

4.  Remove cover from vertical gray cable duct on 

control panel to allow wire harness from installed 
relay to route into it (see Figure 1).

NOTE:

 

The unit wiring diagram (included with unit 

literature assembly and also located on inner 

control panel cover) can be used to wire this 

kit. However, the following instructions listed 

here provide the necessary connections point-to-

point.

NOTE:

 

If this kit is being installed together with the 

outdoor thermostat kit, use the relay assembly 

supplied with the thermostat kit. Only the solid 

black wire and the multiplier will need used 

from the relay assembly in this kit.

5.  Locate black wire from the relay assembly and 

route through cable duct to defrost control logic 
board (see Figure 1). Before connecting this black 
wire to the NC fan relay contact on the defrost 
logic control board, remove wire that is currently 
connected there (on 230V models, it’s the black 
outdoor fan motor lead; on 460V models, red/black 
wire) and connect that wire to Terminal 3 on the 
installed relay.

6.  Locate black/white wire from relay assembly and 

route through cable duct to defrost control logic 
board. Connect black/white wire to C terminal. If 
the heat pump is a dehum unit, remove the black/
white wire already connected to the C terminal and 
stack it back onto the black/white wire from the 
relay assembly.

7.  Locate blue wire from relay assembly and route 

through cable duct to defrost control logic board. 
Connect blue wire to B terminal. Remove blue wire 
already connected to B terminal and stack it back 
onto the blue wire from the relay assembly.

8.  A service port is located on the refrigerant liquid 

line just above the liquid line filter drier (mounted 
to the outdoor fan shroud). This port is intended 
for the application of 8406-105 low ambient fan 
cycling switch (see Figure 2 on page 4). Remove 
the service cap from this service port and quickly 
thread the low ambient fan cycling switch onto 
this port. Once snug, use two wrenches to tighten 
the switch an additional 1/4 turn (one to hold 
the service port and one on the switch). Use soap 
bubbles to confirm the seal is completely tight on 
this connection.

9.  Install outdoor temperature switch assembly to the 

fan shroud and route the wires to the control panel 
as shown in Figure 2. This switch defeats Balanced 
Climate airflow whenthe temperature falls below 
50°F to help prevent evaporator freeze up. Refer to 
the unit installation manual for more information 
on Balanced Climate operation.

10. Install freeze protect thermostat to the evaporator 

coil as shown in Figure 3 on page 5. Route the 
wires down through the copper bushing and into 
the control panel with the blower motor wires.

11. Route the two black leads from the low ambient 

fan cycling switch up into the control panel with 
the other wires from this compartment, taking 
care to route and secure the wires. Use cable 
ties included with kit. Route the two black wires 
into the cable duct and then out the side of 
the cable duct towards the installed 910-2011 
relay. Connect these two wires to Terminal 1 and 
Terminal 3 of the relay (see Figure 4 on page 6).

12. Find the purple wire not connected to anything 

that is tucked in the cable duct (see Figure 1). 
Pull it out and connect it to the end of the outdoor 
temp switch wire that has an insulated 1/4" quick 
connect. Connect the other end of the outdoor 
temperature switch to the Y terminal on the defrost 
logic board for 1-phase units or on the phase 
monitor for 3-phase units. Refer to Figures 1 and 4 
and the unit wiring diagram.

13. Connect the freeze protect thermostat wires in 

line with the “Y” input signal to the defrost logic 
control.

 

For 1-phase units, connect the end with the 1/4" 
quick connect to Y terminal on the defrost logic 
control. Connect the other end with the 1/4" tab to 
the yellow/white wire coming from the low voltage 
terminal strip or to the orange/black wire coming 
from the low ambient bypass relay (if equipped) 
or to the yellow/black wire in units equipped with 
mechanical dehumidification. Refer to the unit 
wiring diagram. 

 

For 3-phase units, connect the wire end with the 
1/4" quick connect to “Y out” on the phase monitor 
and the other end with the 1/4" tab to the yellow/
black wire going to the defrost logic control.

14. Recheck wiring by referring to unit wiring diagram.
15. Apply “This unit equipped with CMH-34 control 

module” label to the inside of the inner control 
panel cover above the wiring diagram.

16. Replace all panels and covers. This completes the 

installation.

17. Turn on power to unit. Check for proper operation 

of the unit by referring to 

Sequence of 

Operation

.

Отзывы: