PKT-GD/GS-IM-DE-B-EN-09-19 Rev.0
25
5. Installation
WARNING
Installation works
There is a risk of injury if this prod-
uct is not properly installed, disas-
sembled and put into operation.
•
Make sure the personnel has received
the appropriate training.
•
Observe the safety instructions in
„Chapter 2. Safety“.
NOTE
Check the technical parameters, in par-
ticular pressure and temperature, and the
electrical voltage of the control valve be-
fore installing or commissioning the rotary
actuator.
The piping system and control system must
be installed properly.
Make sure the valve is moving in the cor-
rect direction of rotation. Always mount
the valves into the pipeline without tensing
them.
The valve is not designed to absorb addi-
tional pipe connection forces. In the case of
large valves, it is recommended to support
the pipeline.
5.1 Installation conditions
The minimum space requirement can be
found in the dimension drawing or dimen-
sion table (
„Chapter 1. Annex / Technical
data“).
5.2 Before installation
Observe the following points before instal-
lation:
•
The dew point of the control medium
must be min. 10 °C lower than the low-
est operating temperature! The max.
temperature of the control medium is
45 °C!
•
The rotary actuator is not suitable for
accepting external lateral forces on the
pinion as well as for permanent torsional
vibrations in the end positions.
•
When operating valves, considerable
kinetic energy can be generated which
is transmitted to the actuator. The
user must ensure that the rotary actu-
ator is adequately protected and that
the below-mentioned switching times
for soft-sealing flaps and standard ball
valves for pure 90° rotary movement are
not exceeded.
The following minimum switching times for
the rotary movement of 90° must be ob-
served:
Type (GD/GS)
Switching times
032 till 063
0,3 sec
075 till 125
0,7 sec
140 till 210
1,0 sec
240 till 400
2,0 sec
Tab. 5-1 bar-agturn minimum times for the
rotary movement of 90°
The switching time can be reduced and ad-
justed by using silencers or throttle plates
from our range of accessories.
We recommend hydraulic damping for criti-
cal applications.
For other valve types, in particular large-vol-
ume valves with low torque requirement, the
Содержание agturn PKT Series
Страница 1: ...3 2 way automatic valve of PKT type Translation of the original operating manual bar gmbh de...
Страница 38: ...38 PKT GD GS IM DE B EN 09 19 Rev 0 12 EU Declaration of Incorporation...
Страница 43: ...PKT GD GS IM DE B EN 09 19 Rev 0 43...
Страница 49: ...49 Notes...
Страница 50: ...50 Notes...
Страница 51: ...51 Notes...