background image

Manual 2100-715B 

Page 

7 of 25

supply and/or return stub duct may be connected to the 
unit supply and return flanges before unit installation to 
help with duct connections inside the structure. Supply 
and return ducts must be properly sized for the design 
airflow requirement of the equipment. Air Conditioning 
Contractors of America (ACCA) is an excellent guide 
to proper sizing. All duct work or portions thereof not 
in the conditioned space should be properly insulated 
in order to conserve energy, reduce heat conductivity, 
and prevent condensation or moisture damage. Refer to 
Maximum External Static Pressure (ESP) of Operation 
– Electric Heat Only table on page 25. Design the 
duct work according to methods given by the Air 
Conditioning Contractors of America (ACCA). When 
duct work is installed in unheated spaces, it should 
be insulated with a minimum of 1" of insulation. Use 
insulation with a vapor barrier on the outside of the 
insulation. Flexible joints should be used to connect 
the duct work to the equipment in order to keep the 
noise transmission to a minimum. Ducts through the 
walls must be insulated and all joints taped or sealed to 
prevent air or moisture from entering the wall cavity.

Free Blow Applications

Some installations may not require extensive supply 
duct work throughout the structure and are referred 
to as free blow applications. A short field-fabricated 
supply duct must be used in the wall cavity to 
transition between the supply collar on the unit and 
the supply louver grille in the room. The duct must 
be properly insulated in order to conserve energy, 
reduce heat conductivity and prevent condensation or 
moisture damage. All joints must be taped or sealed to 
prevent air or moisture entering the wall cavity. Follow 
all clearances including distances to combustible 
materials and all instructions provided in this manual. 
A non-restrictive metallic supply air grille with 
deflectors is required for free blow applications. Contact 
the local Bard distributor or visit www.bardhvac.com for 
ordering information.
A metallic return air grille is required for non-ducted 
applications. The spacing between louvers on the grille 
shall not be larger than 5/8". It is recommended that a 
Bard Return Air Grille Kit is installed that is designed 
specifically for the wall mount product. Contact the 
local Bard distributor or visit www.bardhvac.com for 
ordering information. A field-supplied return grille 
that meets the 5/8" louver criteria and does not cause 
the unit to exceed the maximum specified external 
static pressure (ESP) may be used. If using a return 
air filter grille, filters must be of sufficient size to 
allow a maximum velocity of 400 fpm. Filter return 
air grilles do not filter air being brought into the 
structure through ventilation options including fresh air 
dampers, ventilators, economizers and energy recovery 
ventilators. Be sure to install the return grille with the 
louvers pointed downward towards the floor. This will 
help ensure return air is drawn upward from the floor 
and improve air circulation in the room.

NOTE:

  If no return air duct is used, applicable 

installation codes may limit this cabinet to 

installation only in a single story structure.

Thermostat or Indoor Temperature Sensor Placement

The location and installation of the thermostat or 
temperature sensor that monitors indoor temperature is 
very important regarding unit operation. Avoid placing 
the thermostat in an area exposed to direct sunlight 
or air from doorways leading outdoors. Use a piece 
of insulating material to close off conduit openings 
or holes in the wall surface for wire entry into the 
thermostat or temperature sensor. This will help avoid 
non-conditioned air from entering the thermostat 
and effecting temperature and/or humidity readings. 
As common practice, the thermostat or temperature 
sensor should measure the temperature of the air 
being returned to the unit, and not the conditioned 
air being supplied by the unit. Placing the thermostat 
or temperature sensor near a return air opening will 
normally result in optimal unit performance.

Unit Installation

Make sure to have the proper tools at the work site that 
are needed for unit installation. The following steps 
are provided to ensure the unit is installed properly to 
the wall surface, and that the unit will provide years of 
service with minimal service requirements.

Materials/Tools List

Additional hardware and miscellaneous supplies are 
needed for installation. These items are field supplied 
and must be sourced before installation. This list also 
includes tools needed for installation.

•  Appropriate safety gear including gloves and safety 

glasses

•  5/16" hex bit with drill driver
•  Phillips head screwdriver
•  Small straight (thermostat) screwdriver
•  Tape measure
•  Leveling device
•  One (1) tube of caulk and caulk gun
•  Utility knife
•  Tools for cutting holes in the wall surface (if 

needed)

•  Electrical components and wiring along with 

electrical tools

• Multimeter
•  Wall fasteners for side flanges and top rain 

flashing.

•  Duct tape and/or other duct sealing materials.

Содержание 11EER WA Series

Страница 1: ...11EER WA SERIES WALL MOUNT AIR CONDITIONER Models INSTALLATION INSTRUCTIONS W12AB A W12AB D Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 715B Supersedes 2100 715A Date 2 24 20 W12AB K ...

Страница 2: ... Short Cycle Delay on Break 18 Low Pressure Detection 18 High Pressure Detection 19 Test Mode 19 Brownout Protection with Adjustment 19 Pressure Service Ports 20 Service 21 Fan Blade Setting Dimensions 21 R 410A Refrigerant Charge 21 Setting Unit Airflow 24 Blower Speeds 24 Speed Tap 1 Balanced Climate 24 Speed Tap 2 Default Cooling Heating 24 Speed Tap 3 Optional HI Cooling Heating 24 FIGURES Fig...

Страница 3: ...g ACCA Manual J Residential Duct Design for Residential Winter and Summer Air Conditioning and Equipment Selection ACCA Manual D For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Teleph...

Страница 4: ...nd or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made accord...

Страница 5: ...n codes may limit this cabinet to installation only in a single story structure Filters A 1 throwaway filter is standard with each unit The filter slides into position making it easy to service This filter can be serviced from the outside by removing the service door A 2 pleated filters is also available as an optional accessory The internal filter brackets are adjustable to accommodate the 2 filt...

Страница 6: ... drainage A clear flexible PVC drain hose 3 4 ID 1 OD extends from the drain pan in the upper section of the unit and extends down to the unit base An opening is supplied towards the back of the unit base for the drain hose to pass through and the hose extends 1 to 2 below the unit base Water removed from the indoor air condensate will be expelled from the unit in large amounts during cooling oper...

Страница 7: ...e that meets the 5 8 louver criteria and does not cause the unit to exceed the maximum specified external static pressure ESP may be used If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm Filter return air grilles do not filter air being brought into the structure through ventilation options including fresh air dampers ventilators economi...

Страница 8: ...m bend into the rear bend of the unit top see Figure 3 3 Apply a liberal amount of caulk on left and right cabinet side wall mount brackets and back of top rain flashing Place unit back surface flush against wall Unit must be level to ensure proper condensate drainage 4 Units are secured to the wall by using field supplied fasteners along each side of the wall mount through the built in wall mount...

Страница 9: ...OLTAGE ELECTRICAL ENTRANCE BUILT IN RAIN HOOD 2 PITCH 1 50 48 00 21 88 14 63 CONDENSER AIR OUTLET HEATER FILTER ACCESS AIR VENTILATION CONDENSER AIRFLOW IS BLOW THRU 19 72 3 88 31 06 19 72 20 43 SHIPPING LOCATION ENTRANCE ELECTRICAL OPTIONAL TOP RAIN FLASHING DRAIN HOSE 22 25 25 750 10 00 5 00 5 00 17 00 30 13 32 00 2 50 MIS 3599 ...

Страница 10: ...PPLIED FOAM AIR SEAL WALL WALL STRUCTURE MIS 3600 FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION SUPPLY AIR DUCT RETURN AIR NOTE IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHIND THE SIDE MOUNTING OPENING WALL OPENING AND HOLE LOCATION VIEW 7 031 19 719 10 000 7 031 17 000 6 969 19 719 5 000 17 000 5 000 2 500 ...

Страница 11: ...tions RETURN AIR RETURN AIR OPENING OPENING DUCT SUPPLY AIR OPENING SUPPLY AIR OPENING CONCRETE BLOCK WALL INSTALLATION WOOD FRAME WALL INSTALLATION WALL STRUCTURE MOUNT ON UNIT SIDE VIEW OPENING WOOD OR STEEL SIDING RETURN AIR BEFORE INSTALLATION FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 3670 ...

Страница 12: ...Manual 2100 715B Page 12 of 25 FIGURE 6 Common Wall Mounting Installations ...

Страница 13: ...erating condition For low voltage wiring an 18 gauge copper color coded cable is recommended See Table 4 on page 14 for more information Low Voltage 24VAC Connections These units use a 24 volt AC low voltage circuit C terminal is the 24VAC common and is grounded G terminal is the indoor blower input Y1 terminal is the 1st Stage input for cooling Y2 terminal is the 2nd Stage compressor input for co...

Страница 14: ...Sensor w dehumidification Motion Sensor w Intelligent Learning Control BACnet compatible CS9B THOC 3 stage Cool 3 stage Heat Programmable Non Programmable HP or Conventional Auto or Manual Changeover Humidity Sensor w dehumidification CO2 Sensor Motion Sensor w Intelligent Learning Control BACnet compatible CS9BE THO 3 stage Cool 3 stage Heat Programmable Non Programmable HP or Conventional Auto o...

Страница 15: ...4 1 2 3 If not equipped with a ventilation option to plug in a jumper plug must be installed 2 5 2 Factory installed jumper Remove jumper and connect to N C fire alarm circuit if emergency shutdown required 5 4 control optional for ECON only see vent instruction manuals 0 10 VDC modulating C02 control signal for modulating ventilation 3 periods Must be configured for multi stage for Y1 output to b...

Страница 16: ...089 W C Rc Y R G O B to N C fire alarm circuit if emergency shutdown required If not equipped with a ventilation option to plug in a jumper plug must be installed TH311OD1040 8403 057 TH522OD1151 8403 058 5 4 6 7 3 Do not add these wires if setting up for modulating control See note 7 Thermostat will not work with units equipped with economizers 1 5 control Optional for ECON Only See vent installa...

Страница 17: ...nk as a liquid to avoid any fractionation and to ensure optimal system performance Refer to instructions for the cylinder that is being utilized for proper method of liquid extraction Safety Practices 1 Never mix R 410A with other refrigerants 2 Use gloves and safety glasses Polyol ester oils can be irritating to the skin and liquid refrigerant will freeze the skin 3 Never use air and R 410A to le...

Страница 18: ...ced Climate is not a replacement for a dehumidification hot gas reheat unit for extreme applications but rather an enhancement feature for limited climates and applications Vent Connection Plug All units are equipped with a vent connection plug in the side of the control panel for the different ventilation packages to plug in to If the compressor will not start and there is no Y1 at the compressor...

Страница 19: ...g The conditions needed for the unit to enter test mode are as follows POT must start at a time less than or equal to the 40 second mark The POT must then be rapidly rotated to a position greater than or equal to the 280 second mark in less than second Normal operation will resume after power is reset or after the unit has been in test mode for at least 5 minutes Brownout Protection with Adjustmen...

Страница 20: ...or units switches from utility power to generator power With slower transfer switches the time delay between the utility power and generator power didn t cause a problem The units lost power shut off and came back on line normally With the introduction of almost instantaneous transfer switches the millisecond long power glitch can be enough that the compressor will start to run backwards In this s...

Страница 21: ...eadings this information should only be used by certified technicians as a guide for evaluating proper system performance They shall not be used to adjust charge If charge is in doubt reclaim evacuate and recharge the unit to the serial plate charge A AIRFLOW MIS 1724 Model Dimension A W12AB 2 25 Fan Blade Setting Dimensions Shown in Figure 10 is the correct fan blade setting for proper air delive...

Страница 22: ...system evacuated and recharged to serial plate charge weight NOTE Pressure table based on high speed condenser fan operation If condensing pressures appear elevated check condenser fan wiring See Condenser Fan Operation Operating at these conditions would be outside the compressor operating envelope and is not recommended Model Return Air Temp DB WB Pressure 75 80 85 90 95 100 105 110 115 120 125 ...

Страница 23: ...duit the conductors must be derated Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three current carrying conductors are in a raceway IMPORTANT While this electrical data is presented as a guide it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all local codes MODEL...

Страница 24: ...hermostat or other controlling device Multiple motor speed taps may be energized simultaneously by 24VAC power during different modes of operation The highest number speed tap energized takes priority with 3 being the highest and 1 being the lowest See Table 10 for the corresponding blower speeds with the different modes of operation Speed Tap 1 Balanced Climate Speed tap 1 is set as a lower than ...

Страница 25: ... Optional HI Cooling Heating Speed Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil W12AB B W12AB D 0 00 330 325 465 460 545 525 0 10 315 305 450 435 495 470 0 15 305 290 435 420 465 445 0 20 285 270 415 400 440 415 0 25 260 250 395 380 410 390 0 30 375 355 380 360 0 40 315 305 320 305 0 50 245 245 255 245 W12AB K 0 00 335 320 455 450 510 505 0 10 295 280 450 435 525 505 0 15 270 255 435 420 ...

Отзывы: