background image

Manual 2100-715B 

Page 

6 of 25

INSTALLATION

Basic Installation Design and 

Application Planning

Successful unit installations require proper planning 
and site inspection before installation begins. Before 
installing the wall mount unit, make sure that all 
service and airflow clearances are met and that the 
unit can meet all applicable code and regulation 
requirements. Provide an inspection of both the inside 
and outside of the structure by reviewing floorplans 
and/or visiting the installation site.

Wall Construction

The wall must be inspected to ensure that the weight 
of the unit can be supported. Be sure to review all 
applicable construction codes and regulations including 
seismic requirements. When inspecting wood frame 
walls, the wall construction must be strong and 
rigid enough to carry the weight of the unit without 
transmitting any unit vibration. It is important that 
the side unit wall mounting lags and optional bottom 
bracket are supported by structural members inside 
the wall cavity. Concrete block and brick walls must be 
thoroughly inspected to ensure that they are capable 
of carrying the weight of the installed unit. Metal 
buildings must contain structural components to 
support the unit weight. If heavily corrugated siding 
is present, it may need to be trimmed and flashed to 
provide a flat, even surface to attach and seal the unit 
to the wall.

Outdoor Area Inspection

Inspect the outdoor area of the jobsite or review 
construction plans and locate the area where the wall 
mount is to be installed. The outdoor area must be 
free from obstructions including fences, bushes and 
walls that will hinder unit operation regarding outdoor 
condenser airflow and unit serviceability. Do not 
install units in enclosed areas that limit the amount 
of ambient temperature airflow. Warm air will exit 
the front condenser section of the unit, and outdoor 
ambient temperature air must be able to enter side 
intake condenser openings of the unit. Portable or 
modular building placement must be in a way that the 
wall mount units have a constant supply of outdoor air 
for proper unit operation. Make sure that the service 
panels of the unit are accessible. Inspect wall surfaces 
for obstructions that could hinder unit installation 
and servicing including outdoor electrical conduits, 
junction boxes, wall drains, vent hoods, windows, doors, 
overhangs and posts.

Condensate Water Drainage

Review all codes and requirements for unit condensate 
drainage. A clear, flexible PVC drain hose (3/4" ID, 1" 
OD) extends from the drain pan in the upper section of 

the unit and extends down to the unit base. An opening 
is supplied towards the back of the unit base for the 
drain hose to pass through, and the hose extends 1" 
to 2" below the unit base. Water removed from the 
indoor air (condensate) will be expelled from the unit 
in large amounts during cooling operation through the 
hose. Units running in cooling operation in cold outdoor 
below freezing conditions can cause the condensate 
to freeze after leaving the drain hose. In the event the 
drain hose is connected to a drain system of some type, 
it must be an open or vented type system to ensure 
proper drainage throughout seasonal use.

Indoor Ducted and Non-Ducted 

Applications

Air distribution inside the structure being conditioned 
plays an important role in making sure the area is 
a consistent temperature. Improper air distribution 
can result in areas being cooler or warmer, electrical 
equipment not receiving sufficient airflow or occupancy 
discomfort felt inside an area. Thermostat or indoor 
temperature sensor placement inside the area being 
conditioned also plays an important role in indoor 
climate control.

Indoor Supply Airflow

Indoor installation areas must provide a non-restrictive 
path for the conditioned supply air to leave supply 
grilles and registers. Inspect the area to ensure that all 
indoor portions of the room or rooms will have access 
to supply air. Ductwork may be used to ensure proper 
air circulation and all provided ductwork guidelines and 
clearances must be followed. Non-ducted applications 
must use a supply louver grille installed over the supply 
opening inside the room. Be sure to adjust supply 
deflectors to properly disperse the conditioned supply 
air to all parts of the room. Avoid closing sections of 
the supply grilles which would cause unneeded supply 
duct pressurization.

Indoor Return Airflow

A non-restrictive path for room air returning to the 
center section of the unit must be provided inside 
the room. Avoid placing objects including furniture, 
electronics equipment, equipment racks and cabinets 
directly in front of the unit return grilles and registers. 
Bard recommends at least 2' between solid objects 
and return grilles or registers. Ductwork may be used to 
ensure proper air circulation and all provided ductwork 
guidelines and clearances must be followed. Non-
ducted applications must use a return louver grille 
installed over the return opening inside the room. 

Ducted Applications

Field fabricated supply and return duct work may be 
installed inside the structure being conditioned. A short 

Содержание 11EER WA Series

Страница 1: ...11EER WA SERIES WALL MOUNT AIR CONDITIONER Models INSTALLATION INSTRUCTIONS W12AB A W12AB D Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 715B Supersedes 2100 715A Date 2 24 20 W12AB K ...

Страница 2: ... Short Cycle Delay on Break 18 Low Pressure Detection 18 High Pressure Detection 19 Test Mode 19 Brownout Protection with Adjustment 19 Pressure Service Ports 20 Service 21 Fan Blade Setting Dimensions 21 R 410A Refrigerant Charge 21 Setting Unit Airflow 24 Blower Speeds 24 Speed Tap 1 Balanced Climate 24 Speed Tap 2 Default Cooling Heating 24 Speed Tap 3 Optional HI Cooling Heating 24 FIGURES Fig...

Страница 3: ...g ACCA Manual J Residential Duct Design for Residential Winter and Summer Air Conditioning and Equipment Selection ACCA Manual D For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Teleph...

Страница 4: ...nd or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See page 3 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made accord...

Страница 5: ...n codes may limit this cabinet to installation only in a single story structure Filters A 1 throwaway filter is standard with each unit The filter slides into position making it easy to service This filter can be serviced from the outside by removing the service door A 2 pleated filters is also available as an optional accessory The internal filter brackets are adjustable to accommodate the 2 filt...

Страница 6: ... drainage A clear flexible PVC drain hose 3 4 ID 1 OD extends from the drain pan in the upper section of the unit and extends down to the unit base An opening is supplied towards the back of the unit base for the drain hose to pass through and the hose extends 1 to 2 below the unit base Water removed from the indoor air condensate will be expelled from the unit in large amounts during cooling oper...

Страница 7: ...e that meets the 5 8 louver criteria and does not cause the unit to exceed the maximum specified external static pressure ESP may be used If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm Filter return air grilles do not filter air being brought into the structure through ventilation options including fresh air dampers ventilators economi...

Страница 8: ...m bend into the rear bend of the unit top see Figure 3 3 Apply a liberal amount of caulk on left and right cabinet side wall mount brackets and back of top rain flashing Place unit back surface flush against wall Unit must be level to ensure proper condensate drainage 4 Units are secured to the wall by using field supplied fasteners along each side of the wall mount through the built in wall mount...

Страница 9: ...OLTAGE ELECTRICAL ENTRANCE BUILT IN RAIN HOOD 2 PITCH 1 50 48 00 21 88 14 63 CONDENSER AIR OUTLET HEATER FILTER ACCESS AIR VENTILATION CONDENSER AIRFLOW IS BLOW THRU 19 72 3 88 31 06 19 72 20 43 SHIPPING LOCATION ENTRANCE ELECTRICAL OPTIONAL TOP RAIN FLASHING DRAIN HOSE 22 25 25 750 10 00 5 00 5 00 17 00 30 13 32 00 2 50 MIS 3599 ...

Страница 10: ...PPLIED FOAM AIR SEAL WALL WALL STRUCTURE MIS 3600 FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION SUPPLY AIR DUCT RETURN AIR NOTE IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHIND THE SIDE MOUNTING OPENING WALL OPENING AND HOLE LOCATION VIEW 7 031 19 719 10 000 7 031 17 000 6 969 19 719 5 000 17 000 5 000 2 500 ...

Страница 11: ...tions RETURN AIR RETURN AIR OPENING OPENING DUCT SUPPLY AIR OPENING SUPPLY AIR OPENING CONCRETE BLOCK WALL INSTALLATION WOOD FRAME WALL INSTALLATION WALL STRUCTURE MOUNT ON UNIT SIDE VIEW OPENING WOOD OR STEEL SIDING RETURN AIR BEFORE INSTALLATION FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 3670 ...

Страница 12: ...Manual 2100 715B Page 12 of 25 FIGURE 6 Common Wall Mounting Installations ...

Страница 13: ...erating condition For low voltage wiring an 18 gauge copper color coded cable is recommended See Table 4 on page 14 for more information Low Voltage 24VAC Connections These units use a 24 volt AC low voltage circuit C terminal is the 24VAC common and is grounded G terminal is the indoor blower input Y1 terminal is the 1st Stage input for cooling Y2 terminal is the 2nd Stage compressor input for co...

Страница 14: ...Sensor w dehumidification Motion Sensor w Intelligent Learning Control BACnet compatible CS9B THOC 3 stage Cool 3 stage Heat Programmable Non Programmable HP or Conventional Auto or Manual Changeover Humidity Sensor w dehumidification CO2 Sensor Motion Sensor w Intelligent Learning Control BACnet compatible CS9BE THO 3 stage Cool 3 stage Heat Programmable Non Programmable HP or Conventional Auto o...

Страница 15: ...4 1 2 3 If not equipped with a ventilation option to plug in a jumper plug must be installed 2 5 2 Factory installed jumper Remove jumper and connect to N C fire alarm circuit if emergency shutdown required 5 4 control optional for ECON only see vent instruction manuals 0 10 VDC modulating C02 control signal for modulating ventilation 3 periods Must be configured for multi stage for Y1 output to b...

Страница 16: ...089 W C Rc Y R G O B to N C fire alarm circuit if emergency shutdown required If not equipped with a ventilation option to plug in a jumper plug must be installed TH311OD1040 8403 057 TH522OD1151 8403 058 5 4 6 7 3 Do not add these wires if setting up for modulating control See note 7 Thermostat will not work with units equipped with economizers 1 5 control Optional for ECON Only See vent installa...

Страница 17: ...nk as a liquid to avoid any fractionation and to ensure optimal system performance Refer to instructions for the cylinder that is being utilized for proper method of liquid extraction Safety Practices 1 Never mix R 410A with other refrigerants 2 Use gloves and safety glasses Polyol ester oils can be irritating to the skin and liquid refrigerant will freeze the skin 3 Never use air and R 410A to le...

Страница 18: ...ced Climate is not a replacement for a dehumidification hot gas reheat unit for extreme applications but rather an enhancement feature for limited climates and applications Vent Connection Plug All units are equipped with a vent connection plug in the side of the control panel for the different ventilation packages to plug in to If the compressor will not start and there is no Y1 at the compressor...

Страница 19: ...g The conditions needed for the unit to enter test mode are as follows POT must start at a time less than or equal to the 40 second mark The POT must then be rapidly rotated to a position greater than or equal to the 280 second mark in less than second Normal operation will resume after power is reset or after the unit has been in test mode for at least 5 minutes Brownout Protection with Adjustmen...

Страница 20: ...or units switches from utility power to generator power With slower transfer switches the time delay between the utility power and generator power didn t cause a problem The units lost power shut off and came back on line normally With the introduction of almost instantaneous transfer switches the millisecond long power glitch can be enough that the compressor will start to run backwards In this s...

Страница 21: ...eadings this information should only be used by certified technicians as a guide for evaluating proper system performance They shall not be used to adjust charge If charge is in doubt reclaim evacuate and recharge the unit to the serial plate charge A AIRFLOW MIS 1724 Model Dimension A W12AB 2 25 Fan Blade Setting Dimensions Shown in Figure 10 is the correct fan blade setting for proper air delive...

Страница 22: ...system evacuated and recharged to serial plate charge weight NOTE Pressure table based on high speed condenser fan operation If condensing pressures appear elevated check condenser fan wiring See Condenser Fan Operation Operating at these conditions would be outside the compressor operating envelope and is not recommended Model Return Air Temp DB WB Pressure 75 80 85 90 95 100 105 110 115 120 125 ...

Страница 23: ...duit the conductors must be derated Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three current carrying conductors are in a raceway IMPORTANT While this electrical data is presented as a guide it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all local codes MODEL...

Страница 24: ...hermostat or other controlling device Multiple motor speed taps may be energized simultaneously by 24VAC power during different modes of operation The highest number speed tap energized takes priority with 3 being the highest and 1 being the lowest See Table 10 for the corresponding blower speeds with the different modes of operation Speed Tap 1 Balanced Climate Speed tap 1 is set as a lower than ...

Страница 25: ... Optional HI Cooling Heating Speed Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil W12AB B W12AB D 0 00 330 325 465 460 545 525 0 10 315 305 450 435 495 470 0 15 305 290 435 420 465 445 0 20 285 270 415 400 440 415 0 25 260 250 395 380 410 390 0 30 375 355 380 360 0 40 315 305 320 305 0 50 245 245 255 245 W12AB K 0 00 335 320 455 450 510 505 0 10 295 280 450 435 525 505 0 15 270 255 435 420 ...

Отзывы: