16. Attach terminal board label to terminal board.
17. Attach “CMA-40” label and wiring diagram to the 

inner control panel cover above the unit wiring 
diagrams.

18. Make low voltage connections from the DDC 

controller to the terminal board.

19. Install the blower access cover, control panel 

covers and heater access panel.

20. Apply power to unit
21. Turn the unit blower on.
22. Restrict the filter of the unit by 75%.
23. Adjust the filter switch until it trips.
24. Remove restriction and reset filter switch.
25. Install the service panel.