Duct and Outside Air Humidity (H200-H300) 

4 to 20mA or 0 to 5V Humidity Output with Optional Temperature Sensor

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

9938_ins_hum_temp_duct_out_5_20

3 of 4

rev. 02/15/18

Specifications subject to change without notice.

 Specifications

Power:

   10 to 35 VDC  

For 0 to 5 VDC or 4 to 20 mA Humidity Outputs 

   12 to 27 VAC 

For 0 to 5 VDC Humidity Output

Power Consumption:

 

   22 mA max. DC  

For 0 to 5 VDC or 4 to 20 mA Humidity Outputs 

   0.53 VA max. AC  

For 0 to 5 VDC Humidity Output 

Sensor:

  

Factory corrected @17 RH points (10 to 90% RH)

   Humidity 

Capacitive Polymer

   RH Accuracy  

±2% @ 73°F (23°C) from 10 to 90%

   Drift   

0.5% per year

   Response time 

< 5 seconds in moving air 

   RH Linearity 

Negligible, factory corrected linear from 10 to 90% 

   RH Hysteresis   

Factory corrected to <1%  

   Opt. Temp. 

Passive RTD or Thermistor

Filter:   

80 micron sintered stainless steel filter

Calibrated Accuracy:  

Calibration @17 RH points, (10% to 90%)  

   RH 2% 

2% from 10 to 90% @ 73°F (23°C), Non-condensing

   RH 3% 

3% from 10 to 95% @ 73°F (23°C), Non-condensing

   Thermistor 

±0.36ºF (0.2ºC) from 32 to 158ºF (0 to 70ºC) - High accuracy units are available

   RTD  

±0.55ºF (0.31ºC) @ 32ºF (0ºC) - High accuracy units are available

Output:  

Selectable via wiring detail

   Humidity 

0 to 5VDC or 4 to 20mA at 0 to 100% RH

   Opt. Temp. 

Resistance RTD or Thermistor

Humidity Output Impedance:

 

   Current  

700

W

@ 24VDC, Voltage drop is 10VDC

 

   

(Supply Voltage DC – Transmitter voltage drop 10VDC) / 0.02 Amps = Max load Impedance

   Voltage 

10K

W

Probe Length:

   Duct  

5.3” (13.5cm) Duct Insertion, 1” diameter

  Outside Air 

2.4” (6.1cm) Below Enclosure, 1” diameter

Dimensions:

  

W x H x D 

   Weatherproof (WP)  

2.75” x 4.5” x 2.2”, (70 x 114 x 55 mm) 

   Weather Tight (EU)  

4.1”x 3.8” x 2.1”, (105 x 97 x 54 mm) 

   BAPI-Box (BB)  

4.15” x 5” x 2.5”, (105.4 x 127 x 63.5mm) 

   BAPI-Box 2 (BB2)  

4.9” x 2.8” x 2.35”, (124.8 x 71.6 x 59.7mm)

Termination:

  

Open wire

   Crimp  

18 to 26 AWG  with Sealant Filled Crimp Connector (BA/SFC1000-x00)

   Wire Nut 

26 to 16 AWG with Sealant Filled Wire Nut (BA/SFC2000-x00)

Enclosure Material:

   Weatherproof (WP) 

Cast Aluminum

   Weather Tight (EU) 

ABS plastic, UV resistant

   BAPI-Boxes (BB, BB2)  Polycarbonate, UV resistant

Enclosures Ratings:

   Weatherproof (WP) 

NEMA-3R

   Weather Tight (EU) 

IP66, UL94V-0

   BAPI-Boxes (BB, BB2)  NEMA-4, IP66, UL94V-0

Environmental Operation Range:

 -40º to 158ºF (-40º to 70ºC) • 0% to 100% RH