CHECk GAS TYPE
Use only natural gas. If your gas supply is not
natural gas, you must install ON/OFF Safety
Valve/Pilot Kit (see
Accessories
, page 17).
Call dealer where you bought log set.
If the fireplace does not have a gas supply
shutoff valve, one must be installed.
VENTING SPECIFICATIONS FOR
INSTALLATION
The fireplace chimney flue and vent must be
drafting properly. To check the vent for proper
drafting: Light a tightly rolled newspaper on
one end and place it at the inside front edge
of the fireplace. Observe the smoke and be
sure the vent is properly drawing it up the
chimney. If the smoke spills out into the room,
extinguish the flame and remove any obstruc-
tion until proper venting is achieved.
The chimney flue must remain open a mini-
mum of 3" at all times during the operation
of this log set.
INSTALLING DAMPER CLAMP
Secure the damper stop clamp provided to
the leading edge of the damper as shown in
Figure 3. If for any reason this clamp doesn't
work on your fireplace, another suitable clamp
or permanent stop must be installed or the
damper blade must be cut or removed.
INSTALLATION
Continued
Figure 3 - Attaching Damper Clamp
CONNECTING TO GAS SUPPLY
WARNING: A qualified ser
-
vice person must connect log
set to gas supply. Follow all
local codes.
Installation Items Needed
Before installing log set, make sure you have
the items listed below.
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve
• test gauge connection
• adjustable (crescent) wrench or pliers
• sediment trap
• tee joint
• pipe wrench
CAUTION: Use only new,
black iron or steel pipe. Inter
-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of
1/2" diameter or greater to allow
proper gas volume to log set. If
pipe is too small, undue loss of
volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from log set (see
Figure 4).
Figure 4 - Gas Connection
* Purchase the optional CSA design-certified
equipment shutoff valve from your dealer.
** Minimum inlet pressure for purpose of input
adjustment.
3" Minimum
Sediment Trap
From Gas
Meter
(5" W.C.** to
10.5" W.C.
Pressure)
CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*
Approved
Gas Hose
Cap Pipe Tee
Nipple Joint
Damper
Damper
Clamp
Damper
Manufactured Fireplace
Masonry Fireplace
Damper
Clamp
Damper