background image

Door Monitor Alarm (DMA)

rev. 09/02/21

47290_ins_BAPI_DMA

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

 Installation & Operations

4 of 4

Operation continued...

Audible annunciator Reset Interval - 0 min or 5 min RESET 

(Position 2 of DIP Switch S2)

When set to 0 min RESET, the audible annunciator timer resets immediately 

after the door is closed. This essentially means that there is no waiting 

period before you should open the door again. The audible annunciator will 

not sound again unless the door is opened for longer than the Door Timer 

Interval rotary switch setting.
When set to 5 min RESET, the audible annunciator timer will not reset until 

the door has been closed for more than 5 minutes. This means that if the 

door has been open for longer than the Door Timer Interval rotary switch 

setting and the audible annunciator sounds, then closing the door will silence 

the audible annunciator BUT NOT reset the audible annunciator timer. The 

audible annunciator will immediately 

sound if the door is opened any time 

within the next 5 minutes. Each time the 

door is opened during this period, a new 

5 minute “count down” period is started. 

The Door Status LEDs will change to 

green once the 5 minute period has 

expired.

Door Timer Interval - SECONDS or 

MINUTES

(Position 3 of DIP Switch S2)

Normal operation is set to “OFF” - MINUTES. For a quick confidence test, this switch can be set to SECONDS by 

placing it to the “ON” position. This means that the audible annunciator will sound after 1 to 30 seconds (depending on 

the rotary switch settings) rather than 1 to 30 minutes. This switch also changes the audible annunciator Reset Interval 

from minutes to seconds (5 min RESET now equals 5 secs RESET).

Operational Test - OPERATE or TEST 

(Position 4 of DIP Switch S2)

Used to test all of the output combinations of the DMA. 

NOTE: The test mode disables door monitoring.

1. Set DIP switch (S2) to TEST.

2. Set rotary switch (S1) to the positions in the Operational Chart above to confirm that the unit’s output matches those 

listed in the table.

3. Return the unit to normal operation by setting DIP switch to OPERATE and rotary switch (S1) to its intended time.

Rotary Switch 

(S1) Position 

Power 

LED 

Both Relay 

LEDs 

Both 

Relays 

Door Status 

LEDs 

Audible 

Annuciator 

1 min 

On 

Off 

De-energized 

Solid green 

Silent 

5 min 

On 

On 

Energized 

Flashing amber 

Silent 

10 min 

On 

On 

Energized 

Flashing red 

Sounding 

15 min 

On 

Off 

De-energized 

Solid amber 

Silent 

20 min 

On 

Off 

De-energized 

Solid red 

Silent 

25 min 

On 

Off 

De-energized 

All off 

Silent 

 

Operational Chart

Fig. 5:

 DIP Switches (S2)

 

Diagnostics

Possible Problems:

 

Power LED (PWR1) does not light

Door Status LEDs indicate the 

wrong status

Door Status LEDs do not change

Door Status LEDs do not come on

Possible Solutions:

Confirm that there is 24 VAC/VDC at connector TB1 and that the polarity is 

correct.

Make sure that the unit is in Operate mode, not Test mode (DIP Switch S2).

Confirm that the door switch is wired as a Normally Closed (NC) connection. 

(A closed door equals an open circuit.)
Check for loose or shorted wires at the Door Switch connection.

Make sure that the unit is in Operate mode, not Test mode (DIP Switch S2).

Confirm that the unit is powered correctly. Power LED should be on.

Make sure that the unit is in Operate mode, not Test mode (DIP Switch S2).

Run the Operational Test described above to confirm that the LEDs, relays or 

audible annunciator are not burned out.

Отзывы: